Toshiba G8000 Series installation manual Control Wires, External Connections

Page 37

11.5 Control Wires

The terminal layout of control wires at TB1 is shown in Table 11.10.

Table 11.10 External Connections

No.

I/O

Signal Name

Operation

1

Output

Low Battery

Close at Low Battery

2

Output

Backup Operation

Close while Backup Operation

3

Output

Fault

Close by Faults

4

Output

Inverter Supply

Close during Normal Operation

5

Output

Warning

Close by Warnings

6

Input

P24

 

7

Input

Remote Run

Close to run UPS

8

Input

P24

 

9

Input

Remote Stop

Close to stop UPS

10

Output

Bypass Supply

Close during Bypass Operation

11

Output

Output Signal Ground

(Ground for pin #1~5 & #10)

12

Input

P24

Battery’s

13

Input

Battery Overheat

Overheat B-contact

14

Output

 

Bypass Breaker

15

Output

52C Trip Signal

Shunt Trip Signal by EPO

16

Output

 

Battery Breaker shunt trip

17

Output

72B Trip Signal

by EPO or Battery shutdown

18

Output

 

Battery breaker’s

19

Output

72B Aux. Contact

Auxiliary A-contact

The UPS, the battery cabinet, and the bypass breaker should be wired as shown in Figure 11.7.

Jumper wire if battery

Power source

OH is not applied.

 

TC

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

To Bypass

Bypass Breaker

 

 

Input

10

 

 

 

 

 

11

 

 

 

12

 

 

 

13

 

Power source

 

14

 

 

 

for trip coil

 

15

 

 

 

 

 

16

 

 

 

17

 

 

TC

18

 

 

19

To DC

Overheat

 

 

B-contact

 

TB1

Input

 

 

 

 

Auxiliary A-

 

 

 

contact

< UPS Cabinet >

 

< Battery Cabinet >

Figure 11.7 - Connection among UPS, battery cabinet & bypass breaker

36

Image 37
Contents Document Number February Introduction Uninterruptible Power Supply Contacting Toshiba’s Customer Support Center Manual’s Purpose and ScopeGeneral Safety Instructions Important Safety Instructions Safety Precautions Prohibited General Terms Do not remove the rear/side panelsAvoid vibration or shock exceeding 0.5G to the UPS Installation PrecautionsUPS Installation Environment Standard Do not install the UPS close to a water source Keep the UPS room cleanKeep the specified clearance around the UPS Mandatory Connect ground wire to the earth ground terminal onlyLocations of the Warning Labels 100/125 kVA Locations of the Warning Labels 150/180/225 kVA AC Input Grounding Electrode Terminal Contents 100/125kVA UPS Exterior dimensions front & right side Dimensions and Weight150/180/225kVA UPS Exterior dimensions front & right side 250/300kVA UPS Exterior dimensions front & right side Avoid vibration or shock exceeding 0.5 G to the UPS TransportationDo not expose the UPS to water Transportation by a craneAngle more than Transportation by a forklift Storage Ensure that there is adequate working space around InstallationPoints to be observed UnpackingUPS Clearance Anchor bolt tightening Anchor boltsOverview External Wiring DiagramPhase 3-wire Phase 4-wire Terminal Blocks and Power CablesRecommended Cable Size and Tightening Torque for 125kVA UPS Recommended Cable Size and Tightening Torque for 180kVA UPS Phase 3-wire Phase 4-wire Recommended Cable Size and Tightening Torque for 250kVA UPS Ilsco External Breaker Rating External Breakers100~225kVA 250/300kVA Grounding Wire10 External Connections Control WiresRecommended configuration with input neutral grounded Grounding configurationRecommended configuration with delta-input Grounding configuration without input neutral12 Grounding configuration with corner-grounded delta-input Grounding configuration with corner-grounded delta-input