4 |
Where the Background Window Time is the time in milliseconds that you should set the background window timer. The other elements in the formula are described above in the calculation for words per sweep. The constants (F and C) are for the CPU 780.
Background Window Time =
448 0 x (100 + 176 x 0.0008 x 2)
(120000 ± 4480)
Background Window Time = 3.9 rounded up to 4 ms
Miscellaneous Operation Information
Timer and PID FunctionBlocks
These function blocks will remain in lock step between the two synchronized units provided:
A.Enabling logic is identical on both units. This includes power flow, frequency of calling
B.The
C.Reference registers (3 for timers, 40 for PID) and reset references are copied from the unit that was in
For example, if the following ladder logic is identical in
%M100
±±±±] / [±±±±±±±±±±± TMR 1.00s
%L10 ± PV CV %R250
%M100
±±±±±±±±±±±±±±±±±±±( )
± %L20
Timed Contacts
When both systems are synchronized, timed contacts will have exactly the same value in both units. That is, whenever T_SEC is on in one unit, it will also be on in the other unit as long as both units are synchronized.
OVR_PRE %S Reference
The OVR_PRE %S reference which indicates whether one or more overrides is active is not supported by the CPU 780. This reference should not be used in a redundancy system.
70 | Series |
|