Bosch Appliances MIC400AL Connecting the MIC400 to the PC, Connecting the Greenwich Adaptor

Page 27

MIC400 Series Camera Installation and Operation Manual

16.LED 5 illuminates when the IR supply is selected to on by the camera telemetry.

17.LED 6 Pulses on/off when the MIC400 camera is correctly configured to operate with the IR power supply.

18.Please see the section on commissioning MIC400 Power Supplies for details on commissioning and setting up alarms.

19.When satisfied the PSU is functioning correctly, re-attach the enclosure lid & screw down until tight.

Commissioning the IR lamps

The following instructions apply to all MIC400IR cameras; please connect to a PC via RS422/485 telemetry and Universal Camset as shown on the next page, before applying power to the power supply check that all connections are correct.

Apply power to the unit and ensure that the 2 Red LEDs at the top of the PCB (under R1) and the +5v LED (LED4) are all on. This confirms that Fuses FS1, 2, 3, and 5 are intact.

Check that the MIC400 is generating a video picture.

Once connected set the camera current address in CamSet and check that the camera can be moved using the pan, tilt and stop buttons.

EN 27

CHAPTER 4 Configuring the MIC400 Camera

Connecting the MIC400 to the PC

The MIC can be connected to a PC’s serial port via a RS232/RS422 adaptor unit; this will generally be assigned to Comm Port 1.

Suitable serial port adaptor units are the Greenwich RS232/RS422 adaptor unit (Farnell 778-758, RS No: 201-758), the KK systems K2-ADE RS232 to RS485/422 adaptor or the MIC-USB485CVTR (485 to USB Converter) for PC’s without a serial port.

Connecting the Greenwich Adaptor

To connect the Greenwich serial adaptor to the PC you will also need a 9 pin D female to 25 pin D male RS232 compatible adaptor cable. A suitable cable is Farnell 960-573 or RS Part No: 202-644.

The adaptor should be set to DCE mode and the power supply connected.

Connections from the Greenwich adaptor to the MIC400 power supply are as follows:

Table N – Connecting the Greenwich Adaptor

The IR lamps selection is enabled by entering the Setups tab and setting the Multi Alarm mode on and Auto IR on. The PSU board LED should start flashing (LED 6) called PIC OK to indicate correct operation.

Adaptor Connections

F 778-758.

DATA OUT 6-3+

DATA OUT 5-4-

SCREEN

DATA IN 4-5-

DATA IN 3-6+

HD4

Connection and wire

colour.

RXB White

RXA Yellow

0v

TXA Blue

TXB Violet

Bosch Security Systems

Issue 1

Image 27
Contents MIC400 PTZ Camera Series MIC400 PTZ Camera Series Introduction Safety Precautions Important Safety Instructions Reference MIC-12PSU MIC-240PSUMIC-115PSU MIC-24PSUMIC-BP4 MIC-WKTMIC-ALM MIC-BP3Unpacking Packaging ContentsInstallation Environment Key to MIC-PMB drawing Installation Instructions Associated Equipment & Typical InstallationsUnderwater Installation Earthing of the MIC400 cameraLightning Protection MIC-240PSU, MIC-24PSU and MIC-115 PSU NON-IR Power Supply UnitsElectrical Connections Table a MIC Composite Cable Pin tablePower Supply Layout and Connections Table B Power Connection to Header HD1PCB Earth Link HD3 HD4HD5 Rating for Primary Bi-phase cards etcMIC-12PSU Power Supply Unit Table G Power Input wiring connections for MIC-12PSU12 or 24 Volt vehicle supply Heater Option Optional Cards and Kits for Non-IR MIC400 CamerasCommissioning MIC400PA and MIC400’s with heaters fitted MIC400PABosch Security Systems Issue MIC400IR Power Supply Units Setting the Power Supply Link OptionsMIC-IR-240PSU, MIC-IR-115PSU, MIC-IR-24PSU and MIC-IR-12PSU Table I Fuse Ratings for MIC-IR-240PSU Function Type Figure D MIC-IR-240PSU LayoutTable L -Washer Pump Connection HD7 SignalTable K -IR Lamp Connections HD6 Terminal Box ID MarkingMIC-IR-12PSU Table M Fuse ratings for MIC-IR-12PSU Function Type Rating Figure E MIC-IR-12PSU SchematicInstallation Instructions Adaptor Connections Connecting the MIC400 to the PCConnecting the Greenwich Adaptor Table N Connecting the Greenwich AdaptorTable O K2-ADE Adaptor connections Connecting the KK systems K2-ADE RS232 to RS485/422 AdaptorDIP Switch SettingTable Q MIC-USB485CVTR Connection Table and Diagram MIC Power Supply Converter Output Telemetry HeaderCommunication Mode MIC-USB485CVTR and Universal Camset Software Installation Commissioning the MIC400 through Universal CamsetStandard Controls MIC Settings Boot MessagesCamset Settings Focus Controls Reset CamsetManual Control Pan, Tilt and Zoom Controls Iris ControlsAuxiliaries Preset PositionsSoft Stops and Non Dwell Zones Tour ControlsTilt Reverse MIC SetupsGeneral Settings Pan ReverseAuto Home Controls Other controls Default SettingsMulti Alarm Settings Frame Integration Settings Privacy and CaptionsLens Recalibration and Frame Integration Privacy Controls Captions Privacy CalibrationThermal Clear All Statistics Advanced SettingsTemperature and Humidity TimersRemap Auxiliary Pelco Only Eeprom CopierDownload Eeprom To File Upload Eeprom From FilePOT Test Menu Controls Panasonic OnlyMatrix Controls Pot Test Results Pot Test ControlsComms Send Direct CommandCam Comms Communications TestingAlarms MIC CommsSony Set SonySet Preset NumberGet Preset from MIC Send Preset to MICClear Table Execute this PresetLoad Table from File to MIC Save Table from MIC to FileTable R Sonyset Commands MIC Programmer Bosch Security Systems Issue Communication & Protocols AlarmsCamera Module OperationalElectrical AccessoriesPhysical EnvironmentalTwin Speakers MIC400PAMIC400UL and MIC400UT MIC400S IR Illuminators MIC400IRDimension Drawings Bosch Security Systems Inc Contact AmericasEurope, Middle East, Africa Asia-PacificAppendix a Protocol Preset codes Preset CodesPelco Bosch Security Systems Vision Special Setup PresetsBosch Security Systems Issue American Dynamics Kalatel Impossible to reach Molynx Panasonic Privacypresetend Multialarmpreset Bosch Forward Vision VCL Pantiltscaleonpreset Vicon PRIVACYSETUPBYTE2