Quick Installation Guide
Rosemount 3095 MultiVariable
Table 9. Temperature Sensor Connection Parameters
Uo = 30V
Io = 19 mA
Po = 140 mW
Table 10. Connection Parameters for Temperature Sensor Terminals
Co = 0.066 F | Gas Group IIC |
Co = 0.560 F | Gas Group IIB |
Co = 1.82 F | Gas Group IIA |
Lo = 96 mH | Gas Group IIC |
Lo = 365 mH | Gas Group IIB |
Lo = 696 mH | Gas Group IIA |
Lo/Ro = 247 H/ohm | Gas Group IIC |
Lo/Ro = 633 H/ohm | Gas Group IIB |
Lo/Ro= 633 H/ohm | Gas Group IIA |
Special conditions for safe use (x):
Versions of the apparatus fitted with the transient protected terminals are not capable of withstanding the 500 volts insulation test required by Clause 6.4.12 of EN 50020:2002. This must be taken into account when installing the apparatus.
GATEX Type N
Certificate Number: Baseefa05ATEX0023X
II 3 G
EEx nA nL IIC T5 (Tamb =
RTD Terminals - The apparatus is designed for connection to a remote temperature sensor such as a resistance temperature detection (RTD).
Special Conditions for Safe Use
Versions of the apparatus fitted with the transient protected terminals are not capable of withstanding the 500 volts insulation test required by Clause 8.1 of EN
HATEX Flameproof
Certificate Number: KEMA02ATEX2320X
II 1/2 G
EEx d IIC T5
Vmax = 55 Vdc MAX Imax = 23 mA MAX IP66
1180
Special conditions for safe use (x):
The device contains a thin wall diaphragm. Installation, maintenance, and use shall take into account the environmental conditions to which the diaphragm will be subjected. The manufacturer’s instructions for installation and maintenance shall be followed in detail to assure safety during its expected lifetime.
26