Emerson 00825-0100-4716 Continued, Rosemount 3095 MultiVariable, Quick Installation Guide

Page 6
STEP 2 CONTINUED...

Quick Installation Guide

Rosemount 3095 MultiVariable

00825-0100-4716, Rev DA October 2009

STEP 2 CONTINUED...

3.Set the Failure Mode Alarm (HART devices), which is located on the front of the electronics board inside the electronics housing cover. The Alarm Jumper position determines if the output is driven high or low when a failure is detected. The transmitter operates normally if the jumpers are not installed and the Alarm default fail is HI.

Figure 2. Alarm Jumper Location

Security Jumper

Simulate Jumper

HART Electronics Board

FOUNDATION fieldbus Electronics Board

4.Set the Simulate Jumper (FOUNDATION fieldbus devices), which is located on the front of the electronics board inside the electronics housing cover. The jumper is used to simulate the measurement and is used as a lock-out feature for the AI function block. To enable the simulate feature, insert the jumper across ENABLE while the transmitter is powered. The default position for the Simulate Jumper is DISABLE. Enable the simulate feature after power is applied to the device. Simulate is automatically disabled regardless of jumper position if power is cycled.

5.Connect the transmitter to the process.

6.Install the RTD Cable Assembly (optional). All RTD 3095 Cable Assemblies use the 3095 RTD Cable Connector. Identify the cable type being installed and follow the steps below.

Installing an Armored Shielded RTD Cable (See Figure 3)

a.Fully engage the black cable connector to the 3095 RTD connector. b.Tighten the cable adapter until metal contacts metal.

c. Install the compression fitting.

d.Tighten the cap onto the compression fitting.

Figure 3. Armored Shielded RTD Cable

Compression Fitting

Black Cable Connector

Connect

Conductive Bushing

Cable Adapter

to RTD

RTD Cap Cap

3/4 to 1/2-14 NPT Adapter

Washer

Bushing

 

 

Compression Fitting

6

Image 6
Contents Fieldbus Protocol Rosemount 3095MF Series Flowmeter Transmitter Quick Installation GuideRosemount 3095 MultiVariable ¢00825-0100-4716/¤Electrical shock can result in death or serious injury Explosions could result in death or serious injuryProcess leaks may cause harm or result in death IMPORTANT NOTICETerminal Block HART O-ring Cover TRANSMITTER EXPLODED VIEWRTD Connector Certification Label Electronics Board Nameplate Module O-ringGas Flow Applications STEP 1 MOUNT THE TRANSMITTERLiquid Flow Applications Steam Flow ApplicationsSTEP 2 TRANSMITTER INSTALLATION Consider Housing RotationField Installation STEP 2 CONTINUED Figure 2. Alarm Jumper LocationFigure 3. Armored Shielded RTD Cable Figure 4. Shielded RTD Cable Cable Adapter 1/2-14 NPT Black Cable ConnectorCable Gland Black Cable Connector/ RTD Connector Figure 5. ATEX/IECEx Flameproof RTD CableBolting Considerations Figure 6. Common Transmitter AssembliesO-ring O-rings with Flange AdaptersFlange Adapter PTFE BasedSTEP 3 SOFTWARE INSTALLATION 3095 Engineering Assistant EA for HART Software InstallationSTEP 3 CONTINUED Installing the HART Modem3095 Engineering Assistant EA for FOUNDATION Fieldbus 3. Select Hart ModemSTEP 4 CONNECT WIRING AND POWER UP HART 24 Vdc Supply Current RL≥ 250Ω MeterPower Conditioner STEP 4 CONNECT WIRING AND POWER UP FIELDBUSPower Supply Shield Wire GroundSend the Configuration to the Transmitter STEP 5 CONFIGURE THE TRANSMITTER HARTSetting the Loop to Manual Basic Configuration ParametersFunction/Variable STEP 5 CONFIGURE THE TRANSMITTER FIELDBUS To configure the AI BlockAI Block configuration parameters Using the Foundation Fieldbus Host System Using the Field CommunicatorUsing the Foundation Fieldbus AI Block STEP 6 TRIM THE TRANSMITTEREuropean Directive Information PRODUCT CERTIFICATIONS Rosemount 3095 with HARTApproved Manufacturing Locations Rosemount 3095 HART Hazardous Locations CertificationsCanadian Standards Association CSA European CertificationsSpecial Conditions for Safe Use IECEx Certifications HART Conditions of Certification INMETRO CertificationsChina NEPSI Certifications Special conditions for safe useL i ≈ Maximum Temperature of ATEX Directive 94/9/EC Rosemount 3095 with FieldbusCombinations of Certifications European Pressure Equipment Directive PED 97/23/ECFM Approvals Rosemount 3095 Fieldbus Hazardous Locations CertificationsNorth American Certifications Canadian Standards Association CSASpecial conditions for safe use IECEx Certifications Fieldbus Quick Installation Guide Rosemount 3095 MultiVariableCombinations of Certifications Quick Installation Guide Rosemount 3095 MultiVariableQuick Installation Guide Rosemount 3095 MultiVariableQuick Installation Guide Rosemount 3095 MultiVariableQuick Installation Guide Rosemount 3095 MultiVariable