STEP 2: TRANSMITTER INSTALLATION

Quick Installation Guide

00825-0100-4716, Rev DA October 2009

Rosemount 3095 MultiVariable

STEP 2: TRANSMITTER INSTALLATION

Consider Housing Rotation

To improve field access or to better view the optional LCD display:

1.Loosen the housing rotation set screw.

2.Rotate the housing clockwise to the desired position – up to 180° from its original position. Over rotating will damage the transmitter.

3.If the desired position is attained, tighten the housing rotation set screw.

4.If the desired position cannot be reached because the housing will not rotate further, rotate the housing counterclockwise until in the desired position is attained (up to 180° from its original position).

5.Tighten the housing rotation set screw.

Housing Rotation Set

Consider Housing RotationField InstallationManual background Screw (9/64-inch)

Field Installation

1. Mount the transmitter

a.Install the flange or flange/adapter bolt finger-tight.

b.Torque bolts to initial torque value using a cross pattern (see Table 1). When installing to a mounting bracket, torque bolts to 125 in./lb (169 N/m)

Table 1. Torque Cross Pattern

Bolt Material

Initial Value

Final Value

Carbon Steel (CS)

300 in./lb (34 N/m)

650 in./lb (73 N/m)

Stainless Steel (SST)

150 in./lb (17 N/m)

300 in./lb (34 N/m)

2.Set the Security Jumper, which is located on the front of the electronics board inside the electronics housing cover. Putting the Security Jumper in the ON position will protect against configuration change from being unintentionally made. The transmitter operates normally if the jumpers are not installed. The Security default is OFF.

5

Image 5
Contents Rosemount 3095 MultiVariable Quick Installation GuideFieldbus Protocol Rosemount 3095MF Series Flowmeter Transmitter ¢00825-0100-4716/¤Process leaks may cause harm or result in death Explosions could result in death or serious injuryElectrical shock can result in death or serious injury IMPORTANT NOTICERTD Connector TRANSMITTER EXPLODED VIEWTerminal Block HART O-ring Cover Certification Label Electronics Board Nameplate Module O-ringLiquid Flow Applications STEP 1 MOUNT THE TRANSMITTERGas Flow Applications Steam Flow ApplicationsField Installation STEP 2 TRANSMITTER INSTALLATIONConsider Housing Rotation Figure 3. Armored Shielded RTD Cable STEP 2 CONTINUEDFigure 2. Alarm Jumper Location Cable Gland Black Cable Connector/ RTD Connector Cable Adapter 1/2-14 NPT Black Cable ConnectorFigure 4. Shielded RTD Cable Figure 5. ATEX/IECEx Flameproof RTD CableFigure 6. Common Transmitter Assemblies Bolting ConsiderationsFlange Adapter O-rings with Flange AdaptersO-ring PTFE Based3095 Engineering Assistant EA for HART Software Installation STEP 3 SOFTWARE INSTALLATION3095 Engineering Assistant EA for FOUNDATION Fieldbus Installing the HART ModemSTEP 3 CONTINUED 3. Select Hart Modem24 Vdc Supply Current RL≥ 250Ω Meter STEP 4 CONNECT WIRING AND POWER UP HARTPower Supply STEP 4 CONNECT WIRING AND POWER UP FIELDBUSPower Conditioner Shield Wire GroundSetting the Loop to Manual STEP 5 CONFIGURE THE TRANSMITTER HARTSend the Configuration to the Transmitter Basic Configuration ParametersRosemount 3095 MultiVariable AI Block configuration parameters STEP 5 CONFIGURE THE TRANSMITTER FIELDBUSTo configure the AI Block Using the Foundation Fieldbus AI Block Using the Field CommunicatorUsing the Foundation Fieldbus Host System STEP 6 TRIM THE TRANSMITTERApproved Manufacturing Locations PRODUCT CERTIFICATIONS Rosemount 3095 with HARTEuropean Directive Information Rosemount 3095 HART Hazardous Locations CertificationsSpecial Conditions for Safe Use Canadian Standards Association CSAEuropean Certifications IECEx Certifications HART INMETRO Certifications Conditions of CertificationL i ≈ China NEPSI CertificationsSpecial conditions for safe use Maximum Temperature of Combinations of Certifications Rosemount 3095 with FieldbusATEX Directive 94/9/EC European Pressure Equipment Directive PED 97/23/ECNorth American Certifications Rosemount 3095 Fieldbus Hazardous Locations CertificationsFM Approvals Canadian Standards Association CSARosemount 3095 MultiVariable IECEx Certifications Fieldbus Combinations of Certifications Quick Installation GuideRosemount 3095 MultiVariable Rosemount 3095 MultiVariable Quick Installation GuideRosemount 3095 MultiVariable Quick Installation GuideRosemount 3095 MultiVariable Quick Installation GuideRosemount 3095 MultiVariable Quick Installation Guide