Quick Installation Guide
Rosemount 3095 MultiVariable
STEP 2 CONTINUED...
•Installing a Shielded 3095 RTD Cable (See Figure 4) Note: Shielded cable is intended for use in a conduit.
a.Fully engage the black cable connector to the 3095 RTD Connector. b.Tighten the cable adapter until metal contacts metal.
Figure 4. Shielded RTD Cable
Cable Adapter 1/2–14 NPT
Black Cable Connector
•Installing a ATEX/IECEx Flameproof 3095 RTD Cable (See Figure 5) a.Fully engage the black cable connector to the 3095 RTD Connector. b.Tighten the cable adapter and cable gland until metal contacts metal.
Figure 5. ATEX/IECEx Flameproof RTD Cable
RTD Cable Gland CM20 |
|
| Cable Adapter |
|
|
|
| ||||||||||||||||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Cable Gland
Black Cable Connector/ RTD Connector
7.Check all process connections for leaks.
8.Connect the appropriate wiring (see Step 5). Ground the transmitter according to national and local electrical codes. Install field wiring grounding (optional).
7