Emerson 00825-0100-4716 manual Rosemount 3095 MultiVariable, Quick Installation Guide

Page 23
Maximum Temperature of

Quick Installation Guide

00825-0100-4716, Rev DA October 2009

Rosemount 3095 MultiVariable

11.When installation, use and maintenance transmitter, observe the following standards GB3836.13-1997 “Electrical apparatus for explosive gas atmospheres Part 13: Repair and overhaul for apparatus used in explosive gas atmospheres” GB3836.15-2000 “Electrical apparatus for explosive gas atmospheres Part 15: Electrical installations in hazardous area (other than mines)”

GB3836.16-2006 “Electrical apparatus for explosive gas atmospheres Part 16: Inspection and maintenance of electrical installation (other than mines): GB50257-1996 “Code for construction and acceptance of electric device for explosion atmospheres and fire hazard electrical equipment installation engineering”

3China Flameproof Ex d II B+H2T4~T6

Special conditions for safe use (x):

1.The ambient temperature range is (-20 ~ +60) °C.

2.The relation between temperature class and maximum temperature of process medium is as following.

Maximum Temperature of

Temperature Class

Process Medium (°C)

121

T4

95

T5

80

T6

3.The earth connection facility in the enclosure should be connected reliably.

4.During installation, use and maintenance of transmitter, observe the warning, “Don’t open the cover when the circuit is alive.”

5.During installation, there should be no mixture harm to flameproof housing.

6.Cable entry, certified by NEPSI with type of protection Ex d IIC in accordance with GB3836.2-2000, should be applied when installation in hazardous location. Five full threads should be in engagement when the cable entry is assembled onto the transmitter.

7.The diameter of cable should observe the instruction manual of cable entry. The compressing nut should be fastened. The aging of seal ring should be changed in time.

8.Maintenance should be done in non-hazardous location.

9.End users is not permitted to change any components insides.

10.When installation, use and maintenance of transmitter, observe following standards. GB3836.13-1997 “Electrical apparatus for explosive gas atmospheres Part 13: Repair and overhaul for apparatus used in explosive gas atmospheres” GB3836.15-2000 “Electrical apparatus for explosive gas atmospheres Part 15: Electrical installations in hazardous area (other than mines)”

GB50257-1996 “Code for construction and acceptance of electric device for explosion atmospheres and fire hazard electrical equipment installation engineering”

RTIIS Flameproof

Consult factory for availability

23

Image 23
Contents ¢00825-0100-4716/¤ Quick Installation GuideRosemount 3095 MultiVariable Fieldbus Protocol Rosemount 3095MF Series Flowmeter TransmitterIMPORTANT NOTICE Explosions could result in death or serious injuryProcess leaks may cause harm or result in death Electrical shock can result in death or serious injuryCertification Label Electronics Board Nameplate Module O-ring TRANSMITTER EXPLODED VIEWRTD Connector Terminal Block HART O-ring CoverSteam Flow Applications STEP 1 MOUNT THE TRANSMITTERLiquid Flow Applications Gas Flow ApplicationsField Installation STEP 2 TRANSMITTER INSTALLATIONConsider Housing Rotation Figure 3. Armored Shielded RTD Cable STEP 2 CONTINUEDFigure 2. Alarm Jumper Location Figure 5. ATEX/IECEx Flameproof RTD Cable Cable Adapter 1/2-14 NPT Black Cable ConnectorCable Gland Black Cable Connector/ RTD Connector Figure 4. Shielded RTD CableFigure 6. Common Transmitter Assemblies Bolting ConsiderationsPTFE Based O-rings with Flange AdaptersFlange Adapter O-ring3095 Engineering Assistant EA for HART Software Installation STEP 3 SOFTWARE INSTALLATION3. Select Hart Modem Installing the HART Modem3095 Engineering Assistant EA for FOUNDATION Fieldbus STEP 3 CONTINUED24 Vdc Supply Current RL≥ 250Ω Meter STEP 4 CONNECT WIRING AND POWER UP HARTShield Wire Ground STEP 4 CONNECT WIRING AND POWER UP FIELDBUSPower Supply Power ConditionerBasic Configuration Parameters STEP 5 CONFIGURE THE TRANSMITTER HARTSetting the Loop to Manual Send the Configuration to the TransmitterFast Key Sequence AI Block configuration parameters STEP 5 CONFIGURE THE TRANSMITTER FIELDBUSTo configure the AI Block STEP 6 TRIM THE TRANSMITTER Using the Field CommunicatorUsing the Foundation Fieldbus AI Block Using the Foundation Fieldbus Host SystemRosemount 3095 HART Hazardous Locations Certifications PRODUCT CERTIFICATIONS Rosemount 3095 with HARTApproved Manufacturing Locations European Directive InformationSpecial Conditions for Safe Use Canadian Standards Association CSAEuropean Certifications IECEx Certifications HART INMETRO Certifications Conditions of CertificationL i ≈ China NEPSI CertificationsSpecial conditions for safe use Maximum Temperature of European Pressure Equipment Directive PED 97/23/EC Rosemount 3095 with FieldbusCombinations of Certifications ATEX Directive 94/9/ECCanadian Standards Association CSA Rosemount 3095 Fieldbus Hazardous Locations CertificationsNorth American Certifications FM ApprovalsSpecial conditions for safe use IECEx Certifications Fieldbus Combinations of Certifications Quick Installation GuideRosemount 3095 MultiVariable Rosemount 3095 MultiVariable Quick Installation GuideRosemount 3095 MultiVariable Quick Installation GuideRosemount 3095 MultiVariable Quick Installation GuideRosemount 3095 MultiVariable Quick Installation Guide