STEP 4: CONNECT WIRING AND POWER UP (FIELDBUS)

Quick Installation Guide

00825-0100-4716, Rev DA October 2009

Rosemount 3095 MultiVariable

STEP 4: CONNECT WIRING AND POWER UP (FIELDBUS)

Use the following steps to wire the transmitter:

1.Remove the housing cover labeled “Field Terminals.” Terminals are not polarity sensitive.

2.Connect the signal leads to the terminals labeled “Fieldbus Wiring”.

3.Plug and seal unused conduit connections.

4.Install wiring with a drip loop. Arrange the drip loop so the bottom is lower than the conduit connections and the transmitter housing.

5.Replace the housing cover.

NOTE

Do not attach shield to ground.

Power Supply

To operate and provide complete functionality, the transmitter requires the supply voltage to be within the ranges shown below.

 

 

Approval Option Code

Supply Voltage

B, D, F, J, K, L, N, 2, 4, 9

9-30 Vdc

A, C, E, G, H, P, R, 0, 3, 5, 7, 8

9-32 Vdc

T, U, V, W, Y, 6

9-17.5 Vdc

Power Conditioner

A fieldbus segment requires a power conditioner to isolate the power supply filter and decouple the segment from other segments attached to the same power supply.

Grounding

Signal wiring of the fieldbus segment can not be grounded. Grounding out one of the signal wires will shut down the entire fieldbus segment.

Shield Wire Ground

To protect the fieldbus segment from noise, grounding techniques for shield wire usually requires one and only one grounding point for shield wire to avoid creating a ground loop. The ground point is typically at the power supply.

Signal Termination

For every fieldbus segment a terminator should be installed at the beginning and at the end of each segment.

13

Image 13
Contents Rosemount 3095 MultiVariable Quick Installation GuideFieldbus Protocol Rosemount 3095MF Series Flowmeter Transmitter ¢00825-0100-4716/¤Process leaks may cause harm or result in death Explosions could result in death or serious injuryElectrical shock can result in death or serious injury IMPORTANT NOTICERTD Connector TRANSMITTER EXPLODED VIEWTerminal Block HART O-ring Cover Certification Label Electronics Board Nameplate Module O-ringLiquid Flow Applications STEP 1 MOUNT THE TRANSMITTERGas Flow Applications Steam Flow ApplicationsConsider Housing Rotation STEP 2 TRANSMITTER INSTALLATIONField Installation Figure 2. Alarm Jumper Location STEP 2 CONTINUEDFigure 3. Armored Shielded RTD Cable Cable Gland Black Cable Connector/ RTD Connector Cable Adapter 1/2-14 NPT Black Cable ConnectorFigure 4. Shielded RTD Cable Figure 5. ATEX/IECEx Flameproof RTD CableFigure 6. Common Transmitter Assemblies Bolting ConsiderationsFlange Adapter O-rings with Flange AdaptersO-ring PTFE Based3095 Engineering Assistant EA for HART Software Installation STEP 3 SOFTWARE INSTALLATION3095 Engineering Assistant EA for FOUNDATION Fieldbus Installing the HART ModemSTEP 3 CONTINUED 3. Select Hart Modem24 Vdc Supply Current RL≥ 250Ω Meter STEP 4 CONNECT WIRING AND POWER UP HARTPower Supply STEP 4 CONNECT WIRING AND POWER UP FIELDBUSPower Conditioner Shield Wire GroundSetting the Loop to Manual STEP 5 CONFIGURE THE TRANSMITTER HARTSend the Configuration to the Transmitter Basic Configuration ParametersRosemount 3095 MultiVariable To configure the AI Block STEP 5 CONFIGURE THE TRANSMITTER FIELDBUSAI Block configuration parameters Using the Foundation Fieldbus AI Block Using the Field CommunicatorUsing the Foundation Fieldbus Host System STEP 6 TRIM THE TRANSMITTERApproved Manufacturing Locations PRODUCT CERTIFICATIONS Rosemount 3095 with HARTEuropean Directive Information Rosemount 3095 HART Hazardous Locations CertificationsEuropean Certifications Canadian Standards Association CSASpecial Conditions for Safe Use IECEx Certifications HART INMETRO Certifications Conditions of CertificationSpecial conditions for safe use China NEPSI CertificationsL i ≈ Maximum Temperature of Combinations of Certifications Rosemount 3095 with FieldbusATEX Directive 94/9/EC European Pressure Equipment Directive PED 97/23/ECNorth American Certifications Rosemount 3095 Fieldbus Hazardous Locations CertificationsFM Approvals Canadian Standards Association CSARosemount 3095 MultiVariable IECEx Certifications Fieldbus Rosemount 3095 MultiVariable Quick Installation GuideCombinations of Certifications Rosemount 3095 MultiVariable Quick Installation GuideRosemount 3095 MultiVariable Quick Installation GuideRosemount 3095 MultiVariable Quick Installation GuideRosemount 3095 MultiVariable Quick Installation Guide