Quick Installation Guide
Rosemount 3095 MultiVariable
STEP 5: CONFIGURE THE TRANSMITTER (HART)
Setting the Loop to Manual
Set the process application loop to manual when preparing to send or request data that would disrupt the loop or change the output of the transmitter. A prompt will appear reminding the user to set the loop to manual when necessary. Acknowledging this prompter does not set the loop to manual.
Send the Configuration to the Transmitter
Use the following steps to send the configuration to the transmitter. All previous transmitter information will be overwritten when the information is sent.
1.EA: Select Configure > Configure Flow.
2.Step through the Flow Configuration wizard.
3.Check Send Flow Configuration to update the transmitter’s flow calculation.
4.From the Device Connection window, right click on the transmitter icon, and select Configuration Properties. On the Basic Setup window, verify the units of measure and the LRV to URV range
Basic Configuration Parameters
NOTE:
A check (✓) indicates the basic configuration parameters. At minimum, these parameters should be verified as part of the configuration and startup procedure.
Transmitters are shipped from Emerson Process Management fully calibrated and configured for the application when C2 Option is ordered. Without C2 Option, configuration will be by the factory default.
Table 2. HART Communicator Fast Key Sequence |
|
Function/Variable | Fast Key Sequence |
% rnge | 1, 1, 2 |
% rnge | 1, 1, 5, 1, 3 |
4V is | 1, 1, 5, 4, 1 |
AO Alrm typ | 1, 4, 1, 1, 1 |
AO1 | 1, 1, 3 |
AO1 | 3 |
AP Damping | 1, 4, 2, 5, 2 |
AP Sens Trim | 1, 2, 2, 1, 2 |
AP Units | 1, 3, 2, 2 |
Absolute (AP) | 1, 1, 4, 2 |
Atm Press Cnfg | 1, 4, 2, 3 |
Burst mode | 1, 4, 1, 2, 4, 2 |
Burst option | 1, 4, 1, 2, 4, 1 |
Change PV Assgn | 1, 1, 5, 1, 5 |
Change SV Assgn | 1, 1, 5, 2, 3 |
Change TV Assgn | 1, 1, 5, 3, 3 |
Change 4V Assgn | 1, 1, 5, 4, 3 |
D/A trim | 1, 2, 2, 2, 1 |
DP Low Flow Cutoff | 1, 4, 6 |
DP LRV | 4 |
14