STEP 5: CONFIGURE THE TRANSMITTER (HART)

Quick Installation Guide

Rosemount 3095 MultiVariable

00825-0100-4716, Rev DA October 2009

STEP 5: CONFIGURE THE TRANSMITTER (HART)

Setting the Loop to Manual

Set the process application loop to manual when preparing to send or request data that would disrupt the loop or change the output of the transmitter. A prompt will appear reminding the user to set the loop to manual when necessary. Acknowledging this prompter does not set the loop to manual.

Send the Configuration to the Transmitter

Use the following steps to send the configuration to the transmitter. All previous transmitter information will be overwritten when the information is sent.

1.EA: Select Configure > Configure Flow.

2.Step through the Flow Configuration wizard.

3.Check Send Flow Configuration to update the transmitter’s flow calculation.

4.From the Device Connection window, right click on the transmitter icon, and select Configuration Properties. On the Basic Setup window, verify the units of measure and the LRV to URV range (4-20 mA setpoints).

Basic Configuration Parameters

NOTE:

A check () indicates the basic configuration parameters. At minimum, these parameters should be verified as part of the configuration and startup procedure.

Transmitters are shipped from Emerson Process Management fully calibrated and configured for the application when C2 Option is ordered. Without C2 Option, configuration will be by the factory default.

Table 2. HART Communicator Fast Key Sequence

 

Function/Variable

Fast Key Sequence

% rnge

1, 1, 2

% rnge

1, 1, 5, 1, 3

4V is

1, 1, 5, 4, 1

AO Alrm typ

1, 4, 1, 1, 1

AO1

1, 1, 3

AO1

3

AP Damping

1, 4, 2, 5, 2

AP Sens Trim

1, 2, 2, 1, 2

AP Units

1, 3, 2, 2

Absolute (AP)

1, 1, 4, 2

Atm Press Cnfg

1, 4, 2, 3

Burst mode

1, 4, 1, 2, 4, 2

Burst option

1, 4, 1, 2, 4, 1

Change PV Assgn

1, 1, 5, 1, 5

Change SV Assgn

1, 1, 5, 2, 3

Change TV Assgn

1, 1, 5, 3, 3

Change 4V Assgn

1, 1, 5, 4, 3

D/A trim

1, 2, 2, 2, 1

DP Low Flow Cutoff

1, 4, 6

DP LRV

4

14

Image 14
Contents Fieldbus Protocol Rosemount 3095MF Series Flowmeter Transmitter Quick Installation GuideRosemount 3095 MultiVariable ¢00825-0100-4716/¤Electrical shock can result in death or serious injury Explosions could result in death or serious injuryProcess leaks may cause harm or result in death IMPORTANT NOTICETerminal Block HART O-ring Cover TRANSMITTER EXPLODED VIEWRTD Connector Certification Label Electronics Board Nameplate Module O-ringGas Flow Applications STEP 1 MOUNT THE TRANSMITTERLiquid Flow Applications Steam Flow ApplicationsField Installation STEP 2 TRANSMITTER INSTALLATIONConsider Housing Rotation Figure 3. Armored Shielded RTD Cable STEP 2 CONTINUEDFigure 2. Alarm Jumper Location Figure 4. Shielded RTD Cable Cable Adapter 1/2-14 NPT Black Cable ConnectorCable Gland Black Cable Connector/ RTD Connector Figure 5. ATEX/IECEx Flameproof RTD CableBolting Considerations Figure 6. Common Transmitter AssembliesO-ring O-rings with Flange AdaptersFlange Adapter PTFE BasedSTEP 3 SOFTWARE INSTALLATION 3095 Engineering Assistant EA for HART Software InstallationSTEP 3 CONTINUED Installing the HART Modem3095 Engineering Assistant EA for FOUNDATION Fieldbus 3. Select Hart ModemSTEP 4 CONNECT WIRING AND POWER UP HART 24 Vdc Supply Current RL≥ 250Ω MeterPower Conditioner STEP 4 CONNECT WIRING AND POWER UP FIELDBUSPower Supply Shield Wire GroundSend the Configuration to the Transmitter STEP 5 CONFIGURE THE TRANSMITTER HARTSetting the Loop to Manual Basic Configuration ParametersFunction/Variable AI Block configuration parameters STEP 5 CONFIGURE THE TRANSMITTER FIELDBUSTo configure the AI Block Using the Foundation Fieldbus Host System Using the Field CommunicatorUsing the Foundation Fieldbus AI Block STEP 6 TRIM THE TRANSMITTEREuropean Directive Information PRODUCT CERTIFICATIONS Rosemount 3095 with HARTApproved Manufacturing Locations Rosemount 3095 HART Hazardous Locations CertificationsSpecial Conditions for Safe Use Canadian Standards Association CSAEuropean Certifications IECEx Certifications HART Conditions of Certification INMETRO CertificationsL i ≈ China NEPSI CertificationsSpecial conditions for safe use Maximum Temperature of ATEX Directive 94/9/EC Rosemount 3095 with FieldbusCombinations of Certifications European Pressure Equipment Directive PED 97/23/ECFM Approvals Rosemount 3095 Fieldbus Hazardous Locations CertificationsNorth American Certifications Canadian Standards Association CSASpecial conditions for safe use IECEx Certifications Fieldbus Combinations of Certifications Quick Installation GuideRosemount 3095 MultiVariable Quick Installation Guide Rosemount 3095 MultiVariableQuick Installation Guide Rosemount 3095 MultiVariableQuick Installation Guide Rosemount 3095 MultiVariableQuick Installation Guide Rosemount 3095 MultiVariable