Emerson 00825-0100-4716 manual Rosemount 3095 MultiVariable, Quick Installation Guide

Page 32
Manual background

Quick Installation Guide

Rosemount 3095 MultiVariable

00825-0100-4716, Rev DA October 2009

32

Image 32
Contents Quick Installation Guide Rosemount 3095 MultiVariableFieldbus Protocol Rosemount 3095MF Series Flowmeter Transmitter ¢00825-0100-4716/¤Explosions could result in death or serious injury Process leaks may cause harm or result in deathElectrical shock can result in death or serious injury IMPORTANT NOTICETRANSMITTER EXPLODED VIEW RTD ConnectorTerminal Block HART O-ring Cover Certification Label Electronics Board Nameplate Module O-ringSTEP 1 MOUNT THE TRANSMITTER Liquid Flow ApplicationsGas Flow Applications Steam Flow ApplicationsField Installation STEP 2 TRANSMITTER INSTALLATIONConsider Housing Rotation Figure 3. Armored Shielded RTD Cable STEP 2 CONTINUEDFigure 2. Alarm Jumper Location Cable Adapter 1/2-14 NPT Black Cable Connector Cable Gland Black Cable Connector/ RTD ConnectorFigure 4. Shielded RTD Cable Figure 5. ATEX/IECEx Flameproof RTD CableBolting Considerations Figure 6. Common Transmitter AssembliesO-rings with Flange Adapters Flange AdapterO-ring PTFE BasedSTEP 3 SOFTWARE INSTALLATION 3095 Engineering Assistant EA for HART Software InstallationInstalling the HART Modem 3095 Engineering Assistant EA for FOUNDATION FieldbusSTEP 3 CONTINUED 3. Select Hart ModemSTEP 4 CONNECT WIRING AND POWER UP HART 24 Vdc Supply Current RL≥ 250Ω MeterSTEP 4 CONNECT WIRING AND POWER UP FIELDBUS Power SupplyPower Conditioner Shield Wire GroundSTEP 5 CONFIGURE THE TRANSMITTER HART Setting the Loop to ManualSend the Configuration to the Transmitter Basic Configuration ParametersQuick Installation Guide AI Block configuration parameters STEP 5 CONFIGURE THE TRANSMITTER FIELDBUSTo configure the AI Block Using the Field Communicator Using the Foundation Fieldbus AI BlockUsing the Foundation Fieldbus Host System STEP 6 TRIM THE TRANSMITTERPRODUCT CERTIFICATIONS Rosemount 3095 with HART Approved Manufacturing LocationsEuropean Directive Information Rosemount 3095 HART Hazardous Locations CertificationsSpecial Conditions for Safe Use Canadian Standards Association CSAEuropean Certifications IECEx Certifications HART Conditions of Certification INMETRO CertificationsL i ≈ China NEPSI CertificationsSpecial conditions for safe use Maximum Temperature of Rosemount 3095 with Fieldbus Combinations of CertificationsATEX Directive 94/9/EC European Pressure Equipment Directive PED 97/23/ECRosemount 3095 Fieldbus Hazardous Locations Certifications North American CertificationsFM Approvals Canadian Standards Association CSAQuick Installation Guide IECEx Certifications Fieldbus Combinations of Certifications Quick Installation GuideRosemount 3095 MultiVariable Quick Installation Guide Rosemount 3095 MultiVariableQuick Installation Guide Rosemount 3095 MultiVariableQuick Installation Guide Rosemount 3095 MultiVariableQuick Installation Guide Rosemount 3095 MultiVariable