Quick Installation Guide
Rosemount 3095 MultiVariable
STEP 6: TRIM THE TRANSMITTER
NOTE
Transmitters are shipped from Emerson Process Management fully calibrated and configured for the application when C2 Option is ordered. Without C2 Option, configuration will be by the factory default (span = upper range limit for FOUNDATION fieldbus transmitters).
Zero Trim
A zero trim is a
Using the Field Communicator
1.Equalize the transmitter and connect Field communicator.
2.At the menu, input the Fast Key sequence.
3.Follow the commands to perform a zero trim.
Fast Keys | Steps |
1, 2, 2, 1, 1 | Trim DP Offset (Zero) |
1, 2, 2, 1, 2 | Trim SP Offset (Zero), (AP, GP) |
4.Once the zero trim is complete, verify that the high side block valve is open, close the equalize valve tightly, then open the low side block valve.
Using the Foundation Fieldbus AI Block
For zero errors greater than the allowable zero trim, compensate for the offset by using the XD_Scaling, Out_Scaling and Indirect L_Type.
Using the Foundation Fieldbus Host System
Perform a Zero Trim method if the host system supports methods associated with the TRANSDUCER 1400 block. Otherwise, if the host system does not support methods see the 3095 Manual
NOTE
For Absolute Pressure (AP) Sensor: If open to atmosphere, reading should be at atmospheric pressure (roughly 12 - 15 psi (0.8 - 1.0 bar), not zero. Use a barometer that is four times as accurate as the 3095 AP sensor.