Emerson 00825-0100-4716 manual IECEx Certifications Fieldbus, Rosemount 3095 MultiVariable

Page 27
IECEx Certifications (Fieldbus)

Quick Installation Guide

00825-0100-4716, Rev DA October 2009

Rosemount 3095 MultiVariable

PATEX Dust

Certificate Number: KEMA02ATEX2321

Manual background II 1 D T90°C (-50°C Tamb 80°C) Vmax = 55 Vdc

Imax = 23 mA IP66

Manual background 1180

IECEx Certifications (Fieldbus)

4/Y IECEx Intrinsic Safety

Certificate Number: IECEx BAS05.0023X Ex ia IIC T4 (-45°C Ta 70°C)

Ex ia IIC T5 (-45°C Ta 40°C)

Table 11. Input Parameters

 

 

Fieldbus I.S.

FISCO

 

Ui = 30Vdc

Ui = 17.5Vdc

 

Ii = 300 mAdc

Ii = 380 mAdc

 

Pi = 1.3 W

Pi = 5.32 W

 

Ci = 3.3 nF

Ci 5 nF

 

Li = 0

Li 10 mH

Table 12. RTD Terminals Entity Parameters

Uo = 30Vdc

Io = 19 mAdc

Po = 140 mW

The capacitance and either the Inductance or the Inductance to Resistance Ratio (L/R) of the load connected to the 4-pin connector must not exceed the following values:

Group

Capacitance

Inductance

or L/R Ratio

 

(￿F)

(mH)

￿H/Ohm

IIC

0.066

96

247

IIB

0.56

365

633

IIA

1.82

696

633

Conditions of Certification (X):

When fitted with the transient option, the apparatus is not capable of withstanding the 500V electrical strength test as defined in Clause 6.4.12 of IEC 60079-11: 1999. This must be taken into account during installation.

5IECEx Type n

Certificate Number: IECEx BAS05.0024X Ex nC IIC T4 (-45°C Ta 70°C)

Ex nC IIC T5 (-45°C Ta 40°C) Ui = 55V dc max

Conditions of Certification (X):

When fitted with the transient option, the apparatus is not capable of withstanding the 500V electrical strength test as defined in Clause 8 of IEC 60079-15: 1987. This must be taken into account during installation.

27

Image 27
Contents ¢00825-0100-4716/¤ Quick Installation GuideRosemount 3095 MultiVariable Fieldbus Protocol Rosemount 3095MF Series Flowmeter TransmitterIMPORTANT NOTICE Explosions could result in death or serious injuryProcess leaks may cause harm or result in death Electrical shock can result in death or serious injuryCertification Label Electronics Board Nameplate Module O-ring TRANSMITTER EXPLODED VIEWRTD Connector Terminal Block HART O-ring CoverSteam Flow Applications STEP 1 MOUNT THE TRANSMITTERLiquid Flow Applications Gas Flow ApplicationsSTEP 2 TRANSMITTER INSTALLATION Consider Housing RotationField Installation STEP 2 CONTINUED Figure 2. Alarm Jumper LocationFigure 3. Armored Shielded RTD Cable Figure 5. ATEX/IECEx Flameproof RTD Cable Cable Adapter 1/2-14 NPT Black Cable ConnectorCable Gland Black Cable Connector/ RTD Connector Figure 4. Shielded RTD CableFigure 6. Common Transmitter Assemblies Bolting ConsiderationsPTFE Based O-rings with Flange AdaptersFlange Adapter O-ring3095 Engineering Assistant EA for HART Software Installation STEP 3 SOFTWARE INSTALLATION3. Select Hart Modem Installing the HART Modem3095 Engineering Assistant EA for FOUNDATION Fieldbus STEP 3 CONTINUED24 Vdc Supply Current RL≥ 250Ω Meter STEP 4 CONNECT WIRING AND POWER UP HARTShield Wire Ground STEP 4 CONNECT WIRING AND POWER UP FIELDBUSPower Supply Power ConditionerBasic Configuration Parameters STEP 5 CONFIGURE THE TRANSMITTER HARTSetting the Loop to Manual Send the Configuration to the TransmitterFast Key Sequence STEP 5 CONFIGURE THE TRANSMITTER FIELDBUS To configure the AI BlockAI Block configuration parameters STEP 6 TRIM THE TRANSMITTER Using the Field CommunicatorUsing the Foundation Fieldbus AI Block Using the Foundation Fieldbus Host SystemRosemount 3095 HART Hazardous Locations Certifications PRODUCT CERTIFICATIONS Rosemount 3095 with HARTApproved Manufacturing Locations European Directive InformationCanadian Standards Association CSA European CertificationsSpecial Conditions for Safe Use IECEx Certifications HART INMETRO Certifications Conditions of CertificationChina NEPSI Certifications Special conditions for safe useL i ≈ Maximum Temperature of European Pressure Equipment Directive PED 97/23/EC Rosemount 3095 with Fieldbus Combinations of Certifications ATEX Directive 94/9/ECCanadian Standards Association CSA Rosemount 3095 Fieldbus Hazardous Locations CertificationsNorth American Certifications FM ApprovalsSpecial conditions for safe use IECEx Certifications Fieldbus Quick Installation Guide Rosemount 3095 MultiVariableCombinations of Certifications Rosemount 3095 MultiVariable Quick Installation GuideRosemount 3095 MultiVariable Quick Installation GuideRosemount 3095 MultiVariable Quick Installation GuideRosemount 3095 MultiVariable Quick Installation Guide