AEG 8000012364 BAL operating instructions Principle of Operation of the SBS, Electrical

Page 16

"UniVert 2" inverter

2.6Principle of Operation of the SBS, Electrical

If the SBS is supplied by connecting the mains or the load voltage, the corresponding operating status is automatically activated after 3 to 5 seconds.

With mains operation, the DOU displays load voltage and SBS current. With all other operating statuses, in addition to the load voltage the corresponding status (ready, blocked, fault) is displayed.

The toggle switch on the DOU serves exclusively to acknowledge SBS faults.

The SBS control unit continually monitors the load voltage and, in the event of a load voltage deviation, initiates switchover of the loads from the INV/INVs to the SBS without interruption. Then the loads are automatically switched back to the INV/INVs. The thyristors of the SBS only quench when the supply of the loads is guaranteed by the activation of the output contactors of the INV/INVs.

When the SBS is fired, both antiparallel thyristors are triggered over the whole period ensuring reliable operation of the SBS in the entire range from inductive to capacitive load.

The entire control and monitoring process is carried out using a microprocessor. LEDs and relays show the unit status, whilst the output voltage and output current are displayed on an LCD. If the SBS is operated with one or more INVs connected in parallel, a CAN bus is required between the units for control purposes. An additional CAN bus allows the unit to be integrated in a power supply system and connected to a central control and monitoring unit (PSM).

Page 16 of 42

8000012364 BAL, en

Image 16
Contents Operating Instructions UniVert 2 inverter and SBS option Warranty Duty to Provide InformationValidity HandlingHotline AbbreviationsCopyright Table of Contents Technical Data Maintenance TroubleshootingDimensional Drawing Important Instructions and Explanations Safety InstructionsAccident Prevention Regulations Qualified Personnel Safety Awareness ApplicationLiability DirectivesGeneral Information System DescriptionFunction of the System Individual INV operationParallel INV operation Individual or parallel operation with SBSParallel INV operation Block diagram of the inverter Description of the INVPrinciple of Operation of the INV, Electrical Description of the SBS SBSPrinciple of Operation of the SBS, Electrical Function of the Inverter ON/OFF Switch DIL SwitchCan Bus Interfaces X6 S2.1 S2.2 S2.3Switches S2.4, S2.5 and S2.6 Own Address INV Switches S2.7 and S2.8 Number of redundant INVsINVs Settings must be the same on all INVs and the SBS S2.4 S2.5 S2.6 AddressSignalling, Displays and Remote Signals Display Colour Operating statusFunction of the SBS optional Switchback AttemptsOperating Statuses Reset Button AC Mains InputAC Busbar AC Mains Monitoring SystemS3.1 S3.2 S3.3 S3.7 S3.8 INVs Switchover without gap Assignment of the signal terminalsOperating modes Switchover with gap Installation Connecting the Loads / DC / MainsStart-Up ConnectionDisconnection Maintenance Output Voltage Deviation TroubleshootingFor systems with SBS additionally Technical Data General Data INVFault Overtemperature ϑCollective fault OperationGeneral Data SBS With safe isolation at UO ≤ 60 V DC UniVert 2 inverter Electrical Data At 24 Type E-number G110 E230/10,9/2rfg-CFp2,5 3000000263 Type E-number E230 E230/115/2-VFp26,5-8 3000000646 Dimensional Drawing Inverter dimensions type 1.5 and 3.3 kVAInverter dimensions type 2.5 kVA SBS dimensions