AEG 8000012364 BAL Function of the SBS optional, Operating Statuses, Switchback Attempts

Page 21

"UniVert 2" inverter

4 Function of the SBS (optional)

For the technical data or unit settings, refer to the chapter “Technical

Data”.

4.1Operating Statuses

The following operating statuses are possible:

"PowerUp":

Status after PowerUp or Reset. The control system checks the ambient conditions.

"on":

Mains operation: The SBS supplies the load.

"ready":

In the event of load voltage deviation or INV failure / switch-off, the SBS takes over the load without interruption, i.e. the SBS control system switches over to the "on" operating status.

"blocked":

The SBS control unit is blocked. In the event of load voltage deviation or INV failure / switch-off, the SBS does not take over the load, i.e. the SBS control system remains in the "blocked" operating status. The operating status "blocked" is activated in the event of mains failures or phase deviations.

"Fault":

A fault has occurred in the SBS. This fault must be remedied and acknowledged using the Reset button.

ATTENTION:

If the INV is switched off in the event of a blocked or faulty SBS, the loads are no longer supplied with power.

4.2Switchback Attempts

Should the load voltage deviate excessively e.g. due to overload of the INVs or load short circuits (see chapter 4.4), the loads are automatically switched over to the SBS without interruption. Then the loads are also automatically switched back to the INV. It this switchback attempt fails, the SBS continues to supply the loads. After 3 unsuccessful switchback attempts within 1 minute, the INV is switched off and the loads remain supplied by the SBS.

Page 21 of 42

8000012364 BAL, en

Image 21 Contents
Operating Instructions UniVert 2 inverter and SBS option Duty to Provide Information WarrantyValidity HandlingAbbreviations HotlineCopyright Table of Contents Maintenance Troubleshooting Technical DataDimensional Drawing Safety Instructions Important Instructions and ExplanationsAccident Prevention Regulations Qualified Personnel Application Safety AwarenessDirectives LiabilitySystem Description General InformationIndividual INV operation Function of the SystemParallel INV operation Individual or parallel operation with SBSParallel INV operation Description of the INV Block diagram of the inverterPrinciple of Operation of the INV, Electrical SBS Description of the SBSPrinciple of Operation of the SBS, Electrical Function of the Inverter DIL Switch ON/OFF SwitchCan Bus Interfaces X6 S2.1 S2.2 S2.3Switches S2.7 and S2.8 Number of redundant INVs Switches S2.4, S2.5 and S2.6 Own Address INVINVs Settings must be the same on all INVs and the SBS S2.4 S2.5 S2.6 AddressDisplay Colour Operating status Signalling, Displays and Remote SignalsSwitchback Attempts Function of the SBS optionalOperating Statuses AC Mains Input Reset ButtonAC Busbar AC Mains Monitoring SystemS3.1 S3.2 S3.3 S3.7 S3.8 INVs Assignment of the signal terminals Switchover without gapOperating modes Switchover with gap Connecting the Loads / DC / Mains InstallationStart-Up ConnectionDisconnection Maintenance Troubleshooting Output Voltage DeviationFor systems with SBS additionally General Data INV Technical DataOvertemperature ϑ FaultCollective fault OperationGeneral Data SBS With safe isolation at UO ≤ 60 V DC UniVert 2 inverter Electrical Data At 24 Type E-number G110 E230/10,9/2rfg-CFp2,5 3000000263 Type E-number E230 E230/115/2-VFp26,5-8 3000000646 Inverter dimensions type 1.5 and 3.3 kVA Dimensional DrawingInverter dimensions type 2.5 kVA SBS dimensions