AEG 8000012364 BAL Signalling, Displays and Remote Signals, Display Colour Operating status

Page 20

"UniVert 2" inverter

3.10Signalling, Displays and Remote Signals

The following signals are indicated via LEDs on the front panel:

Display

Colour

Operating status

Operation

green

INV operation

UO OK

green

INV output voltage present

UI<

red

Input voltage < 85% of rated voltage,

 

 

INV has switched off

UI>

red

Input voltage > 128% of rated voltage,

 

 

INV has switched off

Fault

red

INV output voltage below 90% of rated

 

 

voltage

ϑ>

red

Overtemperature on heat sink or

 

 

overload

Collective

red

Delayed collective fault signal,

fault

 

delay time 20 s,

 

 

signalling relay is triggered at the same time.

 

 

The following disturbing influences are

 

 

registered:

 

 

INV fault

 

 

UI<

 

 

UI>

 

 

ϑ>

 

 

Overload

 

 

INV output miniature circuit-breaker

 

 

 

The unit is equipped with a liquid-crystal display. When the unit is switched off, the LCD shows "OFF", when the unit is switched on it shows the INV output voltage and output current. While the INV starts up and output contactor K7 is still switched off, "READY" is signalled.

In the event of a fault, the 1st display row shows "FAULT" and the 2nd display row shows the type of fault.

The INV voltage and current values are displayed with three decimals before and one decimal after the decimal point. The display accuracy corresponds to class 1 with respect to the rated output value of the unit.

Remote signalling is carried out by means of potential-free contacts via a Combicon connector on the front of the unit.

Assignment of the signal terminals:

INV fault:

In the event of a signal, X10.2 – X10.3 or X3.2 – X3.3 close. No fault: X10.2 – X10.1 or X3.2 – X3.1.

When the INV is disconnected from the power supply (no DC supply), a fault is signalled!

The remote signals are designed for safe isolation. The minimum load should not be below 12 V and 0.1 A.

Page 20 of 42

8000012364 BAL, en

Image 20
Contents Operating Instructions UniVert 2 inverter and SBS option Warranty Duty to Provide InformationValidity HandlingCopyright AbbreviationsHotline Table of Contents Dimensional Drawing Maintenance TroubleshootingTechnical Data Accident Prevention Regulations Safety InstructionsImportant Instructions and Explanations Qualified Personnel Safety Awareness ApplicationLiability DirectivesGeneral Information System DescriptionFunction of the System Individual INV operationParallel INV operation Individual or parallel operation with SBSParallel INV operation Block diagram of the inverter Description of the INVPrinciple of Operation of the INV, Electrical Description of the SBS SBSPrinciple of Operation of the SBS, Electrical Function of the Inverter ON/OFF Switch DIL SwitchCan Bus Interfaces X6 S2.1 S2.2 S2.3Switches S2.4, S2.5 and S2.6 Own Address INV Switches S2.7 and S2.8 Number of redundant INVsINVs Settings must be the same on all INVs and the SBS S2.4 S2.5 S2.6 AddressSignalling, Displays and Remote Signals Display Colour Operating statusOperating Statuses Switchback AttemptsFunction of the SBS optional Reset Button AC Mains InputAC Busbar AC Mains Monitoring SystemS3.1 S3.2 S3.3 S3.7 S3.8 INVs Operating modes Assignment of the signal terminalsSwitchover without gap Switchover with gap Installation Connecting the Loads / DC / MainsStart-Up ConnectionDisconnection Maintenance For systems with SBS additionally TroubleshootingOutput Voltage Deviation Technical Data General Data INVFault Overtemperature ϑCollective fault OperationGeneral Data SBS With safe isolation at UO ≤ 60 V DC UniVert 2 inverter Electrical Data At 24 Type E-number G110 E230/10,9/2rfg-CFp2,5 3000000263 Type E-number E230 E230/115/2-VFp26,5-8 3000000646 Dimensional Drawing Inverter dimensions type 1.5 and 3.3 kVAInverter dimensions type 2.5 kVA SBS dimensions