AEG 8000012364 BAL ON/OFF Switch, Can Bus Interfaces X6, DIL Switch, S2.1 S2.2 S2.3, INVs

Page 18

"UniVert 2" inverter

3.7ON/OFF Switch

The inverter is set ready for operation using the DOU switch on the front panel. The monitoring functions with their respective messages are only active when the inverter is switched on. After switch-off, all faults are acknowledged. The settings of the DIL switches are only accepted if the unit is switched off!

3.8CAN Bus Interfaces X6 / X7

The unit can be controlled and monitored using the 10-pin CAN bus connector X6 if the INV is installed in a power supply cabinet with PSM control unit.

The CAN bus connector X7 has no significance if one inverter in single operation operated without SBS. Both ends of the bus have to be connected to a terminating resistor when several INVs are operated in parallel!

For operation with SBS, only the end of the bus on the INV must have a terminating resistor connected; a bus terminating resistor is integrated in the SBS! (See Figure 1.)

3.9DIL Switch

An 8-pin DIL switch is arranged below the LCD. All settings of / changes to the DIL switch are only activated after the INV has been switched off using the ON/OFF switch. It is counted from the left S2.1 to the right S2.8, switches that are pushed in at the bottom signify "open"! The setting of the switches is shown on the display as a check whenever a change is made; 0 = open; 1 = closed.

Switches S2.1, S2.2 and S2.3: Number of parallel INVs in the system

The settings must be the same on all INVs and the SBS! Standard setting:

1 INV: S2.1, S2.2 and S2.3 open

 

S2.1

S2.2

S2.3

 

 

 

 

1 INV

0

0

0

 

 

 

 

2 INVs

0

0

1

 

 

 

 

3 INVs

0

1

0

 

 

 

 

4 INVs

0

1

1

5 INVs

1

0

0

 

 

 

 

6 INVs

1

0

1

7 INVs

1

1

0

 

 

 

 

8 INVs

1

1

1

Page 18 of 42

8000012364 BAL, en

Image 18
Contents Operating Instructions UniVert 2 inverter and SBS option Validity WarrantyDuty to Provide Information HandlingAbbreviations HotlineCopyright Table of Contents Maintenance Troubleshooting Technical DataDimensional Drawing Safety Instructions Important Instructions and ExplanationsAccident Prevention Regulations Qualified Personnel Safety Awareness ApplicationLiability DirectivesGeneral Information System DescriptionParallel INV operation Function of the SystemIndividual INV operation Individual or parallel operation with SBSParallel INV operation Block diagram of the inverter Description of the INVPrinciple of Operation of the INV, Electrical Description of the SBS SBSPrinciple of Operation of the SBS, Electrical Function of the Inverter Can Bus Interfaces X6 ON/OFF SwitchDIL Switch S2.1 S2.2 S2.3INVs Settings must be the same on all INVs and the SBS Switches S2.4, S2.5 and S2.6 Own Address INVSwitches S2.7 and S2.8 Number of redundant INVs S2.4 S2.5 S2.6 AddressSignalling, Displays and Remote Signals Display Colour Operating statusSwitchback Attempts Function of the SBS optionalOperating Statuses AC Busbar Reset ButtonAC Mains Input AC Mains Monitoring SystemS3.1 S3.2 S3.3 S3.7 S3.8 INVs Assignment of the signal terminals Switchover without gapOperating modes Switchover with gap Start-Up InstallationConnecting the Loads / DC / Mains ConnectionDisconnection Maintenance Troubleshooting Output Voltage DeviationFor systems with SBS additionally Technical Data General Data INVCollective fault FaultOvertemperature ϑ OperationGeneral Data SBS With safe isolation at UO ≤ 60 V DC UniVert 2 inverter Electrical Data At 24 Type E-number G110 E230/10,9/2rfg-CFp2,5 3000000263 Type E-number E230 E230/115/2-VFp26,5-8 3000000646 Dimensional Drawing Inverter dimensions type 1.5 and 3.3 kVAInverter dimensions type 2.5 kVA SBS dimensions