AEG 8000012364 BAL operating instructions Electrical Data

Page 36

"UniVert 2" inverter

8.3Electrical Data

Type E-number

G48 – 60 E230/14,4/2rfg-CFp3,3

3000000352

G220 E 230/14,4/2rfg-CFp3,3

300000601

Rated output capacity

3.3 kVA

 

 

 

 

 

with power factor

0.8

 

 

 

 

 

Power factor range

0 inductive to 0 capacitive

 

 

 

 

Rated output voltage

230 V ±0.5 static, ±3% dynamic at 100% load connection

 

 

 

 

Output frequency

50 Hz ±0.05%

 

 

 

 

 

THD factor

< 3%

 

 

 

 

 

 

Rated output current

14.4 A

 

14.4 A

 

 

 

 

 

DC rated input voltage

48 V -15% / 60 V +20%

 

220 V -15% +20%

 

 

 

 

 

DC rated current

64 A at 48 V / 51 A at 60 V

 

14 A at 220 V

 

 

 

 

 

Efficiency

> 85%

 

 

> 86%

 

 

 

 

DC input current ripple

< 10% of DC rated current

 

 

 

 

 

Monitoring systems

 

 

 

 

 

 

 

 

DC undervoltage, switch-off

Fault < 85% of 48 V (40.8 V),

 

 

Fault < 85% of 220 V (187 V),

 

without delay

 

 

without delay

 

Acknowledgement > 103% of 48 V

 

 

Acknowledgement > 103% of

 

(49.4 V), 15 s delay

 

 

220 V (226 V), 15 s delay

 

 

 

 

 

DC overvoltage, switch-off

Fault > 128% of 60 V (76.8 V),

 

 

Fault > 128% of 220 V (281 V),

 

without delay

 

 

without delay

 

Acknowledgement < 125% of 60 V

 

 

Acknowledgement < 125% of

 

(75 V), 15 s delay

 

 

220 V (275 V), 15 s delay

 

 

 

 

AC undervoltage, switch-off

Fault < 90% rated (207 V), 2.5 s delay

 

Acknowledgement by ON/OFF switch

 

 

Overtemperature, switch-off

Fault > 80 °C, acknowledgement < 70 °C, approx. 5 s delay

 

 

 

 

 

Page 36 of 42

8000012364 BAL, en

Image 36
Contents Operating Instructions UniVert 2 inverter and SBS option Warranty Duty to Provide InformationValidity HandlingAbbreviations HotlineCopyright Table of Contents Maintenance Troubleshooting Technical DataDimensional Drawing Safety Instructions Important Instructions and ExplanationsAccident Prevention Regulations Qualified Personnel Safety Awareness ApplicationLiability DirectivesGeneral Information System DescriptionFunction of the System Individual INV operationParallel INV operation Individual or parallel operation with SBSParallel INV operation Block diagram of the inverter Description of the INVPrinciple of Operation of the INV, Electrical Description of the SBS SBSPrinciple of Operation of the SBS, Electrical Function of the Inverter ON/OFF Switch DIL SwitchCan Bus Interfaces X6 S2.1 S2.2 S2.3Switches S2.4, S2.5 and S2.6 Own Address INV Switches S2.7 and S2.8 Number of redundant INVsINVs Settings must be the same on all INVs and the SBS S2.4 S2.5 S2.6 AddressSignalling, Displays and Remote Signals Display Colour Operating statusSwitchback Attempts Function of the SBS optionalOperating Statuses Reset Button AC Mains InputAC Busbar AC Mains Monitoring SystemS3.1 S3.2 S3.3 S3.7 S3.8 INVs Assignment of the signal terminals Switchover without gapOperating modes Switchover with gap Installation Connecting the Loads / DC / MainsStart-Up ConnectionDisconnection Maintenance Troubleshooting Output Voltage DeviationFor systems with SBS additionally Technical Data General Data INVFault Overtemperature ϑCollective fault OperationGeneral Data SBS With safe isolation at UO ≤ 60 V DC UniVert 2 inverter Electrical Data At 24 Type E-number G110 E230/10,9/2rfg-CFp2,5 3000000263 Type E-number E230 E230/115/2-VFp26,5-8 3000000646 Dimensional Drawing Inverter dimensions type 1.5 and 3.3 kVAInverter dimensions type 2.5 kVA SBS dimensions