AEG 8000012364 BAL operating instructions Type E-number G110 E230/10,9/2rfg-CFp2,5 3000000263

Page 38

"UniVert 2" inverter

Type E-number

G110 E230/10,9/2rfg-CFp2,5

3000000263

Rated output capacity

2.5 kVA

 

 

with power factor

0.8

 

 

Power factor range

0 inductive to 0 capacitive

 

 

Rated output voltage

230 V ±0.5 static, ±3% dynamic at 100% load change

 

 

Output frequency

50 Hz ±0.05%

 

 

THD factor

< 3%

 

 

Rated output current

10.9 A

 

 

DC rated input voltage

110 V -15% ... +20%

 

 

DC rated current

20.4 A at 110 V

 

 

Efficiency

>88%

 

 

DC input current ripple

< 50% of DC rated current

 

 

Monitoring systems

 

 

 

DC undervoltage, switch-off

Fault < 85% of 110 V (93.5 V), without delay

 

Acknowledgement > 103% of 110 V (113.3 V), 15 s delay

 

 

DC overvoltage, switch-off

Fault > 128% of 110 V (140.8 V), without delay

 

Acknowledgement < 125% of 110 V (137 V), 15 s delay

 

 

AC undervoltage, switch-off

Fault < 90% rated (207 V), 2.5 s delay

 

Acknowledgement by ON/OFF switch

 

 

Overtemperature, switch-off

Fault > 80 °C, acknowledgement < 70 °C, approx. 5 s delay

 

 

Page 38 of 42

8000012364 BAL, en

Image 38
Contents Operating Instructions UniVert 2 inverter and SBS option Validity WarrantyDuty to Provide Information HandlingCopyright AbbreviationsHotline Table of Contents Dimensional Drawing Maintenance TroubleshootingTechnical Data Accident Prevention Regulations Safety InstructionsImportant Instructions and Explanations Qualified Personnel Safety Awareness ApplicationLiability DirectivesGeneral Information System DescriptionParallel INV operation Function of the SystemIndividual INV operation Individual or parallel operation with SBSParallel INV operation Block diagram of the inverter Description of the INVPrinciple of Operation of the INV, Electrical Description of the SBS SBSPrinciple of Operation of the SBS, Electrical Function of the Inverter Can Bus Interfaces X6 ON/OFF SwitchDIL Switch S2.1 S2.2 S2.3INVs Settings must be the same on all INVs and the SBS Switches S2.4, S2.5 and S2.6 Own Address INVSwitches S2.7 and S2.8 Number of redundant INVs S2.4 S2.5 S2.6 AddressSignalling, Displays and Remote Signals Display Colour Operating statusOperating Statuses Switchback AttemptsFunction of the SBS optional AC Busbar Reset ButtonAC Mains Input AC Mains Monitoring SystemS3.1 S3.2 S3.3 S3.7 S3.8 INVs Operating modes Assignment of the signal terminalsSwitchover without gap Switchover with gap Start-Up InstallationConnecting the Loads / DC / Mains ConnectionDisconnection Maintenance For systems with SBS additionally TroubleshootingOutput Voltage Deviation Technical Data General Data INVCollective fault FaultOvertemperature ϑ OperationGeneral Data SBS With safe isolation at UO ≤ 60 V DC UniVert 2 inverter Electrical Data At 24 Type E-number G110 E230/10,9/2rfg-CFp2,5 3000000263 Type E-number E230 E230/115/2-VFp26,5-8 3000000646 Dimensional Drawing Inverter dimensions type 1.5 and 3.3 kVAInverter dimensions type 2.5 kVA SBS dimensions