AEG 8000012364 BAL operating instructions At 24

Page 37

"UniVert 2" inverter

Type E-number

G48 – 60 E230/6,5/2rfg-CFp1,5

3000000351

G24 E230/6,5/2rfg-CFp1,5

3000000602

Rated output capacity

1.5 kVA

 

 

 

 

 

with power factor

0.8

 

 

 

 

 

Power factor range

0 inductive to 0 capacitive

 

 

 

 

Rated output voltage

230 V ±0.5 static, ±3% dynamic at 100% load change

 

 

 

 

Output frequency

50 Hz ±0.05%

 

 

 

 

THD factor

< 3%

 

 

 

 

 

Rated output current

6.5 A

 

6.5 A

 

 

 

 

 

DC rated input voltage

48 V -15% / 60 V +20%

 

24 V -15% +20%

 

 

 

 

 

DC rated current

29 A at 48 V / 23 A at 60 V

 

62 A at 24 V

 

 

 

 

 

Efficiency

> 85%

 

 

> 80%

 

 

 

 

DC input current ripple

< 10% of DC rated current

 

 

 

 

 

Monitoring systems

 

 

 

 

 

 

 

 

DC undervoltage, switch-off

Fault < 85% of 48 V (40.8 V),

 

 

Fault < 85% of 24 V (20.4 V),

 

without delay

 

 

without delay

 

Acknowledgement > 103% of 48 V

 

 

Acknowledgement > 103% of 24 V

 

(49.4 V), 15 s delay

 

 

(24.7 V), 15 s delay

 

 

 

 

 

DC overvoltage, switch-off

Fault > 128% of 60 V (76.8 V),

 

 

Fault > 128% of 24 V (30,7 V),

 

without delay

 

 

without delay

 

Acknowledgement < 125% of 60 V

 

 

Acknowledgement < 125% of 24 V

 

(75 V), 15 s delay

 

 

(30 V), 15 s delay

AC undervoltage, switch-off

Fault < 90% rated (207 V), 2.5 s delay

 

Acknowledgement by ON/OFF switch

 

 

Overtemperature, switch-off

Fault > 80 °C, acknowledgement < 70 °C, approx. 5 s delay

 

 

 

 

 

Page 37 of 42

8000012364 BAL, en

Image 37
Contents Operating Instructions UniVert 2 inverter and SBS option Duty to Provide Information WarrantyValidity HandlingHotline AbbreviationsCopyright Table of Contents Technical Data Maintenance TroubleshootingDimensional Drawing Important Instructions and Explanations Safety InstructionsAccident Prevention Regulations Qualified Personnel Application Safety AwarenessDirectives LiabilitySystem Description General InformationIndividual INV operation Function of the SystemParallel INV operation Individual or parallel operation with SBSParallel INV operation Description of the INV Block diagram of the inverterPrinciple of Operation of the INV, Electrical SBS Description of the SBSPrinciple of Operation of the SBS, Electrical Function of the Inverter DIL Switch ON/OFF SwitchCan Bus Interfaces X6 S2.1 S2.2 S2.3Switches S2.7 and S2.8 Number of redundant INVs Switches S2.4, S2.5 and S2.6 Own Address INVINVs Settings must be the same on all INVs and the SBS S2.4 S2.5 S2.6 AddressDisplay Colour Operating status Signalling, Displays and Remote SignalsFunction of the SBS optional Switchback AttemptsOperating Statuses AC Mains Input Reset ButtonAC Busbar AC Mains Monitoring SystemS3.1 S3.2 S3.3 S3.7 S3.8 INVs Switchover without gap Assignment of the signal terminalsOperating modes Switchover with gap Connecting the Loads / DC / Mains InstallationStart-Up ConnectionDisconnection Maintenance Output Voltage Deviation TroubleshootingFor systems with SBS additionally General Data INV Technical DataOvertemperature ϑ FaultCollective fault OperationGeneral Data SBS With safe isolation at UO ≤ 60 V DC UniVert 2 inverter Electrical Data At 24 Type E-number G110 E230/10,9/2rfg-CFp2,5 3000000263 Type E-number E230 E230/115/2-VFp26,5-8 3000000646 Inverter dimensions type 1.5 and 3.3 kVA Dimensional DrawingInverter dimensions type 2.5 kVA SBS dimensions