AEG 8000012364 BAL S3.7 S3.8 INVs, INVs Settings must be the same on all INVs and the SBS

Page 24

"UniVert 2" inverter

Switches S3.7 and S3.8: number of redundant INVs

 

S3.7

S3.8

 

 

 

0 INVs

0

0

 

 

 

1 INV

0

1

 

 

 

2 INVs

1

0

 

 

 

3 INVs

1

1

 

 

 

The settings must be the same on all INVs and the SBS!

Standard setting: S3.7 and S3.8 open

Switches S3.4 and S3.5: not used

Switch S3.6: Switchover with gap (yes/no)

Standard setting: switchover not with gap - S3.6 open

i.e. in the event of phase deviations between INV and SBS, the SBS blocks.

If switchover with gap is selected (- S3.6 closed), the SBS does not block in the event of a phase deviation (see chapter 4.12).

4.12Signalling, Displays and Remote Signals (X4)

The following signals are indicated via LEDs on the front panel:

Display

Colour

Operating status

SBS

green

 

SBS is in operation,

operation

 

 

operating voltage present

 

 

 

 

INV present

green

 

INV voltage present

 

 

 

 

Mains

green

 

Mains voltage present

present

 

 

 

Synchronism

green

 

Mains and INV run synchronously

 

 

 

 

Load on INV

green

 

The INV supplies the load

 

 

 

 

Load

green

 

The mains supplies the load

on the mains

 

 

 

 

 

 

 

Collective

red

 

Collective fault signal delayed by 20 s,

fault

 

 

the signalling relay is triggered at the same

 

 

 

time.

The unit is equipped with a liquid-crystal display.

The following displays are to be expected during the corresponding operating statuses.

Mains operation: "U=230.0V" Load voltage

"I=13.7A" SBS current

Page 24 of 42

8000012364 BAL, en

Image 24
Contents Operating Instructions UniVert 2 inverter and SBS option Warranty Duty to Provide InformationValidity HandlingAbbreviations HotlineCopyright Table of Contents Maintenance Troubleshooting Technical DataDimensional Drawing Safety Instructions Important Instructions and ExplanationsAccident Prevention Regulations Qualified Personnel Safety Awareness ApplicationLiability DirectivesGeneral Information System DescriptionFunction of the System Individual INV operationParallel INV operation Individual or parallel operation with SBSParallel INV operation Block diagram of the inverter Description of the INVPrinciple of Operation of the INV, Electrical Description of the SBS SBSPrinciple of Operation of the SBS, Electrical Function of the Inverter ON/OFF Switch DIL SwitchCan Bus Interfaces X6 S2.1 S2.2 S2.3Switches S2.4, S2.5 and S2.6 Own Address INV Switches S2.7 and S2.8 Number of redundant INVsINVs Settings must be the same on all INVs and the SBS S2.4 S2.5 S2.6 AddressSignalling, Displays and Remote Signals Display Colour Operating statusSwitchback Attempts Function of the SBS optionalOperating Statuses Reset Button AC Mains InputAC Busbar AC Mains Monitoring SystemS3.1 S3.2 S3.3 S3.7 S3.8 INVs Assignment of the signal terminals Switchover without gapOperating modes Switchover with gap Installation Connecting the Loads / DC / MainsStart-Up ConnectionDisconnection Maintenance Troubleshooting Output Voltage DeviationFor systems with SBS additionally Technical Data General Data INVFault Overtemperature ϑCollective fault OperationGeneral Data SBS With safe isolation at UO ≤ 60 V DC UniVert 2 inverter Electrical Data At 24 Type E-number G110 E230/10,9/2rfg-CFp2,5 3000000263 Type E-number E230 E230/115/2-VFp26,5-8 3000000646 Dimensional Drawing Inverter dimensions type 1.5 and 3.3 kVAInverter dimensions type 2.5 kVA SBS dimensions