AEG 8000012364 BAL Start-Up, Installation, Connection, Connecting the Loads / DC / Mains

Page 27

"UniVert 2" inverter

5 Start-Up

5.1Installation

When installing the INV, the following regulations must be observed:

The INV has been designed for use in a dry room, practically free of dust.

It is imperative to observe the specifications concerning ambient temperature and site altitude (see chapter “Technical Data”).

Severe dust accumulation or a chemically aggressive atmosphere are not permissible; the system must be especially protected against conductive, humid dust deposits and condensation.

The INV functions with forced air cooling. The supply air temperature must not exceed 45°C. The power loss of an INV is below 340 W at rated load.

The inverter must be installed in suitable module racks.

5.2Connection

Before connecting the unit to the DC supply, ensure that the voltage values given on the nameplate correspond to the supplied voltages. The load is connected using terminals X2 (L1, N) on the front of the unit. The DC supply is connected using terminals X1 (L-, L+). The INV has to be earthed using a separate PE connection on the front of the unit. The cross-section of the PE conductor must be chosen in acc. with VDE 0100 Part 540 depending on the type of installation.

The discharge current lies below 3.5 mA. Prior to start-up, a PE conductor connection must be established.

With earthed DC systems, only the pole of the INV DC connection that is not earthed needs protection. Observe correct polarity of the DC lines.

The load current must be checked before connecting the load; a permanent overload is not permissible and has a very negative impact on the reliability and the service life of the unit.

DIL switch (see chapter 3.9 or chapter 4.11) CAN bus (see chapter 3.8 or chapter 4.10) Remote signals (see chapter 3.10 or chapter 4.12)

5.3Connecting the Loads / DC / Mains

When all lines have been connected completely, proceed as follows:

Individual INV operation:

Switch off the INV, switch on miniature circuit-breaker F1

Connect the DC supply (The INV has a softstart device that limits the charging current in the input capacitors to a value below the rated current of the unit.)

Switch on the INV

Connect the load

Page 27 of 42

8000012364 BAL, en

Image 27 Contents
Operating Instructions UniVert 2 inverter and SBS option Handling WarrantyDuty to Provide Information ValidityAbbreviations HotlineCopyright Table of Contents Maintenance Troubleshooting Technical DataDimensional Drawing Safety Instructions Important Instructions and ExplanationsAccident Prevention Regulations Qualified Personnel Application Safety AwarenessDirectives LiabilitySystem Description General InformationIndividual or parallel operation with SBS Function of the SystemIndividual INV operation Parallel INV operationParallel INV operation Description of the INV Block diagram of the inverterPrinciple of Operation of the INV, Electrical SBS Description of the SBSPrinciple of Operation of the SBS, Electrical Function of the Inverter S2.1 S2.2 S2.3 ON/OFF SwitchDIL Switch Can Bus Interfaces X6S2.4 S2.5 S2.6 Address Switches S2.4, S2.5 and S2.6 Own Address INVSwitches S2.7 and S2.8 Number of redundant INVs INVs Settings must be the same on all INVs and the SBSDisplay Colour Operating status Signalling, Displays and Remote SignalsSwitchback Attempts Function of the SBS optionalOperating Statuses AC Mains Monitoring System Reset ButtonAC Mains Input AC BusbarS3.1 S3.2 S3.3 S3.7 S3.8 INVs Assignment of the signal terminals Switchover without gapOperating modes Switchover with gap Connection InstallationConnecting the Loads / DC / Mains Start-UpDisconnection Maintenance Troubleshooting Output Voltage DeviationFor systems with SBS additionally General Data INV Technical DataOperation FaultOvertemperature ϑ Collective faultGeneral Data SBS With safe isolation at UO ≤ 60 V DC UniVert 2 inverter Electrical Data At 24 Type E-number G110 E230/10,9/2rfg-CFp2,5 3000000263 Type E-number E230 E230/115/2-VFp26,5-8 3000000646 Inverter dimensions type 1.5 and 3.3 kVA Dimensional DrawingInverter dimensions type 2.5 kVA SBS dimensions