AEG 8000012364 BAL operating instructions With safe isolation at UO ≤ 60 V DC

Page 34

"UniVert 2" inverter

- Power cables

Burst test in acc. with

 

 

EN 61000-4-4, 2 kV

 

 

Surge test in acc. with

 

 

EN 61000-4-5,

 

 

2 kV asymmetrical

 

- Control cables

Burst test in acc. with

 

 

EN 61000-4-4, 2 kV

 

 

Surge test in acc. with

 

 

EN 61000-4-5,

 

 

2 kV asymmetrical

 

Functional extra-low voltage

With safe isolation at UO 60 V DC

 

to VDE 0100 Part 410 11.83

 

Section 4.3.2

 

Overload behaviour

1.6 x rated current for 1 minute

 

1.3 x rated current for 10 minutes

 

The mains fuse used must be

 

taken into consideration!

Max. load fusing

gL 40A

 

Messages

- Operation

LED green

 

- INV voltage present

LED green

 

- Mains volt. present

LED green

 

- Synchronism

LED green

 

- INV supplies the load LED green

 

- SBS suppl. the load

LED green

 

- Collective fault

LED red

Remote signals (X4)

Collective fault signal via potential-

 

free relay contact X4.1,2,3

 

(safe isolation)

 

 

INV operation signal via potential-

 

free relay contact X4.4,5,6

 

(safe isolation)

 

 

Max. contact load:

 

 

150 V DC < 1.6 A

 

 

Min. contact load: 12 V 0.1 A

Monitoring systems

- Load undervoltage

 

 

- Load overvoltage

 

 

- Mains undervoltage

 

 

- Mains overvoltage

 

 

- Heat sink overtemperature

 

- Mains / INV synchronism

 

- Self-test, watchdog

 

 

- Internal auxiliary voltages

Design

19" mounting rail for installation in

 

module rack in acc. with

 

DIN 41494

 

Page 34 of 42

8000012364 BAL, en

Image 34
Contents Operating Instructions UniVert 2 inverter and SBS option Validity WarrantyDuty to Provide Information HandlingHotline AbbreviationsCopyright Table of Contents Technical Data Maintenance TroubleshootingDimensional Drawing Important Instructions and Explanations Safety InstructionsAccident Prevention Regulations Qualified Personnel Safety Awareness ApplicationLiability DirectivesGeneral Information System DescriptionParallel INV operation Function of the SystemIndividual INV operation Individual or parallel operation with SBSParallel INV operation Block diagram of the inverter Description of the INVPrinciple of Operation of the INV, Electrical Description of the SBS SBSPrinciple of Operation of the SBS, Electrical Function of the Inverter Can Bus Interfaces X6 ON/OFF SwitchDIL Switch S2.1 S2.2 S2.3INVs Settings must be the same on all INVs and the SBS Switches S2.4, S2.5 and S2.6 Own Address INVSwitches S2.7 and S2.8 Number of redundant INVs S2.4 S2.5 S2.6 AddressSignalling, Displays and Remote Signals Display Colour Operating statusFunction of the SBS optional Switchback AttemptsOperating Statuses AC Busbar Reset ButtonAC Mains Input AC Mains Monitoring SystemS3.1 S3.2 S3.3 S3.7 S3.8 INVs Switchover without gap Assignment of the signal terminalsOperating modes Switchover with gap Start-Up InstallationConnecting the Loads / DC / Mains ConnectionDisconnection Maintenance Output Voltage Deviation TroubleshootingFor systems with SBS additionally Technical Data General Data INVCollective fault FaultOvertemperature ϑ OperationGeneral Data SBS With safe isolation at UO ≤ 60 V DC UniVert 2 inverter Electrical Data At 24 Type E-number G110 E230/10,9/2rfg-CFp2,5 3000000263 Type E-number E230 E230/115/2-VFp26,5-8 3000000646 Dimensional Drawing Inverter dimensions type 1.5 and 3.3 kVAInverter dimensions type 2.5 kVA SBS dimensions