"UniVert 2" inverter
- Power cables | Burst test in acc. with |
|
| EN |
|
| Surge test in acc. with |
|
| EN |
|
| 2 kV asymmetrical |
|
- Control cables | Burst test in acc. with |
|
| EN |
|
| Surge test in acc. with |
|
| EN |
|
| 2 kV asymmetrical |
|
Functional | With safe isolation at UO ≤ 60 V DC | |
| to VDE 0100 Part 410 11.83 | |
| Section 4.3.2 |
|
Overload behaviour | 1.6 x rated current for 1 minute | |
| 1.3 x rated current for 10 minutes | |
| The mains fuse used must be | |
| taken into consideration! | |
Max. load fusing | gL 40A |
|
Messages | - Operation | LED green |
| - INV voltage present | LED green |
| - Mains volt. present | LED green |
| - Synchronism | LED green |
| - INV supplies the load LED green | |
| - SBS suppl. the load | LED green |
| - Collective fault | LED red |
Remote signals (X4) | Collective fault signal via potential- | |
| free relay contact X4.1,2,3 | |
| (safe isolation) |
|
| INV operation signal via potential- | |
| free relay contact X4.4,5,6 | |
| (safe isolation) |
|
| Max. contact load: |
|
| 150 V DC < 1.6 A |
|
| Min. contact load: 12 V 0.1 A | |
Monitoring systems | - Load undervoltage |
|
| - Load overvoltage |
|
| - Mains undervoltage |
|
| - Mains overvoltage |
|
| - Heat sink overtemperature | |
| - Mains / INV synchronism | |
| - |
|
| - Internal auxiliary voltages | |
Design | 19" mounting rail for installation in | |
| module rack in acc. with | |
| DIN 41494 |
|