"UniVert 2" inverter
8 Technical Data
8.1General Data INV
DC input current | < rated input current |
DC fuse required | gL 80 A with type 3.3 kVA 48 V |
| gL 63 A with type 3.3 kVA 60 V |
| gL 20 A with type 3.3 kVA 220 V |
| gL 80 A with type 1.5 kVA 24 V |
| gL 36 A with type 1.5 kVA 48 V |
| gL 32 A with type 1.5 kVA 60 V |
| gL 25 A with type 2.5 kVA 110 V |
Manufacturing and type test | In acc. with DIN 60146 Part |
Emitted interference in acc. with EN | |
- Conducted interference | In acc. with EN 55022 Class "B" |
- Emission | In acc. with EN 55022 Class "B" |
Noise immunity in acc. with EN | |
- Housing | ESD test to EN |
| 6 kV contact |
| HF field to EN |
| 10 V/m (30 MHz – 1 GHz) |
- Power cables | Burst test in acc. with |
| EN |
| Surge test in acc. with |
| EN |
| 2 kV asymmetrical |
- Control cables | Burst test in acc. with |
| EN |
| Surge test in acc. with |
| EN |
| 2 kV asymmetrical |
Functional | With safe isolation at UO ≤ 60 V DC |
| to VDE 0100 Part 410 11.83 |
| Section 4.3.2 |
Dynamic response | ≤ 3% with sudden load fluctuations |
| between |
| output current |
Overload behaviour | 1.6 x rated current for 1 minute |
| 1.3 x rated current for 10 minutes |