AEG 8000012364 BAL operating instructions Technical Data, General Data INV

Page 31

"UniVert 2" inverter

8 Technical Data

8.1General Data INV

DC input current

< rated input current

DC fuse required

gL 80 A with type 3.3 kVA 48 V

 

gL 63 A with type 3.3 kVA 60 V

 

gL 20 A with type 3.3 kVA 220 V

 

gL 80 A with type 1.5 kVA 24 V

 

gL 36 A with type 1.5 kVA 48 V

 

gL 32 A with type 1.5 kVA 60 V

 

gL 25 A with type 2.5 kVA 110 V

Manufacturing and type test

In acc. with DIN 60146 Part 1-1

Emitted interference in acc. with EN 50081-1

- Conducted interference

In acc. with EN 55022 Class "B"

- Emission

In acc. with EN 55022 Class "B"

Noise immunity in acc. with EN 50082-2

- Housing

ESD test to EN 61000-4-2,

 

6 kV contact

 

HF field to EN 61000-4-3,

 

10 V/m (30 MHz – 1 GHz)

- Power cables

Burst test in acc. with

 

EN 61000-4-4, 2 kV

 

Surge test in acc. with

 

EN 61000-4-5,

 

2 kV asymmetrical

- Control cables

Burst test in acc. with

 

EN 61000-4-4, 2 kV

 

Surge test in acc. with

 

EN 61000-4-5,

 

2 kV asymmetrical

Functional extra-low voltage

With safe isolation at UO 60 V DC

 

to VDE 0100 Part 410 11.83

 

Section 4.3.2

Dynamic response

3% with sudden load fluctuations

 

between 0%-100%-0% rated

 

output current

Overload behaviour

1.6 x rated current for 1 minute

 

1.3 x rated current for 10 minutes

Short-circuiting

Continued short-circuit-proof

Page 31 of 42

8000012364 BAL, en

Image 31
Contents Operating Instructions UniVert 2 inverter and SBS option Handling WarrantyDuty to Provide Information ValidityHotline AbbreviationsCopyright Table of Contents Technical Data Maintenance TroubleshootingDimensional Drawing Important Instructions and Explanations Safety InstructionsAccident Prevention Regulations Qualified Personnel Application Safety AwarenessDirectives LiabilitySystem Description General InformationIndividual or parallel operation with SBS Function of the SystemIndividual INV operation Parallel INV operationParallel INV operation Description of the INV Block diagram of the inverterPrinciple of Operation of the INV, Electrical SBS Description of the SBSPrinciple of Operation of the SBS, Electrical Function of the Inverter S2.1 S2.2 S2.3 ON/OFF SwitchDIL Switch Can Bus Interfaces X6S2.4 S2.5 S2.6 Address Switches S2.4, S2.5 and S2.6 Own Address INVSwitches S2.7 and S2.8 Number of redundant INVs INVs Settings must be the same on all INVs and the SBSDisplay Colour Operating status Signalling, Displays and Remote SignalsFunction of the SBS optional Switchback AttemptsOperating Statuses AC Mains Monitoring System Reset ButtonAC Mains Input AC BusbarS3.1 S3.2 S3.3 S3.7 S3.8 INVs Switchover without gap Assignment of the signal terminalsOperating modes Switchover with gap Connection InstallationConnecting the Loads / DC / Mains Start-UpDisconnection Maintenance Output Voltage Deviation TroubleshootingFor systems with SBS additionally General Data INV Technical DataOperation FaultOvertemperature ϑ Collective faultGeneral Data SBS With safe isolation at UO ≤ 60 V DC UniVert 2 inverter Electrical Data At 24 Type E-number G110 E230/10,9/2rfg-CFp2,5 3000000263 Type E-number E230 E230/115/2-VFp26,5-8 3000000646 Inverter dimensions type 1.5 and 3.3 kVA Dimensional DrawingInverter dimensions type 2.5 kVA SBS dimensions