AEG 8000012364 BAL operating instructions Type E-number E230 E230/115/2-VFp26,5-8 3000000646

Page 39

"UniVert 2" inverter

Type E-number

E230 E230/115/2-VFp26,5-8

3000000646

Rated output capacity

26.5 kVA

 

 

Power loss

< 200 W

 

 

AC rated input voltage

230 V

 

 

AC rated input frequency

50 Hz

 

 

Monitoring systems

 

 

 

AC mains undervoltage,

Fault < 90% nominal (207 V), without delay

blocking of the SBS

Acknowledgement > 90% nominal (211 V)

 

 

 

AC mains overvoltage,

Fault > 110% nominal (253 V), without delay

blocking of the SBS

Acknowledgement < 110% nominal (248 V)

 

 

 

AC load undervoltage,

Fault < 88% nominal (202 V), without delay

switchover to mains

Acknowledgement > 88% nominal (207 V)

 

 

AC load overvoltage, switchover

Fault > 112% nominal (258 V), without delay

to mains

Acknowledgement < 112% nominal (253 V)

 

 

 

Overtemperature, message

Fault > 80°C, acknowledgement < 70°C, 4 s delay

 

self-acknowledging

 

 

Synchronism

Fault phase deviation > 3° el., without delay

INV / SBS circuit

Acknowledgement phase deviation < 2.9° el., 2 s delay

 

 

Page 39 of 42

8000012364 BAL, en

Image 39
Contents Operating Instructions UniVert 2 inverter and SBS option Handling WarrantyDuty to Provide Information ValidityAbbreviations HotlineCopyright Table of Contents Maintenance Troubleshooting Technical DataDimensional Drawing Safety Instructions Important Instructions and ExplanationsAccident Prevention Regulations Qualified Personnel Application Safety AwarenessDirectives LiabilitySystem Description General InformationIndividual or parallel operation with SBS Function of the SystemIndividual INV operation Parallel INV operationParallel INV operation Description of the INV Block diagram of the inverterPrinciple of Operation of the INV, Electrical SBS Description of the SBSPrinciple of Operation of the SBS, Electrical Function of the Inverter S2.1 S2.2 S2.3 ON/OFF SwitchDIL Switch Can Bus Interfaces X6S2.4 S2.5 S2.6 Address Switches S2.4, S2.5 and S2.6 Own Address INVSwitches S2.7 and S2.8 Number of redundant INVs INVs Settings must be the same on all INVs and the SBSDisplay Colour Operating status Signalling, Displays and Remote SignalsSwitchback Attempts Function of the SBS optionalOperating Statuses AC Mains Monitoring System Reset ButtonAC Mains Input AC BusbarS3.1 S3.2 S3.3 S3.7 S3.8 INVs Assignment of the signal terminals Switchover without gapOperating modes Switchover with gap Connection InstallationConnecting the Loads / DC / Mains Start-UpDisconnection Maintenance Troubleshooting Output Voltage DeviationFor systems with SBS additionally General Data INV Technical DataOperation FaultOvertemperature ϑ Collective faultGeneral Data SBS With safe isolation at UO ≤ 60 V DC UniVert 2 inverter Electrical Data At 24 Type E-number G110 E230/10,9/2rfg-CFp2,5 3000000263 Type E-number E230 E230/115/2-VFp26,5-8 3000000646 Inverter dimensions type 1.5 and 3.3 kVA Dimensional DrawingInverter dimensions type 2.5 kVA SBS dimensions