AEG 8000012364 BAL Operating modes, Assignment of the signal terminals, Switchover without gap

Page 25

"UniVert 2" inverter

With SBS ready:

"U=230.0V"

Load voltage

"

ready"

Operating status

With SBS blocked:

"U=230.0V"

Load voltage

"blocked"

Operating status

With SBS Power Up:

"

"

(nothing displayed)

"PowerUp"

Operating status

With SBS fault:

"

"

(nothing displayed)

"

fault"

Operating status

The busbar voltage and current values are displayed with three decimals before and one decimal after the decimal point. The display accuracy corresponds to class 1 with respect to the rated output value of the unit.

Remote signalling is carried out by means of potential-free contacts via a Combicon connector on the front of the unit.

Assignment of the signal terminals:

SBS fault:

In the event of a signal, X4.2 – X4.3 close, no fault: X4.2 – X4.1

When the SBS is disconnected from the power supply (no mains / INV supply), a fault is signalled!

INV operation:

In the event of a signal, X4.4 – X4.5 close

The remote signals are designed for safe isolation. The minimum load should not be below 12 V and 0.1 A.

4.13Operating modes

Two operating modes can be selected using the DIL switches (see chapter 4.11).

Switchover without gap:

The switchover from INV to SBS is always carried out without interruption. If the INV and SBS circuit are not synchronous, the SBS blocks. If the INV is switched off due to asynchronism or if it fails, the load is not supplied by the SBS.

This operating mode is set ex works and is recommended.

NOTE:

i If the mains are poor or the SBS circuit is supplied by a diesel generator for example, the SBS can be temporarily blocked due to frequency deviations.

Page 25 of 42

8000012364 BAL, en

Image 25
Contents Operating Instructions UniVert 2 inverter and SBS option Duty to Provide Information WarrantyValidity HandlingHotline AbbreviationsCopyright Table of Contents Technical Data Maintenance TroubleshootingDimensional Drawing Important Instructions and Explanations Safety InstructionsAccident Prevention Regulations Qualified Personnel Application Safety AwarenessDirectives LiabilitySystem Description General InformationIndividual INV operation Function of the SystemParallel INV operation Individual or parallel operation with SBSParallel INV operation Description of the INV Block diagram of the inverterPrinciple of Operation of the INV, Electrical SBS Description of the SBSPrinciple of Operation of the SBS, Electrical Function of the Inverter DIL Switch ON/OFF SwitchCan Bus Interfaces X6 S2.1 S2.2 S2.3Switches S2.7 and S2.8 Number of redundant INVs Switches S2.4, S2.5 and S2.6 Own Address INVINVs Settings must be the same on all INVs and the SBS S2.4 S2.5 S2.6 AddressDisplay Colour Operating status Signalling, Displays and Remote SignalsFunction of the SBS optional Switchback AttemptsOperating Statuses AC Mains Input Reset ButtonAC Busbar AC Mains Monitoring SystemS3.1 S3.2 S3.3 S3.7 S3.8 INVs Switchover without gap Assignment of the signal terminalsOperating modes Switchover with gap Connecting the Loads / DC / Mains InstallationStart-Up ConnectionDisconnection Maintenance Output Voltage Deviation TroubleshootingFor systems with SBS additionally General Data INV Technical DataOvertemperature ϑ FaultCollective fault OperationGeneral Data SBS With safe isolation at UO ≤ 60 V DC UniVert 2 inverter Electrical Data At 24 Type E-number G110 E230/10,9/2rfg-CFp2,5 3000000263 Type E-number E230 E230/115/2-VFp26,5-8 3000000646 Inverter dimensions type 1.5 and 3.3 kVA Dimensional DrawingInverter dimensions type 2.5 kVA SBS dimensions