Centurion CP72SR5 installation manual Setting Gate Limits, Start Automated Gate Limits Routine

Page 25

CP80/CP81

L1 L2

control card

TEST

 

 

STATUS

 

SET

SETTING GATE LIMITS (continued)

NB. Ensure you follow the correct procedure!

The procedure for setting D3/D5 and A5 motors is DIFFERENT. The A5 limits have to be set manually (see page 25 and 26), while the D3/D5 motors set their limits automatically (see page 21 to 23).

D3/D5 ONLY (PAGE 23, 24, 25)

-Press the TEST pushbutton while monitoring LED L1.

-When L1 flashes once, release TEST pushbutton. L2 will go out,

L1 will continue to flash once per second. Controller is now in MENU 1 which sets gate limits.

NB. Understand the procedure detailed on page 24 before continuing.

The controller is about to perform the fully automatic setup routine.

CP80/CP81

L1

L2

control card

TEST

 

 

STATUS

 

 

SET

START AUTOMATED GATE LIMITS ROUTINE

-Press TEST pushbutton until STATUS LED illuminates.

-AUTOMATIC set up routine (described on page 24) starts as soon as TEST button is released.

23

Image 25
Contents Sliding Gate Automation Page Major Components Typical D5 Shown Oil Specifications Grade 75W90 Qty 75mlStart kgF RUN kgF Gate Mass kg 300 500 ANTI-LIFT Brackets Duty Cycle Curves Recommended Installation and Cable Thickness REQUIREMENTS† Option 1 Bolt down onto concrete plinth Mechanical Mounting DetailsPage Option 2 Set into concrete plinth Provision for Cables Gearbox Mounting Down Details Useful TIP Mounting Rack200mm Installing Chain Drive Systems Ensure fan has stopped turning Setting Mechanical Clutch A5 onlyMounting of Gate Sensor Mounting Configuration For Steel RackRemovable Connectors Power Wiring see page 15 for Signal WiringSignal Wiring CP80 and CP81 Recommended Lightning Protection Commissioning Block Diagram Gate Closes Towards Left Above Black Blue RED Towards Right Setting Motor DirectionSelecting Programme Mode A5 only Setting Gate LimitsStart Automated Gate Limits Routine Setting Gate LimitsD3/D5 Motor Automatic SET-UP Start Manual Gate Limits Routine Exit Gate Limits Routine D3/D5 onlyA5 Motor Manual SET-UP Align Origin SwitchFunctions Select Exit Gate Limits Routine A5 onlyFactory Defaults Highlighted Timer and Counter Setting Main Unit Menu Measure Fault Finders Guide D3 / D5 Operators Procedure to Programme Controller Back to Factory SettingsGate Opens to Pedestrian and Closes Page Centurion