Centurion CP72SR5 installation manual Exit Gate Limits Routine A5 only, Functions Select

Page 29

CP81

L1 L2

control card

 

TEST

 

STATUS

 

SET

CP81

74

control card

L1 L2

 

TEST

 

STATUS

 

SET

EXIT GATE LIMITS ROUTINE (A5 ONLY)

If the gate limits described on page 26 are successfully completed, then LED L2 will be ON.

-Position SET link as shown above 74 to exit programming unless proceeding to other menus.

FUNCTIONS SELECT

Several different functions can be programmed. The procedure which is similar for all functions is described below in conjunction with TABLE 2 on page 28

STEP 1 - Ensure controller is in Programme Mode (see page 21).

STEP 2 - Press and hold the TEST pushbutton while monitoring LED L1.

STEP 3 - L1 will flash once then go off, twice in short succession then go off, 3 times then go off, etc. The number of flashes represents the menu number.

STEP 4 - Release TEST button when the required main menu (see Table 2, page 28) is selected.

STEP 5 - To select the sub-division of the main menu (see RHS of Table 2), press and hold the TEST pushbutton, while monitoring the STATUS LED to count flashes. The number of times the STATUS LED flashes represents the sub menu number.

STEP 6 - Release TEST pushbutton when the required subdivision is selected. L2 will come ON to indicate that the controller is back in PROGRAMME MODE and another FUNCTION or TIMER (refer to procedure on page 29) can be programmed.

STEP 7 - Remove SET link when all programming is complete.

27

Image 29
Contents Sliding Gate Automation Page Major Components Typical D5 Shown Oil Specifications Grade 75W90 Qty 75mlStart kgF RUN kgF Gate Mass kg 300 500 ANTI-LIFT Brackets Duty Cycle Curves Recommended Installation and Cable Thickness REQUIREMENTS† Option 1 Bolt down onto concrete plinth Mechanical Mounting DetailsPage Option 2 Set into concrete plinth Provision for Cables Gearbox Mounting Down Details Useful TIP Mounting Rack200mm Installing Chain Drive Systems Ensure fan has stopped turning Setting Mechanical Clutch A5 onlyMounting of Gate Sensor Mounting Configuration For Steel RackRemovable Connectors Power Wiring see page 15 for Signal WiringSignal Wiring CP80 and CP81 Recommended Lightning Protection Commissioning Block Diagram Gate Closes Towards Left Above Black Blue RED Towards Right Setting Motor DirectionSelecting Programme Mode A5 only Setting Gate LimitsStart Automated Gate Limits Routine Setting Gate LimitsD3/D5 Motor Automatic SET-UP Start Manual Gate Limits Routine Exit Gate Limits Routine D3/D5 onlyA5 Motor Manual SET-UP Align Origin SwitchFunctions Select Exit Gate Limits Routine A5 onlyFactory Defaults Highlighted Timer and Counter Setting Main Unit Menu Measure Fault Finders Guide D3 / D5 Operators Procedure to Programme Controller Back to Factory SettingsGate Opens to Pedestrian and Closes Page Centurion