2.GATE DOES NOT RUN BUT THE RELAYS ENERGISE WHEN THE UNIT IS ACTIVATED.

2.1Faulty motor circuit

2.1.1Faulty motor relay / FET

2.1.2Motor fuse blown (replace with 16/20A slow blow 5x20mm)

2.1.3Fuseholder making bad contact.

2.1.4Worn motor brushes

2.1.5Loose motor wire

2.1.6Faulty controller

3.GATE OPENS ON ITS OWN.

3.1Permanent trigger input

3.1.1Check for latched Rx or latched house pushbutton

3.2Intermittent fault on pushbutton line (underground joint with moisture build-up)

3.3Outside transmitter with the same code (typically only possible with compatible remotes QD black / TSM etc))

3.4Faulty Rx

4.INTERMITTENT AUTO-CLOSE.

4.1Latching Rx overrides auto-close

4.2Long pulse on trigger input overrides auto-close (check pulse time of intercom gate release)

4.3Faulty infra red beam input

4.4Faulty controller

5.GATE DOES NOT RECOGNISE ITS LIMITS.

5.1Magnet incorrectly mounted (Check page 13 of installation manual)

5.2Faulty magnetic switch

5.3Check connection between switch and controller via DOSS.

5.4Faulty controller

6.GATE DOES NOT TRIGGER AT ALL. (USING TEST PUSHBUTTON)

6.1LCK input activated (Check state of LCK)

6.2Latched input on TRG or FRX input

6.3IRB input activated

6.4Faulty controller

7.GATE OPENS TO PEDESTRIAN AND CLOSES.

7.1Faulty key switch

7.2Faulty wiring on pedestrian input

8.GATE STARTS CLOSING BUT STOPS AND RE-OPENS.

8.1Intermittent IRB trigger (Check alignment and that the supply voltage for beams is compatible with the operator.)

8.2Collision sensitivity set too sensitive

8.3Spurious signal on FRX (if used) or TRG if in Condo / Pirac / Reverse mode

WHILE COMMISSIONING (automatic Setup Routine)

9.GATE OPENS TO THE FULLY OPEN POSITION AND DOES NOT RETURN

9.1Check the battery. (battery voltage should stay above 11.0v while gate is running).

10.GATE DOES SHORT OPEN AND CLOSE CYCLES (L2 COMES ON AGAIN

10.1Poor connection between the DOSS and the controller (check cable and connector).

10.2DOSS not being driven due to missing coupling.

10.3Adjust collision sensitivity (high to medium or to low).

11.GATE DOES NOT RUN BUT THE RELAYS ENERGISE WHEN THE UNIT IS ACTIVATED

11.1Check motor wires are securely terminated.

11.2Check motor fuse (replace with 16/20A slow blow 5x20mm)

11.3Check battery connections are leads.

11.4Check that battery is not flat.

12.THE OPERATOR COMPLETES SETUP ROUTINE CORRECTLY. HOWEVER WHEN ACTIVATED AFTERWARDS, DRIVES AT FULL SPEED INTO MECHANICAL END STOP.

12.1Check that origin marker (magnet) is correctly positioned for the “Crawl Distance” selected (main menu item 13). If in doubt restore controller factory default settings. Refer to the Installation Manual, Table 3 for table of distances.

12.2On an upgraded system, ensure that controller has been restored back to Factory default settings

32

Image 34
Contents Sliding Gate Automation Page Oil Specifications Grade 75W90 Qty 75ml Major Components Typical D5 ShownStart kgF RUN kgF Gate Mass kg 300 500 ANTI-LIFT Brackets Duty Cycle Curves Recommended Installation and Cable Thickness REQUIREMENTS† Mechanical Mounting Details Option 1 Bolt down onto concrete plinthPage Option 2 Set into concrete plinth Provision for Cables Gearbox Mounting Down Details Mounting Rack Useful TIP200mm Installing Chain Drive Systems Setting Mechanical Clutch A5 only Ensure fan has stopped turningMounting Configuration For Steel Rack Mounting of Gate SensorPower Wiring see page 15 for Signal Wiring Removable ConnectorsSignal Wiring CP80 and CP81 Recommended Lightning Protection Commissioning Block Diagram Setting Motor Direction Gate Closes Towards Left Above Black Blue RED Towards RightSelecting Programme Mode Setting Gate Limits A5 onlySetting Gate Limits Start Automated Gate Limits RoutineD3/D5 Motor Automatic SET-UP Exit Gate Limits Routine D3/D5 only Start Manual Gate Limits RoutineAlign Origin Switch A5 Motor Manual SET-UPExit Gate Limits Routine A5 only Functions SelectFactory Defaults Highlighted Timer and Counter Setting Main Unit Menu Measure Procedure to Programme Controller Back to Factory Settings Fault Finders Guide D3 / D5 OperatorsGate Opens to Pedestrian and Closes Page Centurion