Centurion CP72SR5 Exit Gate Limits Routine D3/D5 only, Start Manual Gate Limits Routine

Page 27

TURBO MODE: If desired the set up time can be shortened by manually overriding the automatic “crawl”speed in steps 1, 2, 3 shown on page 24. This is done by pressing and holding the TEST button. The speed increases to FULL speed while the button is depressed.

NB. Do not run the gate into the end stops at full speed.

CP80

L1 L2

control card

 

TEST

 

STATUS

 

SET

CP80

74

control card

L1 L2

 

TEST

 

STATUS

 

SET

EXIT GATE LIMITS ROUTINE (D3/D5 ONLY)

-After the gate stops at the required pedestrian position (see step 6 on page 24) ie either at the automatic minimum or the manually over-ridden position, press the TEST button for a moment and release.

-L2 will illuminate when TEST button is released.

-Remove SET link and position as shown above, 74 , to exit programming unless proceeding to other menus.

NB. If automatic routine does not complete (indicated by STATUS flashing 5 times & L2 illuminating) then it may be necessary to set collision sensitivity to MED or LOW (see page 28)

START MANUAL GATE LIMITS ROUTINE

A5 ONLY (PAGE 26 & 27)

25

Image 27
Contents Sliding Gate Automation Page Major Components Typical D5 Shown Oil Specifications Grade 75W90 Qty 75mlStart kgF RUN kgF Gate Mass kg 300 500 ANTI-LIFT Brackets Duty Cycle Curves Recommended Installation and Cable Thickness REQUIREMENTS† Option 1 Bolt down onto concrete plinth Mechanical Mounting DetailsPage Option 2 Set into concrete plinth Provision for Cables Gearbox Mounting Down Details Useful TIP Mounting Rack200mm Installing Chain Drive Systems Ensure fan has stopped turning Setting Mechanical Clutch A5 onlyMounting of Gate Sensor Mounting Configuration For Steel RackRemovable Connectors Power Wiring see page 15 for Signal WiringSignal Wiring CP80 and CP81 Recommended Lightning Protection Commissioning Block Diagram Gate Closes Towards Left Above Black Blue RED Towards Right Setting Motor DirectionSelecting Programme Mode A5 only Setting Gate LimitsStart Automated Gate Limits Routine Setting Gate LimitsD3/D5 Motor Automatic SET-UP Start Manual Gate Limits Routine Exit Gate Limits Routine D3/D5 onlyA5 Motor Manual SET-UP Align Origin SwitchFunctions Select Exit Gate Limits Routine A5 onlyFactory Defaults Highlighted Timer and Counter Setting Main Unit Menu Measure Fault Finders Guide D3 / D5 Operators Procedure to Programme Controller Back to Factory SettingsGate Opens to Pedestrian and Closes Page Centurion