Centurion CP72SR5 installation manual Main Unit Menu Measure

Page 32

TABLE 3

 

MAIN

UNIT OF

 

 

MENU

MEASURE

 

 

 

 

 

 

 

Each flash

 

 

No of times of STATUS

 

 

L1 flashes

represents

 

 

 

 

 

 

 

FACTORY

 

 

 

DEFAULTS

NORMAL AUTOCLOSE

3

1 SEC

15 SEC

 

 

 

 

PEDESTRIAN AUTOCLOSE

5

1 SEC

5 SEC

 

 

 

 

COURTESY LIGHT

6

10 SEC

12x10 SEC

 

 

 

 

AUTOCLOSE OVERRIDE

8

1 SEC

3 SEC

 

 

 

 

PREFLASH TIME

11

1 SEC

5 SEC

 

 

 

 

COLLISION COUNTER

12

1 COUNT

4 COUNTS

 

 

 

 

CRAWL DISTANCE (D3/D5)

13

350 MM

1x350mm

COAST MODE (A5)

13

10 MM

30mm

THE CRAWL DISTANCE IS A LENGTH OF TRAVEL WHICH ALLOWS THE GATE TO SLOW DOWN BEFORE REACHING THE END STOP. FOR HEAVIER GATES WITH LESS FRICTION, THE CRAWL DISTANCE MAY HAVE TO BE INCREASED. WHEN INCREASING THE CRAWL DISTANCE, THE POSITION OF THE ORIGIN MARKER (ITEM 66 PAGE 15) MUST BE MOVED.

 

CRAWL

STATUS FLASH

DISTANCE BETWEEN

 

DISTANCE

COUNT

MARKER AND PINION

DEFAULT

350mm

1

500mm

 

 

 

 

700mm

2

750mm

1050mm

3

1100mm

TURBO MODE: TO SPEED UP THE COUNTING WHILE SELECTING MAIN MENU ITEMS TEMPORARILY CONNECT “PED” TERMINAL TO “COM”

30

Image 32
Contents Sliding Gate Automation Page Oil Specifications Grade 75W90 Qty 75ml Major Components Typical D5 ShownStart kgF RUN kgF Gate Mass kg 300 500 ANTI-LIFT Brackets Duty Cycle Curves Recommended Installation and Cable Thickness REQUIREMENTS† Mechanical Mounting Details Option 1 Bolt down onto concrete plinthPage Option 2 Set into concrete plinth Provision for Cables Gearbox Mounting Down Details Mounting Rack Useful TIP200mm Installing Chain Drive Systems Setting Mechanical Clutch A5 only Ensure fan has stopped turningMounting Configuration For Steel Rack Mounting of Gate SensorPower Wiring see page 15 for Signal Wiring Removable ConnectorsSignal Wiring CP80 and CP81 Recommended Lightning Protection Commissioning Block Diagram Setting Motor Direction Gate Closes Towards Left Above Black Blue RED Towards RightSelecting Programme Mode Setting Gate Limits A5 onlySetting Gate Limits Start Automated Gate Limits RoutineD3/D5 Motor Automatic SET-UP Exit Gate Limits Routine D3/D5 only Start Manual Gate Limits RoutineAlign Origin Switch A5 Motor Manual SET-UPExit Gate Limits Routine A5 only Functions SelectFactory Defaults Highlighted Timer and Counter Setting Main Unit Menu Measure Procedure to Programme Controller Back to Factory Settings Fault Finders Guide D3 / D5 OperatorsGate Opens to Pedestrian and Closes Page Centurion