Centurion CP72SR5 installation manual Timer and Counter Setting

Page 31

*The PREFLASHING MODES mentioned on page 28 are described below:

MODE 1 - COURTESY LIGHT PREFLASHES AT 1 HZ, THEN ACTS AS COURTESY LIGHT.

MODE 2 - COURTESY LIGHT FLASHES AT 1 HZ FOR PREFLASH TIME AND THEN FLASHES IN SYNCHRONISM WITH THE STATUS LED WHILE THE MOTOR RUNS.

MODE 3 - COURTESY LIGHT ON CONTINUOUSLY FOR PREFLASH TIME AND MOTOR RUN TIME ONLY.

TIMER and COUNTER SETTING

Various timers and counters can be programmed. The procedure is described below in conjunction with Table 3, page 30.

STEP 1 - Ensure controller is in Programme Mode (see page 21).

STEP 2 - Press and hold the TEST pushbutton while monitoring LED L1.

STEP 3 - L1 will flash once then go off, twice in short succession then go off, 3 times then go off, etc.

STEP 4 - Release TEST pushbutton when the desired MAIN MENU item in Table 3 is required.

STEP 5 - To select required time (or count) hold TEST pushbutton while monitoring STATUS LED. After a short time STATUS will flash continuously and regularly. Each flash represents a unit of measure (i.e. time, distance or count).

Release TEST pushbutton when the required subdivision is selected. L2 will come ON to indicate that the controller is back in PROGRAMME MODE and another TIMER or FUNCTION (refer to procedure on page 27) can be programmed.

STEP 6 - Remove SET link when all programming is complete.

29

Image 31
Contents Sliding Gate Automation Page Major Components Typical D5 Shown Oil Specifications Grade 75W90 Qty 75mlStart kgF RUN kgF Gate Mass kg 300 500 ANTI-LIFT Brackets Duty Cycle Curves Recommended Installation and Cable Thickness REQUIREMENTS† Option 1 Bolt down onto concrete plinth Mechanical Mounting DetailsPage Option 2 Set into concrete plinth Provision for Cables Gearbox Mounting Down Details Useful TIP Mounting Rack200mm Installing Chain Drive Systems Ensure fan has stopped turning Setting Mechanical Clutch A5 onlyMounting of Gate Sensor Mounting Configuration For Steel RackRemovable Connectors Power Wiring see page 15 for Signal WiringSignal Wiring CP80 and CP81 Recommended Lightning Protection Commissioning Block Diagram Gate Closes Towards Left Above Black Blue RED Towards Right Setting Motor DirectionSelecting Programme Mode A5 only Setting Gate LimitsStart Automated Gate Limits Routine Setting Gate LimitsD3/D5 Motor Automatic SET-UP Start Manual Gate Limits Routine Exit Gate Limits Routine D3/D5 onlyA5 Motor Manual SET-UP Align Origin SwitchFunctions Select Exit Gate Limits Routine A5 onlyFactory Defaults Highlighted Timer and Counter Setting Main Unit Menu Measure Fault Finders Guide D3 / D5 Operators Procedure to Programme Controller Back to Factory SettingsGate Opens to Pedestrian and Closes Page Centurion