Centurion CP72SR5 installation manual Recommended Installation and Cable Thickness REQUIREMENTS†

Page 7

2

3

4

7

11

5 6

9

8

10

RECOMMENDED INSTALLATION AND CABLE THICKNESS REQUIREMENTS

2

3

4

5 6

7

8

9 10 11

-LOCAL ISOLATOR

-MAINS SUPPLY (min 0.5mm² ‡, 2 CORE + EARTH)

-INTERCOM AND STATUS SIGNALING TO HOUSE (0.2mm², *n1 + 6 CORE)

-INTERCOM TO GATE STATION (0.2mm², #n2 CORES)

-PILLAR LIGHTS (0.5mm², 2 CORE + EARTH)

-RADIO RECEIVER (0.2mm², 3 CORE)

-PEDESTRIAN KEYSWITCH (0.2mm², 2 CORE)

-INFRA RED BEAM (0.2mm², 3 CORE)

-FREE EXIT LOOP (1.5mm², multi stranded cable)

-FREE EXIT CONTACT (0.2mm², 2 CORE)

For cable types to be used (e.g. SWA, Cabtyre, Intercom cable etc.) consult your municipal authority for details.

*n1 = NUMBER OF CORES REQUIRED BY INTERCOM

# n2 = NUMBER OF CORES REQUIRED BY INTERCOM

‡ sufficient for motor only, increase to suit total load if pillar lights are fitted

5

Image 7
Contents Sliding Gate Automation Page Major Components Typical D5 Shown Oil Specifications Grade 75W90 Qty 75mlStart kgF RUN kgF Gate Mass kg 300 500 ANTI-LIFT Brackets Duty Cycle Curves Recommended Installation and Cable Thickness REQUIREMENTS† Option 1 Bolt down onto concrete plinth Mechanical Mounting DetailsPage Option 2 Set into concrete plinth Provision for Cables Gearbox Mounting Down Details Useful TIP Mounting Rack200mm Installing Chain Drive Systems Ensure fan has stopped turning Setting Mechanical Clutch A5 onlyMounting of Gate Sensor Mounting Configuration For Steel RackRemovable Connectors Power Wiring see page 15 for Signal WiringSignal Wiring CP80 and CP81 Recommended Lightning Protection Commissioning Block Diagram Gate Closes Towards Left Above Black Blue RED Towards Right Setting Motor DirectionSelecting Programme Mode A5 only Setting Gate LimitsStart Automated Gate Limits Routine Setting Gate LimitsD3/D5 Motor Automatic SET-UP Start Manual Gate Limits Routine Exit Gate Limits Routine D3/D5 onlyA5 Motor Manual SET-UP Align Origin SwitchFunctions Select Exit Gate Limits Routine A5 onlyFactory Defaults Highlighted Timer and Counter Setting Main Unit Menu Measure Fault Finders Guide D3 / D5 Operators Procedure to Programme Controller Back to Factory SettingsGate Opens to Pedestrian and Closes Page Centurion