Heat Controller HTH, HTV, HTD Antifreeze Percentages by Volume, Open Loop Ground Water Systems

Page 13

Installation, Operation & Maintenance

HTV/HTD/HTH SERIES

Heat Controller, Inc.

Ground-Loop Heat Pump Applications

Table 2: Antifreeze Percentages by Volume

 

 

Minimum Temperature

 

Type

for Low Temperature Protection

 

 

 

 

 

10°F

15°F

20°F

 

25°F

 

 

 

[-12.2°C]

[-9.4°C]

[-6.7°C]

 

[-3.9°C]

 

 

 

 

 

 

Methanol

21%

17%

13%

 

8%

Propylene Glycol

29%

24%

18%

 

12%

Ethanol*

23%

20%

16%

 

11%

 

 

 

 

 

 

* Must not be denatured with any petroleum based product

GROUND-WATER HEAT PUMP APPLICATIONS

Open Loop - Ground Water Systems

Typical open loop piping is shown in Figure 13. Shut off valves should be included for ease of servicing. Boiler drains or other valves should be “tee’d” into the lines to allow acid flushing of the heat exchanger. Shut off valves should be positioned to allow flow through the coax via the boiler drains without allowing flow into the piping system. P/T plugs should be used so that pressure drop and temperature can be measured. Piping materials should be limited to copper or PVC SCH80. Note: Due to the pressure and temperature extremes, PVC SCH40 is not recommended.

Water quantity should be plentiful and of good quality. Consult table 3 for water quality guidelines. The unit can be ordered with either a copper or cupro-nickel water heat exchanger. Consult table 3 for recommendations. Copper is recommended for closed loop systems and open loop ground water systems that are not high in mineral content or corrosiveness. In conditions anticipating heavy scale formation or in brackish water, a cupro- nickel heat exchanger is recommended. In ground water situations where scaling could be heavy or where biological growth such

as iron bacteria will be present, an open loop system is not recommended. Heat exchanger coils may over time lose heat exchange capabilities due to build up of mineral deposits. Heat exchangers must only be serviced by a qualified technician, as acid and special pumping equipment is required. Desuperheater coils can likewise become scaled and possibly plugged. In areas with extremely hard water, the owner should be informed that the heat exchanger may require occasional acid flushing. In some cases, the desuperheater option should not be recommended due to hard water conditions and additional maintenance required.

Water Quality Standards

Table 3 should be consulted for water quality requirements. Scaling potential should be assessed using the pH/Calcium hardness method. If the pH <7.5 and the Calcium hardness is less than 100 ppm, scaling potential is low. If this method yields numbers out of range of those listed, the Ryznar Stability and Langelier Saturation indecies should be calculated. Use the appropriate scaling surface temperature for the application, 150°F [66°C] for direct use (well water/open loop) and DHW (desuperheater); 90°F [32°F] for indirect use. A monitoring plan should be implemented in these probable scaling situations. Other water quality issues such as iron fouling, corrosion prevention and erosion and clogging should be referenced in Table 3.

Pressure Tank and Pump

Use a closed, bladder-type pressure tank to minimize mineral formation due to air exposure. The pressure tank should be sized to provide at least one minute continuous run time of the pump using its drawdown capacity rating to prevent pump short cycling. Discharge water from the unit is not contaminated in any manner and can be disposed of in various ways, depending on local building codes (e.g. recharge well, storm sewer, drain field, adjacent stream or pond, etc.). Most local codes forbid the use of sanitary sewer for disposal. Consult your local building and zoning department to assure compliance in your area.

The pump should be sized to handle the home’s domestic water load (typically 5-9 gpm [23-41 l/m]) plus the flow rate required for the heat pump. Pump sizing and expansion tank must be chosen as complimentary items. For example, an expansion tank that is too small can causing premature pump failure due to short cycling. Variable speed pumping applications should be considered for the inherent energy savings and smaller pressure tank requirements.

Water Control Valve

Note the placement of the water control valve in figure 13. Always maintain water pressure in the heat exchanger by placing the water control valve(s) on the discharge line to prevent mineral precipitation during the off-cycle. Pilot operated slow closing valves are recommended to reduce water hammer. If water hammer persists, a mini-expansion tank can be mounted on the piping to help absorb the excess hammer shock. Insure that the total ‘VA’ draw of the valve can be supplied by the unit transformer. For instance, a slow closing valve can draw up to 35VA. This

can overload smaller 40 or 50 VA transformers depending on the other controls in the circuit. A typical pilot operated solenoid valve draws approximately 15VA (see Figure 22). Note the special wiring diagrams for slow closing valves (Figures 23 & 24).

Flow Regulation

Flow regulation can be accomplished by two methods. One method of flow regulation involves simply adjusting the ball valve or water control valve on the discharge line. Measure the pressure drop through the unit heat exchanger, and determine flow rate from tables 9a through 9c. Since the pressure is constantly varying, two pressure gauges may be needed. Adjust the valve until the desired flow of 1.5 to 2 gpm per ton [2.0 to 2.6 l/m per kW] is achieved.

A second method of flow control requires a flow control device

13

Image 13
Contents HTV/HTD/HTH Series Two-Stage Geothermal Heat Pumps To 6 Tons Table of Contents Safety General Information Hanger Bracket Horizontal Unit LocationTypical Horizontal Unit Installation Horizontal InstallationSide to Back Discharge Conversion Field Conversion of Air DischargeCondensate Piping Horizontal Units Duct System Installationರ3HU RRW Vertical Unit Location Vertical InstallationMay ease final drain line installation Using a threaded pipe or similar device to clearReturn Air InletPiping Installation Water Connection InstallationExternal Flow Controller Mounting Flushing the Earth LoopGround-Loop Heat Pump Applications Fluid Volume gal liters per 100’ 30 meters PipeAntifreeze Open Loop Ground Water Systems Antifreeze Percentages by VolumeWater Quality Standards Pressure Tank and PumpTypical Open Loop/Well Application Ground-Water Heat Pump ApplicationsWater Quality Standards Hot Water Generator Typical HWG InstallationHigh Water Temperature 160ºF InstallationControl Logic Error ÅashesInitial Start-Up Water Tank PreparationHWG Water Piping Water Tank RefillHT Series Electrical Data Electrical Line VoltagePower Connection General Line Voltage WiringHWG Wiring Split Units Only Electrical Line VoltageLow voltage Äeld wiring for units with ECM fan Electrical Low Voltage WiringLow Water Temperature Cutout Selection Thermostat ConnectionsTwo-stage Units Accessory ConnectionsThermostat Installation Electrical Thermostat WiringFault LED ATM21U01ECM Blower Control HT Units ECM Board Tap SettingsHT Series ECM Blower Performance Data CXM Controls Diagnostic Features Safety Features CXM ControlCXM Control Start-up Operation Unit Operation Stat signalECM fan PSC fan Thermostat Signals Nominal resistance at various temperaturesCXM Thermostat Details Not compatible with the CXMOperating Limits Unit Commissioning And Operating ConditionsCommissioning Conditions Voltage utilization range complies with Ahri StandardUnit Start-up Procedure Before Powering SYSTEM, please check the followingUnit Start-Up and Operating Conditions Unit and System CheckoutUnit Start-Up Procedure Unit Operating Conditions Water Temperature Change Through Heat ExchangerHT Coax Water Pressure Drop Antifreeze Correction TablePsig HT Series Typical Unit Operating Pressures and TemperaturesGPM Cooling EAT 80/67F Performance Data HT 024 Full LoadPerformance Data HT 036 Full Load Performance Data HT 048 Full Load Performance Data HT 060 Full Load Performance Data HT 070 Full Load Preventive Maintenance Troubleshooting CXM Process Flow Chart CXM Functional Troubleshooting Flow ChartMain power problems Functional TroubleshootingPerformance Troubleshooting Htg Clg Possible Cause Solution Performance Troubleshooting+&$ Troubleshooting Form97B00