Heat Controller HTV, HTH, HTD manual Functional Troubleshooting, Main power problems

Page 45

Installation, Operation & Maintenance

HTV/HTD/HTH SERIES

Heat Controller, Inc.

Functional Troubleshooting

Fault

Htg

Clg

Possible Cause

Solution

 

 

 

 

Check line voltage circuit breaker and disconnect.

Main power problems

X

X

Green Status LED Off

Check for line voltage between L1 and L2 on the contactor.

Check for 24VAC between R and C on CXM/DXM'

 

 

 

 

 

 

 

 

Check primary/secondary voltage on transformer.

 

 

X

Reduced or no water flow in cooling

Check pump operation or valve operation/setting.

 

 

Check water flow adjust to proper flow rate.

 

 

 

 

 

 

X

Water Temperature out of range in cooling

Bring water temp within design parameters.

HP Fault

 

 

 

Check for dirty air filter and clean or replace.

Code 2

X

 

Reduced or no air flow in heating

Check fan motor operation and airflow restrictions.

High Pressure

 

Dirty Air Coil- construction dust etc.

 

 

 

 

 

 

Too high of external static. Check static vs blower table.

 

X

 

Air temperature out of range in heating

Bring return air temp within design parameters.

 

X

X

Overcharged with refrigerant

Check superheat/subcooling vs typical operating condition table.

 

X

X

Bad HP Switch

Check switch continuity and operation. Replace.

LP/LOC Fault

X

X

Insufficient charge

Check for refrigerant leaks

Code 3

X

 

Compressor pump down at start-up

Check charge and start-up water flow.

Low Pressure / Loss of Charge

 

 

 

 

 

 

 

 

 

Check pump operation or water valve operation/setting.

LT1 Fault

X

 

Reduced or no water flow in heating

Plugged strainer or filter. Clean or replace..

 

 

 

Check water flow adjust to proper flow rate.

Code 4

 

 

 

 

X

 

Inadequate antifreeze level

Check antifreeze density with hydrometer.

 

 

Water coil low

X

 

Improper temperature limit setting (30°F vs

Clip JW3 jumper for antifreeze (10°F [-12°C]) use.

 

10°F [-1°C vs -2°C])

temperature limit

 

 

 

X

 

Water Temperature out of range

Bring water temp within design parameters.

 

 

 

X

X

Bad thermistor

Check temp and impedance correlation per chart

 

 

 

 

Check for dirty air filter and clean or replace.

LT2 Fault

 

X

Reduced or no air flow in cooling

Check fan motor operation and airflow restrictions.

Code 5

 

 

 

Too high of external static. Check static vs blower table.

Air coil low

 

X

Air Temperature out of range

Too much cold vent air? Bring entering air temp within design parameters.

 

X

Improper temperature limit setting (30°F vs

Normal airside applications will require 30°F [-1°C] only.

temperature limit

 

10°F [-1°C vs -12°C])

 

 

 

 

X

X

Bad thermistor

Check temp and impedance correlation per chart.

 

X

X

Blocked drain

Check for blockage and clean drain.

 

X

X

Improper trap

Check trap dimensions and location ahead of vent.

 

 

 

 

Check for piping slope away from unit.

Condensate Fault

 

X

Poor drainage

Check slope of unit toward outlet.

Code 6

 

 

 

Poor venting. Check vent location.

 

 

X

Moisture on sensor

Check for moisture shorting to air coil.

 

X

X

Plugged air filter

Replace air filter.

 

x

X

Restricted Return Air Flow

Find and eliminate restriction. Increase return duct and/or grille size.

 

 

 

 

Check power supply and 24VAC voltage before and during operation.

Over/Under

X

X

Under Voltage

Check power supply wire size.

Voltage Code 7

Check compressor starting. Need hard start kit?

 

 

 

(Auto resetting)

 

 

 

Check 24VAC and unit transformer tap for correct power supply voltage.

X

X

Over Voltage

Check power supply voltage and 24VAC before and during operation.

 

Check 24VAC and unit transformer tap for correct power supply voltage.

 

 

 

 

Unit Performance Sentinel

X

 

Heating mode FP2>125°F [52°C]

Check for poor air flow or overcharged unit.

 

 

Cooling Mode FP1>125°F [52°C] OR FP2<

 

Code 8

 

X

Check for poor water flow, or air flow.

 

40ºF [4ºC])

 

 

 

 

No Fault Code Shown

X

X

No compressor operation

See "Only Fan Operates".

X

X

Compressor overload

Check and replace if necessary.

 

X

X

Control board

Reset power and check operation.

 

X

X

Dirty air filter

Check and clean air filter.

Unit Short Cycles

X

X

Unit in "test mode"

Reset power or wait 20 minutes for auto exit.

X

X

Unit selection

Unit may be oversized for space. Check sizing for actual load of space.

 

 

X

X

Compressor overload

Check and replace if necessary

 

X

X

Thermostat position

Ensure thermostat set for heating or cooling operation.

 

X

X

Unit locked out

Check for lockout codes. Reset power.

Only Fan Runs

X

X

Compressor Overload

Check compressor overload. Replace if necessary.

 

X

X

Thermostat wiring

Check thermostat wiring at heat pump. Jumper Y and R for compressor operation

 

in test mode.

 

 

 

 

 

 

 

 

 

 

X

X

Thermostat wiring

Check G wiring at heat pump. Jumper G and R for fan operation

 

 

 

 

 

 

X

X

Fan motor relay

Jumper G and R for fan operation. Check for Line voltage across BR contacts.

Only Compressor Runs

 

 

 

X

X

 

Check fan power enable relay operation (if present).

 

X

X

Fan motor

Check for line voltage at motor. Check capacitor.

 

X

X

Thermostat wiring

Check thermostat wiring at heat pump. Jumper Y and R for compressor operation

 

in test mode

 

 

 

 

 

 

 

 

Set for cooling demand and check 24VAC on RV coil and at CXM/DXM board.

 

 

X

Reversing valve

If RV is stuck, run high pressure up by reducing water flow and while operating

 

 

 

 

engage and disengage RV coil voltage to push valve.

Unit Doesn’t Operate

 

X

Thermostat setup

Check for ‘O’ RV setup not ‘B’.

 

X

Thermostat wiring

Check O wiring at heat pump. Jumper O and R for RV coil ‘click’.

in Cooling

 

 

 

 

Put thermostat in cooling mode. Check 24 VAC on O (check between C and

 

 

 

 

 

 

X

Thermostat wiring

O); check for 24 VAC on W (check between W and C). There should be voltage

 

 

on O, but not on W. If voltage is present on W, thermostat may be bad or wired

 

 

 

 

 

 

 

 

incorrectly.

45

Image 45
Contents HTV/HTD/HTH Series Two-Stage Geothermal Heat Pumps To 6 Tons Table of Contents Safety General Information Hanger Bracket Horizontal Unit LocationTypical Horizontal Unit Installation Horizontal InstallationSide to Back Discharge Conversion Field Conversion of Air DischargeDuct System Installation Condensate Piping Horizontal Unitsರ3HU RRW Vertical Unit Location Vertical InstallationMay ease final drain line installation Using a threaded pipe or similar device to clearReturn Air InletPiping Installation Water Connection InstallationExternal Flow Controller Mounting Flushing the Earth LoopFluid Volume gal liters per 100’ 30 meters Pipe Ground-Loop Heat Pump ApplicationsAntifreeze Open Loop Ground Water Systems Antifreeze Percentages by VolumeWater Quality Standards Pressure Tank and PumpTypical Open Loop/Well Application Ground-Water Heat Pump ApplicationsWater Quality Standards Hot Water Generator Typical HWG InstallationHigh Water Temperature 160ºF InstallationControl Logic Error ÅashesInitial Start-Up Water Tank PreparationHWG Water Piping Water Tank RefillHT Series Electrical Data Electrical Line VoltagePower Connection General Line Voltage WiringHWG Wiring Split Units Only Electrical Line VoltageLow voltage Äeld wiring for units with ECM fan Electrical Low Voltage WiringLow Water Temperature Cutout Selection Thermostat ConnectionsTwo-stage Units Accessory ConnectionsThermostat Installation Electrical Thermostat WiringFault LED ATM21U01ECM Blower Control HT Units ECM Board Tap SettingsHT Series ECM Blower Performance Data CXM Controls Diagnostic Features Safety Features CXM ControlUnit Operation Stat signal CXM Control Start-up OperationECM fan PSC fan Thermostat Signals Nominal resistance at various temperaturesCXM Thermostat Details Not compatible with the CXMOperating Limits Unit Commissioning And Operating ConditionsCommissioning Conditions Voltage utilization range complies with Ahri StandardUnit Start-up Procedure Before Powering SYSTEM, please check the followingUnit Start-Up and Operating Conditions Unit and System CheckoutUnit Start-Up Procedure Unit Operating Conditions Water Temperature Change Through Heat ExchangerHT Coax Water Pressure Drop Antifreeze Correction TablePsig HT Series Typical Unit Operating Pressures and TemperaturesGPM Cooling EAT 80/67F Performance Data HT 024 Full LoadPerformance Data HT 036 Full Load Performance Data HT 048 Full Load Performance Data HT 060 Full Load Performance Data HT 070 Full Load Preventive Maintenance Troubleshooting CXM Process Flow Chart CXM Functional Troubleshooting Flow ChartMain power problems Functional TroubleshootingPerformance Troubleshooting Htg Clg Possible Cause Solution Performance Troubleshooting+&$ Troubleshooting Form97B00