Installation, Operation & Maintenance | HTV/HTD/HTH SERIES | Heat Controller, Inc. |
Performance Troubleshooting
Performance Troubleshooting | Htg | Clg | Possible Cause | Solution | |
| X | X | Dirty filter | Replace or clean. | |
|
|
|
| Check for dirty air filter and clean or replace. | |
| X |
|
|
| |
|
| Reduced or no air flow in heating | Check fan motor operation and airflow restrictions. | ||
|
|
|
| Too high of external static. Check static vs. blower table. | |
|
|
|
|
| |
|
|
|
| Check for dirty air filter and clean or replace. | |
|
| X |
|
| |
|
| Reduced or no air flow in cooling | Check fan motor operation and airflow restrictions. | ||
|
|
|
| Too high of external static. Check static vs. blower table. | |
Insufficient capacity/ Not |
|
|
|
| |
X | X | Leaky duct work | Check supply and return air temperatures at the unit and at distant duct registers | ||
cooling or heating | if significantly different, duct leaks are present. | ||||
|
|
| |||
| X | X | Low refrigerant charge | Check superheat and subcooling per chart. | |
| X | X | Restricted metering device | Check superheat and subcooling per chart. Replace. | |
|
| X | Defective reversing valve | Perform RV touch test. | |
| X | X | Thermostat improperly located | Check location and for air drafts behind stat. | |
| X | X | Unit undersized | Recheck loads & sizing. Check sensible clg. load and heat pump capacity. | |
| X | X | Scaling in water heat exchanger | Perform scaling check and clean if necessary. | |
| X | X | Inlet water too hot or too cold | Check load, loop sizing, loop backfill, ground moisture. | |
|
|
|
| Check for dirty air filter and clean or replace. | |
| X |
| Reduced or no air flow in heating |
| |
|
| Check fan motor operation and air flow restrictions. | |||
|
|
|
| Too high of external static. Check static vs. blower table. | |
|
|
|
|
| |
|
| X | Reduced or no water flow in cooling | Check pump operation or valve operation/setting. | |
|
|
| |||
|
| Check water flow. Adjust to proper flow rate. | |||
|
|
|
| ||
High Head Pressure |
|
|
|
| |
| X | Inlet water too hot | Check load, loop sizing, loop backfill, ground moisture. | ||
| X |
| Air temperature out of range in heating | Bring return air temperature within design parameters. | |
|
| X | Scaling in water heat exchanger | Perform scaling check and clean if necessary. | |
| X | X | Unit overcharged | Check superheat and subcooling. | |
| X | X | Vacuum system and | ||
| X | X | Restricted metering device. | Check superheat and subcooling per chart. Replace. | |
|
|
|
| Check pump operation or water valve operation/setting. | |
| X |
| Reduced water flow in heating. |
| |
|
| Plugged strainer or filter. Clean or replace. | |||
|
|
|
| Check water flow. Adjust to proper flow rate. | |
|
|
|
|
| |
| X |
| Water temperature out of range. | Bring water temperature within design parameters. | |
Low Suction Pressure |
|
|
| Check for dirty air filter and clean or replace. | |
|
| X | Reduced air flow in cooling. | Check fan motor operation and air flow restrictions. | |
|
|
|
| Too high of external static. Check static vs. blower table. | |
|
|
|
|
| |
|
| X | Air temperature out of range | Too much cold vent air? Bring entering air temperature within design parameters. | |
| X | X | Insufficient charge | Check for refrigerant leaks. | |
Low Discharge Air Temperature | X |
| Too high of air flow | Check fan motor speed selection and air flow chart. | |
in Heating | X |
| Poor performance | See ‘Insufficient Capacity’ | |
High humidity |
| X | Too high of air flow | Check fan motor speed selection and airflow chart. | |
| X | Unit oversized | Recheck loads & sizing. Check sensible clg load and heat pump capacity. | ||
|
|
46