Heat Controller HTD Condensate Piping Horizontal Units, Duct System Installation, ರ3HU RRW

Page 8

Installation, Operation & Maintenance

HTV/HTD/HTH SERIES

Heat Controller, Inc.

Horizontal Installation

Condensate Piping – Horizontal Units

Pitch the unit toward the drain as shown in Figure 2 to improve the condensate drainage. On small units (less than 2.5 tons/8.8 kW), insure that unit pitch does not cause condensate leaks inside the cabinet.

Install condensate trap at each unit with the top of the trap positioned below the unit condensate drain connection as shown in Figure 6. Design the depth of the trap (water-seal) based upon the amount of ESP capability of the blower (where 2 inches [51mm] of ESP capability requires 2 inches [51mm] of trap depth). As a general rule, 1-1/2 inch [38mm] trap depth is the minimum.

Each unit must be installed with its own individual trap and connection to the condensate line (main) or riser. Provide a means to flush or blow out the condensate line. DO NOT install units with a common trap and/or vent.

Always vent the condensate line when dirt or air can collect in the line or a long horizontal drain line is required. Also vent when large units are working against higher external static pressure than other units connected to the same condensate main since this may cause poor drainage for all units on the line. WHEN A VENT IS INSTALLED IN THE DRAIN LINE, IT MUST BE LOCATED AFTER THE TRAP IN THE DIRECTION OF THE CONDENSATE FLOW.

Condensate Piping

Figure 6: Horizontal Condensate Connection

ರ

ರ3HU )RRW

ರ

ರ

*Some units include a painted drain connection. Using a threaded pipe or similar device to clear any excess paint accumulated inside this fitting may ease final drain line installation.

CAUTION!

CAUTION! Ensure condensate line is pitched toward drain 1/8 inch per ft [11mm per m] of run.

DUCT SYSTEM INSTALLATION

Duct System Installation

The duct system should be sized to handle the design airflow quietly. Refer to Figure 3 for horizontal duct system details or figure 8 for vertical duct system details. A flexible connector is recommended for both discharge and return air duct connections on metal duct systems to eliminate the transfer of vibration to the duct system. To maximize sound attenuation of the unit blower, the supply and return plenums should include internal fiberglass duct liner or be constructed from ductboard for the first few feet. Application of the unit to uninsulated ductwork

in an unconditioned space is not recommended, as the unit’s performance will be adversely affected.

At least one 90° elbow should be included in the supply duct to reduce air noise. If air noise or excessive air flow is a problem, the blower speed can be changed. For airflow charts, consult specifications catalog for the series and model of the specific unit.

If the unit is connected to existing ductwork, a previous check should have been made to insure that the ductwork has the capacity to handle the airflow required for the unit. If ducting is too small, as in the replacement of a heating only system, larger ductwork should be installed. All existing ductwork should be checked for leaks and repaired as necessary.

8

Image 8
Contents HTV/HTD/HTH Series Two-Stage Geothermal Heat Pumps To 6 Tons Table of Contents Safety General Information Horizontal Unit Location Hanger BracketHorizontal Installation Typical Horizontal Unit InstallationField Conversion of Air Discharge Side to Back Discharge Conversionರ3HU RRW Duct System InstallationCondensate Piping Horizontal Units Vertical Installation Vertical Unit LocationUsing a threaded pipe or similar device to clear May ease final drain line installationReturn Air InletWater Connection Installation Piping InstallationExternal Flow Controller Mounting Flushing the Earth LoopAntifreeze Fluid Volume gal liters per 100’ 30 meters PipeGround-Loop Heat Pump Applications Antifreeze Percentages by Volume Open Loop Ground Water SystemsWater Quality Standards Pressure Tank and PumpGround-Water Heat Pump Applications Typical Open Loop/Well ApplicationWater Quality Standards Typical HWG Installation Hot Water GeneratorInstallation High Water Temperature 160ºFControl Logic Error ÅashesWater Tank Preparation Initial Start-UpHWG Water Piping Water Tank RefillElectrical Line Voltage HT Series Electrical DataGeneral Line Voltage Wiring Power ConnectionHWG Wiring Split Units Only Electrical Line VoltageElectrical Low Voltage Wiring Low voltage Äeld wiring for units with ECM fanLow Water Temperature Cutout Selection Thermostat ConnectionsAccessory Connections Two-stage UnitsElectrical Thermostat Wiring Thermostat InstallationFault LED ATM21U01ECM Blower Control ECM Board Tap Settings HT UnitsHT Series ECM Blower Performance Data CXM Controls Safety Features CXM Control Diagnostic FeaturesECM fan PSC fan Unit Operation Stat signalCXM Control Start-up Operation Nominal resistance at various temperatures Thermostat SignalsCXM Thermostat Details Not compatible with the CXMUnit Commissioning And Operating Conditions Operating LimitsCommissioning Conditions Voltage utilization range complies with Ahri StandardBefore Powering SYSTEM, please check the following Unit Start-up ProcedureUnit Start-Up and Operating Conditions Unit and System CheckoutUnit Start-Up Procedure Water Temperature Change Through Heat Exchanger Unit Operating ConditionsHT Coax Water Pressure Drop Antifreeze Correction TableHT Series Typical Unit Operating Pressures and Temperatures PsigGPM Performance Data HT 024 Full Load Cooling EAT 80/67FPerformance Data HT 036 Full Load Performance Data HT 048 Full Load Performance Data HT 060 Full Load Performance Data HT 070 Full Load Preventive Maintenance Troubleshooting CXM Functional Troubleshooting Flow Chart CXM Process Flow ChartFunctional Troubleshooting Main power problemsPerformance Troubleshooting Performance Troubleshooting Htg Clg Possible Cause SolutionTroubleshooting Form +&$97B00