Heat Controller HTV, HTH, HTD Nominal resistance at various temperatures, CXM Thermostat Details

Page 30

Installation, Operation & Maintenance

HTV/HTD/HTH SERIES

Heat Controller, Inc.

CXM Controls

Table 7: Nominal resistance at various temperatures

Temp (ºC)

Temp (ºF)

Resistance

Temp (ºC)

Temp (ºF)

Resistance

(kOhm)

(kOhm)

 

 

 

 

-17.8

0.0

85.34

55

131.0

2.99

-17.5

0.5

84.00

56

132.8

2.88

-16.9

1.5

81.38

57

134.6

2.77

-12

10.4

61.70

58

136.4

2.67

-11

12.2

58.40

59

138.2

2.58

-10

14.0

55.30

60

140.0

2.49

-9

15.8

52.38

61

141.8

2.40

-8

17.6

49.64

62

143.6

2.32

-7

19.4

47.05

63

145.4

2.23

-6

21.2

44.61

64

147.2

2.16

-5

23.0

42.32

65

149.0

2.08

-4

24.8

40.15

66

150.8

2.01

-3

26.6

38.11

67

152.6

1.94

-2

28.4

36.18

68

154.4

1.88

-1

30.2

34.37

69

156.2

1.81

0

32.0

32.65

70

158.0

1.75

1

33.8

31.03

71

159.8

1.69

2

35.6

29.50

72

161.6

1.64

3

37.4

28.05

73

163.4

1.58

4

39.2

26.69

74

165.2

1.53

5

41.0

25.39

75

167.0

1.48

6

42.8

24.17

76

168.8

1.43

7

44.6

23.02

77

170.6

1.39

8

46.4

21.92

78

172.4

1.34

9

48.2

20.88

79

174.2

1.30

10

50.0

19.90

80

176.0

1.26

11

51.8

18.97

81

177.8

1.22

12

53.6

18.09

82

179.6

1.18

13

55.4

17.26

83

181.4

1.14

14

57.2

16.46

84

183.2

1.10

15

59.0

15.71

85

185.0

1.07

16

60.8

15.00

86

186.8

1.04

17

62.6

14.32

87

188.6

1.01

18

64.4

13.68

88

190.4

0.97

19

66.2

13.07

89

192.2

0.94

20

68.0

12.49

90

194.0

0.92

21

69.8

11.94

91

195.8

0.89

22

71.6

11.42

92

197.6

0.86

23

73.4

10.92

93

199.4

0.84

24

75.2

10.45

94

201.2

0.81

25

77.0

10.00

95

203.0

0.79

26

78.8

9.57

96

204.8

0.76

27

80.6

9.16

97

206.6

0.74

28

82.4

8.78

98

208.4

0.72

29

84.2

8.41

99

210.2

0.70

30

86.0

8.06

100

212.0

0.68

31

87.8

7.72

101

213.8

0.66

32

89.6

7.40

102

215.6

0.64

33

91.4

7.10

103

217.4

0.62

34

93.2

6.81

104

219.2

0.60

35

95.0

6.53

105

221.0

0.59

36

96.8

6.27

106

222.8

0.57

37

98.6

6.01

107

224.6

0.55

38

100.4

5.77

108

226.4

0.54

39

102.2

5.54

109

228.2

0.52

40

104.0

5.33

110

230.0

0.51

41

105.8

5.12

111

231.8

0.50

42

107.6

4.92

112

233.6

0.48

43

109.4

4.72

113

235.4

0.47

44

111.2

4.54

114

237.2

0.46

45

113.0

4.37

115

239.0

0.44

46

114.8

4.20

116

240.8

0.43

47

116.6

4.04

117

242.6

0.42

48

118.4

3.89

118

244.4

0.41

49

120.2

3.74

119

246.2

0.40

50

122.0

3.60

120

248.0

0.39

51

123.8

3.47

121

249.8

0.38

52

125.6

3.34

122

251.6

0.37

53

127.4

3.22

123

253.4

0.36

54

129.2

3.10

 

 

 

CXM Thermostat Details

Thermostat Compatibility - Most all heat pump thermostats can be used with the CXM control. However Heat/Cool stats are

NOT compatible with the CXM.

Anticipation Leakage Current - Maximum leakage current for "Y" is 50 mA and for "W" is 20mA. Triacs can be used if leakage current is less than above. Thermostats with anticipators can be used if anticipation current is less than that specified above.

Thermostat Signals -

"Y" and "W" have a 1 second recognition time when being activated or being removed.

"O" and "G" are direct pass through signals but are monitored by the micro processor.

"R" and "C" are from the transformer.

"AL1" and "AL2" originate from the alarm relay.

"A" is paralleled with the compressor output for use with well water solenoid valves.

The "Y" 1/4" quick connect is a connection point to the "Y" input terminal P1 for factory use. This "Y" terminal can be used to drive panel mounted relays such as the loop pump relay.

30

Image 30
Contents HTV/HTD/HTH Series Two-Stage Geothermal Heat Pumps To 6 Tons Table of Contents Safety General Information Horizontal Unit Location Hanger BracketHorizontal Installation Typical Horizontal Unit InstallationField Conversion of Air Discharge Side to Back Discharge ConversionDuct System Installation Condensate Piping Horizontal Unitsರ3HU RRW Vertical Installation Vertical Unit LocationReturn Using a threaded pipe or similar device to clearMay ease final drain line installation Air InletExternal Flow Controller Mounting Water Connection InstallationPiping Installation Flushing the Earth LoopFluid Volume gal liters per 100’ 30 meters Pipe Ground-Loop Heat Pump ApplicationsAntifreeze Water Quality Standards Antifreeze Percentages by VolumeOpen Loop Ground Water Systems Pressure Tank and PumpGround-Water Heat Pump Applications Typical Open Loop/Well ApplicationWater Quality Standards Typical HWG Installation Hot Water GeneratorControl Logic Error InstallationHigh Water Temperature 160ºF ÅashesHWG Water Piping Water Tank PreparationInitial Start-Up Water Tank RefillElectrical Line Voltage HT Series Electrical DataHWG Wiring Split Units Only General Line Voltage WiringPower Connection Electrical Line VoltageLow Water Temperature Cutout Selection Electrical Low Voltage WiringLow voltage Äeld wiring for units with ECM fan Thermostat ConnectionsAccessory Connections Two-stage UnitsFault LED Electrical Thermostat WiringThermostat Installation ATM21U01ECM Blower Control ECM Board Tap Settings HT UnitsHT Series ECM Blower Performance Data CXM Controls Safety Features CXM Control Diagnostic FeaturesUnit Operation Stat signal CXM Control Start-up OperationECM fan PSC fan CXM Thermostat Details Nominal resistance at various temperaturesThermostat Signals Not compatible with the CXMCommissioning Conditions Unit Commissioning And Operating ConditionsOperating Limits Voltage utilization range complies with Ahri StandardUnit Start-Up and Operating Conditions Before Powering SYSTEM, please check the followingUnit Start-up Procedure Unit and System CheckoutUnit Start-Up Procedure HT Coax Water Pressure Drop Water Temperature Change Through Heat ExchangerUnit Operating Conditions Antifreeze Correction TableHT Series Typical Unit Operating Pressures and Temperatures PsigGPM Performance Data HT 024 Full Load Cooling EAT 80/67FPerformance Data HT 036 Full Load Performance Data HT 048 Full Load Performance Data HT 060 Full Load Performance Data HT 070 Full Load Preventive Maintenance Troubleshooting CXM Functional Troubleshooting Flow Chart CXM Process Flow ChartFunctional Troubleshooting Main power problemsPerformance Troubleshooting Performance Troubleshooting Htg Clg Possible Cause SolutionTroubleshooting Form +&$97B00