Heat Controller HTV, HTH, HTD manual Water Quality Standards

Page 15

Installation, Operation & Maintenance

HTV/HTD/HTH SERIES

Heat Controller, Inc.

Water Quality Standards

Table 3: Water Quality Standards

Water Quality Parameter

HX

Material

Closed

Recirculating

Open Loop and Recirculating Well

Scaling Potential - Primary Measurement

Above the given limits, scaling is likely to occur. Scaling indexes should be calculated using the limits below

pH/Calcium Hardness Method

All

-

pH < 7.5 and Ca Hardness <100ppm

Index Limits for Probable Scaling Situations - (Operation outside these limits is not recommended)

Scaling indexes should be calculated at 66°C for direct use and HWG applications, and at 32°C for indirect HX use. A monitoring plan should be implemented.

Ryznar Stability Index

Langelier Saturation Index

All

All

-

-

6.0 - 7.5

If >7.5 minimize steel pipe use.

-0.5 to +0.5

If <-0.5 minimize steel pipe use. Based upon 66°C HWG and Direct well, 29°C Indirect Well HX

Iron Fouling

Iron Fe 2+ (Ferrous) (Bacterial Iron potential)

Iron Fouling

All

All

-

-

<0.2 ppm (Ferrous)

If Fe2+ (ferrous)>0.2 ppm with pH 6 - 8, O2<5 ppm check for iron bacteria.

<0.5 ppm of Oxygen

Above this level deposition will occur .

Corrosion Prevention

pH

Hydrogen Sulfide (H2S)

Ammonia ion as hydroxide, chloride, nitrate and sulfate compounds

Maximum

Chloride Levels

All

All

All

Copper

Cupronickel

304SS

316SS

Titanium

6 - 8.5

Monitor/treat as

needed

-

-

-

-

-

-

-

6 - 8.5

Minimize steel pipe below 7 and no open tanks with pH <8

<0.5 ppm

At H2S>0.2 ppm, avoid use of copper and copper nickel piping or HX's. Rotten egg smell appears at 0.5 ppm level.

Copper alloy (bronze or brass) cast components are OK to <0.5 ppm.

<0.5 ppm

Maximum Allowable at maximum water temperature.

10C

24C

38 C

<20ppm

NR

NR

<150 ppm

NR

NR

<400 ppm

<250 ppm

<150 ppm

<1000 ppm

<550 ppm

< 375 ppm

>1000 ppm

>550 ppm

>375 ppm

Erosion and Clogging

Particulate Size and

Erosion

All

<10 ppm of particles and a maximum velocity of 1.8 m/s Filtered for maximum 841 micron [0.84 mm, 20 mesh] size.

<10 ppm (<1 ppm "sandfree” for reinjection) of particles and a maximum velocity of 1.8 m/s. Filtered for maximum 841 micron 0.84 mm,

20 mesh] size. Any particulate that is not removed can potentially clog components.

The ClimateMastManufacturerr Water Quality Table provides water quality requirements for ClimateMasterManufacturer coaxial heat exchangers. When water properties are outside of those requirements, an external secondary heat exchanger must be used to isolate the heat pump heat exchanger from the unsuitable water. Failure to do so will void the warranty for the coaxial heat exchanger.

Notes:

‡&ORVHG5HFLUFXODWLQJV\VWHPLVLGHQWLILHGE\Dclosed pressurized piping system.

‡5HFLUFXODWLQJRSHQZHOOVVKRXOGREVHUYHWKHRSHQUHFLUFXODWLQJGHVLJQFRQVLGHUDWLRQV

‡15Application not recommended.

‡1RGHVLJQ0D[LPXP

Rev.: 3/22/2012

15

Image 15
Contents HTV/HTD/HTH Series Two-Stage Geothermal Heat Pumps To 6 Tons Table of Contents Safety General Information Hanger Bracket Horizontal Unit LocationTypical Horizontal Unit Installation Horizontal InstallationSide to Back Discharge Conversion Field Conversion of Air DischargeDuct System Installation Condensate Piping Horizontal Unitsರ3HU RRW Vertical Unit Location Vertical InstallationAir Inlet Using a threaded pipe or similar device to clearMay ease final drain line installation ReturnFlushing the Earth Loop Water Connection InstallationPiping Installation External Flow Controller MountingFluid Volume gal liters per 100’ 30 meters Pipe Ground-Loop Heat Pump ApplicationsAntifreeze Pressure Tank and Pump Antifreeze Percentages by VolumeOpen Loop Ground Water Systems Water Quality StandardsTypical Open Loop/Well Application Ground-Water Heat Pump ApplicationsWater Quality Standards Hot Water Generator Typical HWG InstallationÅashes InstallationHigh Water Temperature 160ºF Control Logic ErrorWater Tank Refill Water Tank PreparationInitial Start-Up HWG Water PipingHT Series Electrical Data Electrical Line VoltageElectrical Line Voltage General Line Voltage WiringPower Connection HWG Wiring Split Units OnlyThermostat Connections Electrical Low Voltage WiringLow voltage Äeld wiring for units with ECM fan Low Water Temperature Cutout SelectionTwo-stage Units Accessory ConnectionsATM21U01 Electrical Thermostat WiringThermostat Installation Fault LEDECM Blower Control HT Units ECM Board Tap SettingsHT Series ECM Blower Performance Data CXM Controls Diagnostic Features Safety Features CXM ControlUnit Operation Stat signal CXM Control Start-up OperationECM fan PSC fan Not compatible with the CXM Nominal resistance at various temperaturesThermostat Signals CXM Thermostat DetailsVoltage utilization range complies with Ahri Standard Unit Commissioning And Operating ConditionsOperating Limits Commissioning ConditionsUnit and System Checkout Before Powering SYSTEM, please check the followingUnit Start-up Procedure Unit Start-Up and Operating ConditionsUnit Start-Up Procedure Antifreeze Correction Table Water Temperature Change Through Heat ExchangerUnit Operating Conditions HT Coax Water Pressure DropPsig HT Series Typical Unit Operating Pressures and TemperaturesGPM Cooling EAT 80/67F Performance Data HT 024 Full LoadPerformance Data HT 036 Full Load Performance Data HT 048 Full Load Performance Data HT 060 Full Load Performance Data HT 070 Full Load Preventive Maintenance Troubleshooting CXM Process Flow Chart CXM Functional Troubleshooting Flow ChartMain power problems Functional TroubleshootingPerformance Troubleshooting Htg Clg Possible Cause Solution Performance Troubleshooting+&$ Troubleshooting Form97B00