Installation, Operation & Maintenance | HTV/HTD/HTH SERIES | Heat Controller, Inc. |
Electrical - Line Voltage
WARNING!
WARNING! To avoid possible injury or death due to electrical shock, open the power supply disconnect switch and secure it in an open position during installation.
CAUTION!
CAUTION! Use only copper conductors for field installed electrical wiring. Unit terminals are not designed to accept other types of conductors.
Table 4a: HT Series Electrical Data
|
| All HTT Units with Emerson ECM Fan Motor |
| HTT Units (ECM) Standard | HTT Units (ECM) with ClimaDry | ||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| Compressor |
| HWG | Ext | Fan | Total | Min |
| Max | ClimaDry | Total | Min | Max/ | ||
|
|
|
| Loop |
| Fuse/ | Fuse | ||||||||||
| Model |
|
|
|
|
| Pump | Motor | Unit | Circuit |
| Pump | Unit | Circuit | |||
|
|
|
|
|
| Pump |
| HACR | HACR | ||||||||
|
|
| RLA | LRA |
| Qty | FLA | FLA | FLA | Amps |
| FLA | FLA | Amps | |||
|
|
|
| FLA |
| (2) | (2) | ||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
| 6 |
| 11.7 | 58.3 |
| 1 | 0.5 | 1.7 | 3.9 | 16.1 | 19.0 |
| 30 | 0.8 | 16.9 | 19.8 | 30 |
| 024 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| 0386 |
| 15.3 | 83.0 |
| 1 | 0.5 | 1.7 | 3.9 | 19.7 | 23.5 |
| 35 | 0.8 | 20.5 | 24.3 | 35 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| 0498 |
| 21.2 | 104.0 |
| 1 | 0.5 | 1.7 | 6.9 | 28.6 | 33.9 |
| 50 | 1.1 | 29.7 | 35.0 | 50 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| 0640 |
| 27.1 | 152.9 |
| 1 | 0.5 | 1.7 | 6.9 | 34.5 | 41.2 |
| 60 | 1.1 | 35.6 | 42.3 | 60 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| 0720 |
| 29.7 | 179.2 |
| 1 | 0.5 | 1.7 | 6.9 | 37.1 | 44.5 |
| 70 | 1.1 | 38.2 | 45.6 | 70 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||
|
|
|
|
|
|
|
|
|
| ||||||||
Rated Voltage of |
|
|
|
| Min/Max Voltage of 197/254 |
|
| ||||||||||
HACR circuit breaker in USA only |
|
|
|
| All fuses Class |
|
|
|