Installation, Operation & Maintenance | HTV/HTD/HTH SERIES | Heat Controller, Inc. |
Electrical - Thermostat Wiring
ѥCAUTION! ѥ
CAUTION! Many units are installed with a factory or ¿eld supplied manual or electric
Figure 24: Units With Optional ECM Fan.
Connection to ECM Control
ATP32U04 | Thermostat | ECM |
|
| Board |
|
|
operation. A high pressure switch must be installed on the heat pump side of any ¿eld provided
ѥCAUTION! ѥ
Compressor Compressor Stage 2 Auxiliary Heat Dehumidification Reversing Valve Fan 24Vac Hot
24Vac Common Fault LED
Y1
Y2
W
DH
O
G
R
C
L
Y1
Y2
W
DH
O
G
R
C
AL1
CAUTION! Refrigerant pressure activated water regulating valves should never be used with ClimateMasterManufacturer equipment.
Thermostat Installation
The thermostat should be located on an interior wall in a larger room, away from supply duct drafts. DO NOT locate the thermostat in areas subject to sunlight, drafts or on external walls. The wire access hole behind the thermostat may in certain cases need to be sealed to prevent erroneous temperature measurement. Position the thermostat back plate against the wall so that it appears level and so the thermostat wires protrude through the middle of the back plate. Mark the position of the back plate mounting holes and drill holes with a 3/16” (5mm) bit. Install supplied anchors and secure plate to the wall. Thermostat wire must be 18 AWG wire. Wire the appropriate thermostat as shown in Figures 24 and 25 to the low voltage terminal strip on the CXM (units with PSC motor) or ECM control board (units with ECM motor). Practically any heat pump thermostat will work with these units, provided it has the correct number of heating and cooling stages.
NOTICE: Units with ClimaDry whole house dehumidiÄcation option require a separate humidistat or thermostat part number ATP32U04 (See ClimaDry AOM for more details).
UnitsUnitswithwithCXMCXMororDXMDXMboardboardandandECMECMfanfanmotor,motor,utilizingutilizingECMECMdehumididehum dificationfication mode
mode (without ClimaDry option) Notes:
1)Notes:ECM dehumidification mode slows down fan speed in the cooling mode when 1) Units with whole house dehumidification option have slightly different
dehumidification output from thermostat is active. Normal heating and cooling fan thermostat wiring.Terminal DH at the thermostat is connected to terminal H at speeds are not affected.
the DXM board
2)2)ECMECMboarddehumidificationDIP switch SW9modemustslowsbedownin dehumidfan speed. modein fortheECMcoolingdehumidimode fiwhencation mode.
dehumidification output from thermostat is active. Normal heating and cooling fan speeds are not affected.
3)ECM board DIP switch SW9 must be in dehumid. mode for ECM dehumidification mode.
Figure 25: Typical Thermostat 2 Heat/1 Cool (PSC Fan)
Connection to CXM Control
ATM21U01 | Thermostat | CXM | ||
|
|
|
|
|
Compressor | Y |
| Y | |
| ||||
|
|
|
|
|
Heating Stage 2 | Y2/W |
| W | |
| ||||
|
|
|
|
|
Reversing Valve | O |
| O | |
| ||||
| Fan | G |
| G |
| ||||
24Vac Hot | R |
| R | |
| ||||
24Vac Common | C |
| C | |
| ||||
Fault LED | L |
| AL1 | |
|
23