Heat Controller HTH, HTV, HTD manual Hot Water Generator, Typical HWG Installation

Page 16

Installation, Operation & Maintenance

HTV/HTD/HTH SERIES

Heat Controller, Inc.

Hot Water Generator

The HWG (Hot Water Generator) or desuperheater option provides considerable operating cost savings by utilizing excess heat energy from the heat pump to help satisfy domestic hot water requirements. The HWG is active throughout the year, providing virtually free hot water when the heat pump operates in the cooling mode or hot water at the COP of the heat pump during operation in the heating mode. Actual HWG water heating capacities are provided in the appropriate heat pump performance data.

Heat pumps equipped with the HWG option include a built-in water to refrigerant heat exchanger that eliminates the need to tie into the heat pump refrigerant circuit in the field. The control circuit and pump are also built in for residential equipment. Figure 14 shows a typical example of HWG water piping connections on a unit with built-in circulating pump. This piping layout reduces scaling potential.

The temperature set point of the HWG is field selectable to 125°F or 150°F . The 150°F set point allows more heat storage from the HWG. For example, consider the amount of heat that can be generated by the HWG when using the 125°F set point, versus the amount of heat that can be generated by the HWG when using the 150°F set point.

In a typical 50 gallon two-element electric water heater the lower element should be turned down to 100°F, or the lowest setting, to get the most from the HWG. The tank will eventually stratify so that the lower 80% of the tank, or 40 gallons, becomes 100°F (controlled by the lower element). The upper 20% of the tank, or 10 gallons, will be maintained at 125°F (controlled by the upper element).

Using a 125°F set point, the HWG can heat the lower 40 gallons of water from 100°F to 125°F, providing up to 8,330 btu’s of heat. Using the 150°F set point, the HWG can heat the same 40 gallons of water from 100°F to 150°F and the remaining 10 gallons of water from 125°F to 150°F, providing a total of up to 18,743 btu’s of heat, or more than twice as much heat as when using the 125°F set point.

This example ignored standby losses of the tank. When those losses are considered the additional savings are even greater.

Electric water heaters are recommended. If a gas, propane, or oil water heater is used, a second preheat tank must be installed (Figure 15). If the electric water heater has only a single center element, the dual tank system is recommended to insure a usable entering water temperature for the HWG.

Typically a single tank of at least 52 gallons (235 liters) is used to limit installation costs and space. However, a dual tank, as shown in Figure 15, is the most efficient system, providing the maximum storage and temperate source water to the HWG.

It is always advisable to use water softening equipment on domestic water systems to reduce the scaling potential and lengthen equipment life. In extreme water conditions, it may be necessary to avoid the use of the HWG option since the potential cost of frequent maintenance may offset or exceed any savings. Consult Table 3 for scaling potential tests.

Figure 14: Typical HWG Installation

 

Hot Outlet

Cold

 

Inlet

 

to home

 

 

 

Shut Off

 

 

 

Valve #1

 

 

 

Shut Off

 

 

 

Valve #4

 

 

 

Upper

 

 

 

element to

 

 

 

120 - 130°F

 

 

 

[49 - 54°C]

 

 

 

Lower

 

Powered

element to

 

Water

 

100 - 110°F

Shut-off

Heater

[38 - 43°C]

 

 

 

Valve #3

Shut Off

Valve #2

Field supplied 3/4’ brass nipple and ‘T’

Insulated water lines -

5/8” OD, 50 ft maximum (one way) [16mm OD, 15 meters maximum]

Figure 15: HWG Double Tank Installation

Hot Outlet to

house

Cold Inlet from

Domestic supply

Hot Outlet

Cold Inlet

WARNING!

WARNING! A 150°F SETPOINT MAY LEAD TO SCALDING OR BURNS. THE 150°F SET POINT MUST ONLY BE USED ON SYSTEMS THAT EMPLOY AN APPROVED ANTI-SCALD VALVE.

 

Shut-off

Upper element to 130°F [54°C]

 

Valve #1

(or owner preference)

 

 

 

Shut-off

 

 

Valve #4

 

 

Powered

 

 

Water Heater

Lower element to 120°F [49°C]

 

Unpowered

 

Shut-off

Water Heater

 

 

 

Valve #3

 

 

Shut Off

 

 

Valve #2

 

 

 

Field Supplied 3/4” brass nipple and “T”

Insulated water lines - 5/8” OD, 50 ft maximum (one way)

 

[16mm OD, 15 meters maximum]

 

16

Image 16
Contents HTV/HTD/HTH Series Two-Stage Geothermal Heat Pumps To 6 Tons Table of Contents Safety General Information Horizontal Unit Location Hanger BracketHorizontal Installation Typical Horizontal Unit InstallationField Conversion of Air Discharge Side to Back Discharge ConversionCondensate Piping Horizontal Units Duct System Installationರ3HU RRW Vertical Installation Vertical Unit LocationUsing a threaded pipe or similar device to clear May ease final drain line installationReturn Air InletWater Connection Installation Piping InstallationExternal Flow Controller Mounting Flushing the Earth LoopGround-Loop Heat Pump Applications Fluid Volume gal liters per 100’ 30 meters PipeAntifreeze Antifreeze Percentages by Volume Open Loop Ground Water SystemsWater Quality Standards Pressure Tank and PumpGround-Water Heat Pump Applications Typical Open Loop/Well ApplicationWater Quality Standards Typical HWG Installation Hot Water GeneratorInstallation High Water Temperature 160ºFControl Logic Error ÅashesWater Tank Preparation Initial Start-UpHWG Water Piping Water Tank RefillElectrical Line Voltage HT Series Electrical DataGeneral Line Voltage Wiring Power ConnectionHWG Wiring Split Units Only Electrical Line VoltageElectrical Low Voltage Wiring Low voltage Äeld wiring for units with ECM fanLow Water Temperature Cutout Selection Thermostat ConnectionsAccessory Connections Two-stage UnitsElectrical Thermostat Wiring Thermostat InstallationFault LED ATM21U01ECM Blower Control ECM Board Tap Settings HT UnitsHT Series ECM Blower Performance Data CXM Controls Safety Features CXM Control Diagnostic FeaturesCXM Control Start-up Operation Unit Operation Stat signalECM fan PSC fan Nominal resistance at various temperatures Thermostat SignalsCXM Thermostat Details Not compatible with the CXMUnit Commissioning And Operating Conditions Operating LimitsCommissioning Conditions Voltage utilization range complies with Ahri StandardBefore Powering SYSTEM, please check the following Unit Start-up ProcedureUnit Start-Up and Operating Conditions Unit and System CheckoutUnit Start-Up Procedure Water Temperature Change Through Heat Exchanger Unit Operating ConditionsHT Coax Water Pressure Drop Antifreeze Correction TableHT Series Typical Unit Operating Pressures and Temperatures PsigGPM Performance Data HT 024 Full Load Cooling EAT 80/67FPerformance Data HT 036 Full Load Performance Data HT 048 Full Load Performance Data HT 060 Full Load Performance Data HT 070 Full Load Preventive Maintenance Troubleshooting CXM Functional Troubleshooting Flow Chart CXM Process Flow ChartFunctional Troubleshooting Main power problemsPerformance Troubleshooting Performance Troubleshooting Htg Clg Possible Cause SolutionTroubleshooting Form +&$97B00