Configuration
Set Configuration DIP Switches
Using a small tool, set the Configuration DIP Switches (located on the front panel of your unit, see diagram) to optimize Inverter/Charger operation depending on your application. Warning: Make sure the unit is turned OFF before changing DIP Switch settings.
BATTERY
HIGH
MED
CONFIGURATION DIP SWITCHES LOW
(SEE MANUAL OR TOP OF UNIT FOR INSTRUCTIONS)
OPERATION
LINE
REMOTE INV CONTROL LOAD
1 2 3 | 4 | 5 | 6 7 8 | 9 10 11 12 |
1Not Used
2Select Line Connect Relay Transfer Time - OPTIONAL
Faster
Transfer Time | Switch Position |
|
| |
1/2 Cycle Transfer Time | Up |
|
| |
1 2 3 4 Slower | ||||
1 Cycle Transfer Time | Down (factory setting) | |||
|
|
Note: If you will use the Inverter/Charger to support computers or other sensitive electronic equipment loads, set the transfer time to ½ cycle (switch #2 UP) to ensure uninterrupted operation when the Inverter/Charger transfers to battery power.
3Select Frequency - REQUIRED
Frequency | Switch Position |
60 Hz | Up |
50 Hz | Down (factory setting) |
|
|
|
| 60 Hz | |
|
|
|
| ||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
1 | 2 | 3 | 4 | 50 Hz | |
|
| ||||
|
|
|
|
|
|
4Select Line Voltage - REQUIRED
Voltage | Switch Position |
208 VAC | Up |
230 VAC | Down (factory setting) |
|
| 208 V | ||
|
| |||
|
|
|
|
|
|
|
|
|
|
1 2 3 4 |
|
|
| |
230 V | ||||
|
|
|
|
|
5Select Battery Charger Amp Setting
CAUTION: When switching to the High Charge Amp setting, the user must ensure that the amp hour capacity of their battery system exceeds the amperage of the High Charge Amp setting or the batteries may be damaged or degraded.
Low Charge Amp
1
5 6 7 8 High Charge Amp
Battery Charger | Switch Position |
|
Low Charge Amps (23A) | Up (factory setting) | |
|
|
|
High Charge Amps (90A) | Down |
6Select Equalize Battery Charge - OPTIONAL
This DIP Switch is momentarily engaged to begin the process of equalizing the charge state of your battery’s cells by
“Reset”
5 6 7 8 “Equalize”
Setting Procedure
•Move to “Equalize” (DOWN) postition for three seconds.
•Move to “Reset” (UP) postition and leave it there. This is the factory default setting.
CAUTION: Do not leave DIP switch #3 in the down position after beginning process. Battery charge equalization should only be performed in strict accordance with the battery manufacturer’s instructions and specifications.
Battery Charge | Switch Position |
Reset | Up (factory setting) |
Equalize | Down (momentarily) |
7 |
| 8 |
| 9 | Not Used |