Aurora Electronics PVI-3600-OUTD-UK-F-W Display menù, Address Information, Manual address setting

Page 51

Installation and Operator’s Manual

Page 51 of 63

(PVI-3600-OUTD-UK-F-W Rev.: 1.0)

 

 

 

6.3Display menù

When using PLM or the RS-485 serial link communication each unit must have a unique address. The default address of each unit is 2. When connecting multiple units on the same serial or PLM link a new address needs to be assigned to each unit to avoid communication errors.

6.4Address Information

Addresses 0 is reserved for the host computers; addresses 1 is reserved for the automatic addressing mode.

The RS-485 serial link uses addresses 2 thru 33. The PLM link uses addresses 2 thru 63.

6.5Manual address setting

Use the following procedure to set the new address:

1)Press the key on the side of the LCD display button for at least 5 seconds.

2)AURORA disconnects from the grid, the yellow LED begins to blink and the display shows:

NEW ADDRESS

#####

3)The first address is 2. Press the key as many times as needed to select the address between 2 and 63. After the number 63 there is the AUTO address. Continuing with the Key press, the address starts back from 2. In order to scroll the address number press the key for a short while (less than 5 sec.).

WARNING: The user must NOT select the address AUTO. The automatic setting of addresses through this key is a feature used on multiple wind turbine installations by factory authorized personnel using

special software.

Image 51
Contents AURORA Revision Table Important Safety InstructionsImportant Safety Instructions Useful Information and Safety Standard Foreword AssemblyGeneral Save ALL Documents in a Safe Place Maintenance and ServiceElectrical Connection OperationPVI-3600-OUTD-UK-F-W Contents Page Wind Energy Main Elements of a Wind System Simplified diagram of a Wind system Aurora Technical Description Data Transmission and CheckInverter Ground Fault Protective Devices Anti-IslandingFurther Protective Devices System Design Package Inspection Package Check List Description Quantity No Minimum clearance requirements Choosing Installation LocationWall Mounting Wall mounting diagramPage Inverter tilted mounting Preliminaries to Electrical Connections General wiring diagram Position of the holes on the bottom side Removing the side panel Page Location of Main Ground PE Screw Aurora Connect Aurora to the Dc disconnect switchesPV Input Close the side panel START-UP User’s Interface Mode Data Transmission Options Available Data Real time dataInternally Logged Data LED Indicators KEYLED on LED blinking LED off Any of the above conditions Installation phase Aurora is disconnected from grid Ground Insulation Sleep ModeAurora Initialization and Grid Check Aurora Under ProductionMalfunction-Fault Signal RS-485 Address Setting SignalMessages and Error Codes Error Description LCD Display Second screen Serial Number and Firmware release number Pac ## W Vin Timegrid hhmmss Numgrid ## Error Grid fail Data RS-485 serial link Multiple units connection Data transmission to a PC Power Line Modem PLMData transmission to Aurora Easy Control Manual address setting Display menùAddress Information Verifying the paralleled input configuration Automatic settingSET in Mode Parallel Data Description Unit Measurement AccuracyData Resolution Accuracy Display Measurement Troubleshooting Info Aurora Input Values PVI-3600-OUTD-UK-F-W ValueOutput Values Description Grid protection characteristicsGeneral characteristics Description Value Power Derating Power Derating due to Ambient TemperaturePower Derating due to Input Voltage