8.5Power Derating

To ensure inverter safe operation under any temperature and electrical condition, the unit will automatically derate the power to be delivered to the grid.

Power derating can occur on one of the two following occasions:

Power Derating due to Ambient Temperature

Under certain operating conditions, AURORA automatically regulates the power to ensure that the components are always run well-within their operating temperature limits. Several environmental factors can influence the operating temperature of the unit, such as ambient air temperature, airflow, exposure to sun radiation, input voltage and power, orientation of the heatsink fins, etc.

AURORA supplies the max output power for ambient temperatures ≤ 40°C, provided it is not exposed to sun radiation or other direct heat sources which may affect the internal thermal behavior.

Power Derating due to Input Voltage

The graph shows the automatic derating of delivered power when input voltage values are too high or too low.

Output Power – two Dc sections operating

Power [W]

Non Operating Range

 

Voltage Derating Range

Power Derating (max input current)

Non Operating Range

90

200

Input

530 580 600

 

 

voltage [V]

 

 

 

 

 

Image 62
Contents AURORA Important Safety Instructions Revision TableImportant Safety Instructions General Useful Information and Safety Standard ForewordAssembly Operation Maintenance and ServiceElectrical Connection Save ALL Documents in a Safe PlacePVI-3600-OUTD-UK-F-W Contents Page Wind Energy Main Elements of a Wind System Simplified diagram of a Wind system Data Transmission and Check Aurora Technical DescriptionInverter Further Protective Devices Ground FaultProtective Devices Anti-Islanding System Design Package Inspection Package Check List Description Quantity No Choosing Installation Location Minimum clearance requirementsWall mounting diagram Wall MountingPage Inverter tilted mounting Preliminaries to Electrical Connections General wiring diagram Position of the holes on the bottom side Removing the side panel Page Location of Main Ground PE Screw Connect Aurora to the Dc disconnect switches AuroraPV Input Close the side panel START-UP User’s Interface Mode Data Transmission Options Internally Logged Data Available DataReal time data LED on LED blinking LED off Any of the above conditions LED IndicatorsKEY Installation phase Aurora is disconnected from grid Aurora Under Production Sleep ModeAurora Initialization and Grid Check Ground InsulationMessages and Error Codes Malfunction-Fault SignalRS-485 Address Setting Signal Error Description LCD Display Second screen Serial Number and Firmware release number Pac ## W Vin Timegrid hhmmss Numgrid ## Error Grid fail Data RS-485 serial link Multiple units connection Power Line Modem PLM Data transmission to a PCData transmission to Aurora Easy Control Address Information Manual address settingDisplay menù Automatic setting Verifying the paralleled input configurationSET in Mode Parallel Measurement Accuracy Data Description UnitData Resolution Accuracy Display Measurement Troubleshooting Info Aurora Input Values Value PVI-3600-OUTD-UK-F-WGrid protection characteristics Output Values DescriptionGeneral characteristics Description Value Power Derating due to Input Voltage Power DeratingPower Derating due to Ambient Temperature