Installation and Operator’s Manual | Page 29 of 63 |
(PVI-3600-OUTD-UK-F-W Rev.: 1.0) | |
| |
PV INPUT 2 | -IN2 +IN2 +IN2 |
| -IN2 |
PV INPUT 1 | -IN1 +IN1 +IN1 |
| -IN1 |
Fig.14: Wind Input with the two input sections paralleled
NOTE: Paralleling the two input sections, the input current rating becomes equivalent to 20A (24A short circuit).
In the parallel mode configuration the maximum input power limit is equivalent to the max output power plus losses. It can be rated to 3800W.
WARNING: Take special care to ensure the Wind MPPT voltage polarity corresponds to the symbols “+” and “-” labeled on the contacts of the Wind Interface Box.
Before connecting AURORA with the Wind Interface Box, Magnetek recommends checking, using a proper gauge, that the polarity value and the allowable voltage value between positive and negative contacts are correct.
Wind MPPT connection: Follow this procedure for connecting the Wind Interface to the Aurora Wind Inverter.
1)Install the suitable wire method between AURORA Wind inverter and Wind Interface Box.