PV INPUT 2

-IN2 +IN2 +IN2

 

-IN2

PV INPUT 1

-IN1 +IN1 +IN1

 

-IN1

+

-

Fig.14: Wind Input with the two input sections paralleled

NOTE: Paralleling the two input sections, the input current rating becomes equivalent to 20A (24A short circuit).

In the parallel mode configuration the maximum input power limit is equivalent to the max output power plus losses. It can be rated to 3800W.

WARNING: Take special care to ensure the Wind MPPT voltage polarity corresponds to the symbols “+” and “-” labeled on the contacts of the Wind Interface Box.

Before connecting AURORA with the Wind Interface Box, Magnetek recommends checking, using a proper gauge, that the polarity value and the allowable voltage value between positive and negative contacts are correct.

Wind MPPT connection: Follow this procedure for connecting the Wind Interface to the Aurora Wind Inverter.

1)Install the suitable wire method between AURORA Wind inverter and Wind Interface Box.

Image 29
Contents AURORA Revision Table Important Safety InstructionsImportant Safety Instructions General Useful Information and Safety Standard ForewordAssembly Electrical Connection Maintenance and ServiceOperation Save ALL Documents in a Safe PlacePVI-3600-OUTD-UK-F-W Contents Page Wind Energy Main Elements of a Wind System Simplified diagram of a Wind system Aurora Technical Description Data Transmission and CheckInverter Further Protective Devices Ground FaultProtective Devices Anti-Islanding System Design Package Inspection Package Check List Description Quantity No Minimum clearance requirements Choosing Installation LocationWall Mounting Wall mounting diagramPage Inverter tilted mounting Preliminaries to Electrical Connections General wiring diagram Position of the holes on the bottom side Removing the side panel Page Location of Main Ground PE Screw Aurora Connect Aurora to the Dc disconnect switchesPV Input Close the side panel START-UP User’s Interface Mode Data Transmission Options Internally Logged Data Available DataReal time data LED on LED blinking LED off Any of the above conditions LED IndicatorsKEY Installation phase Aurora is disconnected from grid Aurora Initialization and Grid Check Sleep ModeAurora Under Production Ground InsulationMessages and Error Codes Malfunction-Fault SignalRS-485 Address Setting Signal Error Description LCD Display Second screen Serial Number and Firmware release number Pac ## W Vin Timegrid hhmmss Numgrid ## Error Grid fail Data RS-485 serial link Multiple units connection Data transmission to a PC Power Line Modem PLMData transmission to Aurora Easy Control Address Information Manual address settingDisplay menù Verifying the paralleled input configuration Automatic settingSET in Mode Parallel Data Description Unit Measurement AccuracyData Resolution Accuracy Display Measurement Troubleshooting Info Aurora Input Values PVI-3600-OUTD-UK-F-W ValueOutput Values Description Grid protection characteristicsGeneral characteristics Description Value Power Derating due to Input Voltage Power DeratingPower Derating due to Ambient Temperature