The specifications of the earth leakage breaker :
zRated Sensitive Current: 30mA (or below) (Grounding resistance: 500Ω or below)
zSensitive time: Within 0.1second
The qualified electrician should perform the grounding work of the following 3 points (500Ω or below).
zThe earth grounding terminal in the output terminals
zThe Outer Bonnet (Canopy) of the generator
zThe Outer Bonnet of the load
<Caution>
zIn the event you cannot ground the generator to the earth, consult with the authorized dis- tributor or our engineering section.
DGW311DM
DGW311L
EARTH GROUNDING TERMINAL | EARTH GROUNDING TERMINAL |
|
BONNET GROUNDING | BONNET GROUNDING | |
TERMINAL | ||
TERMINAL | ||
| ||
GROUNDING ROD | GROUNDING ROD |
Before operating the generator, check always if the device can work. RESET BUTTON EARTH LEAKAGE
INDICATION LAMP
①Turn the starter switch from STOP to Run.
②Turn
③ Push the test button. (When the button is pushed, the earth leakage indication lamp turns ON and the circuit breaker is po- sitioned in the middle of ON and OFF positions, the device can
work normal.)
④Push the reset button. (The earth leakage indication lamp (red) turns OFF subsequently.)
⑤Turn (push down) the circuit breaker (lever) to OFF position.
⑥ Restore the switch to STOP. <Caution>
z In the event you cannot complete every step of the above procedure to the end, the device is out of order. Consult with our authorized distributor or our engineering section to repair.
10