Miller Electric TS, IH manual If display flashes no.io again, or if, Before 10 degree window is

Page 57

 

 

Trouble

 

 

Remedy

 

 

 

If display flashes no.io again, or if

Remove 2408 control from its housing by pressing locking tabs outward slightly on sides of control and pulling

0-10 V output card fails.

 

 

control forward. Look for add−on PC card in back of controller, and remove PC card. Reinstall 2408 control

 

 

 

 

 

 

 

into housing being careful not to damage locking tabs on housing. Disable output card function as follows:

 

 

 

 

 

 

 

Goto ConF, IA ConF (Module 1 Config). See Section 8-5-4.

 

 

 

 

 

 

 

 

Change id dc.OP to id nonE.

 

 

 

 

 

 

 

 

Scroll to Exit no and change it to Exit YES, and the controller will reset automatically.

 

 

 

 

 

 

 

 

Set power source panel / remote switch to panel position and set desired maximum output. The control will

 

 

 

 

 

 

 

operate in an on / off mode (at target temp + over temp alarm value).

 

 

 

 

 

 

 

 

The over temp alarm value is set in Goto Ful, AL LiSt, IdHi.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Obtain a replacement 0-10 V isolated card.

 

 

 

 

Output stops when green Run

Replace Hold button.

 

button is released.

 

 

 

 

 

 

 

 

 

 

 

Temperature

readings

go

down

Check for reversed red (−) and yellow (+) leads in 2-pin thermocouple, and correct if necessary.

 

instead of up.

 

 

 

 

 

 

 

 

 

Temperature readings do not rise.

Check for a short between thermocouple wires.

 

 

 

 

Temperatue does not change in

Change the ramp rate for that segment in the Program List.

 

ramp segment.

 

 

 

 

 

 

 

 

 

 

Fault/Limit light is on.

 

 

Parameter Display will indicate either “Coolant Flow Error” or “PS Limit”.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

“Coolant Flow Error” − ensure that cooler is plugged in and turned on.

 

 

 

 

 

 

 

 

For 25 kW system, ensure receptacle switch is on.

 

 

 

 

 

 

 

 

Check coolant level in reservoir, and add coolant if necessary.

 

 

 

 

 

 

 

 

Check filter on cooler and replace, if necessary.

 

 

 

 

 

 

 

 

Verify that coolant “IN” and “OUT” hoses are connected to the correct fittings.

 

 

 

 

 

 

 

 

Check alignment of center pins in plastic quick disconnect fittings.

 

 

 

 

 

 

 

 

Be sure that coolant jumpers are connected properly.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

“PS Limit” indicates the power source will run at less than full output.

 

 

 

 

 

 

 

 

Verify panel/remote switch on power source is in Remote position.

 

 

 

 

 

 

 

 

Turn down dial on front panel of power source until light goes out or

 

 

 

 

 

 

 

 

To obtain full output, adjust the coil to get more coupling into the part.

 

 

 

 

 

 

 

 

Check set-up parameters.

 

 

 

 

 

 

 

 

If Volts setting is greater than 650, add a turn to the heating coil.

 

 

 

 

 

 

Current Source fault.

 

 

Remove a turn from the heating coil.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Power/Volts equals Real Current, Real Current must be kept under 60 A.

 

 

 

 

 

 

 

2408

Controller

displays

dwell

Check that Hold Back setting is in Band, display will read Hb bAnd (see Section 8-5-3, Goto Ful,

ProG

before 10 degree window is

LiSt).

 

reached.

 

 

 

 

 

 

 

 

 

 

 

 

Check that Hold Back Units equals 10 F, display will read Hb U 10 (see Section 8-5-3, Goto Ful,

ProG

 

 

 

 

 

 

 

 

 

 

 

 

 

 

LiSt).

 

 

 

 

 

 

 

 

Parameter

 

display

does

not

See Section 8-3A.

 

operate, but

2408 Temperature

 

 

Controller

and 5100V

Recorder

 

 

displays do operate.

 

 

 

 

 

 

 

 

 

2408

Temperature

Controller

See Section 8-3B.

 

display does not operate, but 5100V

 

 

Recorder display does operate.

 

 

 

 

 

5100V Recorder does not turn on,

See Section 8-3C.

 

but 2408

Temperature Controller

 

 

does turn on.

 

 

 

 

 

 

 

 

 

Flow/Limit light does not illuminate

See Section 8-3D.

 

when cooler is turned off.

 

 

 

 

 

 

Heat On light does not display when

See Section 8-3E.

 

power source is supplying output.

 

 

 

 

 

Output does not start when Run

See Section 8-3F.

 

button is pressed.

 

 

 

 

 

 

 

 

 

 

Pressing

Power

Source Select

See Section 8-3G.

 

button on rear of IH/TS does not

 

 

change selection.

 

 

 

 

 

 

 

 

5100V Recorder displays Channel

See Section 8-3H.

 

Error.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

OM-203 185 Page 53

Image 57
Contents Processes OM-203 185FDescription File Induction HeatingFrom Miller to You Table of Contents Resetting All RAM Variables In The Event Of Display Errors Symbol Usage − Safety Precautions − Read Before UsingInduction Heating Hazards Electric Shock can killCalifornia Proposition 65 Warnings Principal Safety StandardsAbout Pacemakers EMF Information− Mesures DE Securite Pour LE Chauffage PAR Induction LE Chauffage PAR Induction peut être dangereuxLE Chauffage PAR Induction peut provoquer un incendie Porteurs de stimulateur cardiaque, restez à distance DES Organes Mobiles peuvent provoquer des blessuresEn ce qui concerne les stimulateurs cardiaques − Introduction Specifications − InstallationIH/TS Installation Specification DescriptionInput 14 Pin Information For Receptacle RC1 Connecting To Power SourceConnecting 25kW System Cords And Cables FrontRear FrontRear Connecting 5kW System Cords And CablesCooler Such as grinders, drills, lights, etcConnecting External Device IH/TS Front Panel − Components and ControlsIH/TS Rear Panel Controller 200.0Safety Equipment − Setup and OperationIH/TS Setup Select Power Source Parameter Display2-2 Login As Engineer Time Date Setup − DigitalLocale Setup 2-1 Digital Recorder ControlsLogin As User Time And Date SetupGo To Home Screen Channel Cycling On/Off And NotesController Display Definitions OperationRun List Sub-Menu Definitions NameController Operation Program List Terms And Definitions Programming The 2408 ControllerSegment Type Definitions Setpoint remains constant for a specified periodExample Pre−heat Profile Step to 600 F Example Stress Relief ProfileRamp rate Deg/ hrRamp to 800 F @ 400 /hr Ramp to 1250 F Example Multi−Step Stress Relief ProfileRamp to 800 F Ramp to 600 F Deg/hrSets output to Profile Set-Up WorksheetBatch Recording Using 5100 Digital Recorder Begin Batch recording -3-3-1. Login As UserStart Recording Saving Data To a Disk Recommended After Each Batch Stop RecordingNetwork Connection Windows 95, 98, ME Changing IP Address To Connect The IH/TS For WindowsDownloading Files From Recorder For Windows 95, 98, ME Troubleshooting Connection ProblemsRunning a Program To Preheat Or Stress Relief OP1 SP2 Recovering From An InterruptionReview software first time setup screen Installing Review Software And First Time SetupViewing Data In Review Software Backing Up The DatabaseRunning Review Software Start Review softwareSelect Transfer Files Select Files Select OK Single File With Batch NameSelect Start Transfer Single File With No Batch NameMultiple Files With No Batch Names Multiple Files With Batch NamesSelect Add Point Select File Select New ChartScrn14 Select OK to view chart These steps must be done Scrn20 Select OK Comment becomes part of the chart Select Save Select File Select Print to print entire profile on one File name becomes Part of the chartScrn30 Typical Profile Chart Printout − Configuring Controller and Recorder Select Channel Number For each Channel NumberLoad File Date SetupTime Setup Login As UserGo To Home Screen Routine Maintenance − Maintenance & TroubleshootingTroubleshooting MonthsGoto ConF, IA ConF Module 1 Config. See Section If display flashes no.io again, or ifBefore 10 degree window is Is complete, turn Ihts power off and back on again When touched, but does notSee Section Advance to next screenDiagnostic Procedures For IH/TS OM-203 185 5100V Recorder Displays Channel Error Resetting All RAM Variables In The Event Of Display Errors Controller Version Number Factory Set ParametersPress Page to Press Scroll Version NumberController Edit Parameters Navigation Across Scroll Down Home List Controller Full Parameters Prior To VersionVaries Output ListConfigure Parameters Prior To Version ControllerNavigation Across OM-203 Navigation Across Scroll Down Home List Controller Full Parameters Effective w/VersionConfigure Parameters Effective w/Version Type-K Mini Connector Calibration Certification ProcedureFluke-714 Thermocouple CalibratorCircuit Diagram For IH/TS − Electrical DiagramsComplete Assembly − Parts List198 Page Page Service Your distributor also givesSupport Miller Electric Mfg. Co To locate a Distributor or Service Agency visitFor assistance in filing or settling claims, contact Your distributor and/or equipment manufacturer’s