Raypak 0135B, 0030B, 0090B manual Servicing Procedures, General Location of Controls

Page 23

4. SERVICING PROCEDURES

GENERAL LOCATION OF CONTROLS

CIRCULATOR

CONTROL BOX COMPONENT LOCATIONS MODELS 135 & 180

2-Stage Controller

Relay

Fast-

Response Ignition Module

Temperature (Auto Ignition Only)

Sensor

Fig.# 8195.1

VENT SENSOR

BYPASS VALVE

(MODELS 135 & 180 ONLY)

BYPASS LINE

TEMPERATURE

AND PRESSURE GAUGE

2-STAGED CONTROLLER

(MODEL 90 ONLY)

PRESSURE

RELIEF VALVE

RELAY

ADJUSTABLE

HIGH LIMIT

FIELD WIRING

COMPARTMENT

FAST RESPONSE TEMPERATURE SENSOR

IGNITION MODULE

(AUTO IGNITION ONLY)

TRANSFORMER

ROLL-OUT SENSOR

GAS VALVE

Fig.# 8195.4

SEQUENCE OF OPERATION INTERMITTENT IGNITION DEVICE (IID)

Boilers equipped with the IID system will automatically light the pilot burner first and then the main burner, each time there is a call for heat from the room thermostat. Whenever the room thermostat is calling for heat, the circulator supplied with the boiler, will be energized and should be running. The ignition control module will also be energized to initiate the pilot ignition by opening the first main valve (pilot). At the same time, the electronic spark generator in the module produces a high-voltage spark pulse output that lights the pilot burner. If the pilot burner does not light, the module will not energize the second main valve and the burners will not light. Ignition spark continues only until the timed trial for ignition period ends. Then, the module goes into safety shutdown or lockout. Lockout de-energizes the first main valve operator and closes the first main (pilot) valve in the gas control, stopping pilot gas flow. The ignition control system must be reset by setting the thermostat below room temperature for one minute or by turning off power to the module for one minute. When the pilot flame is established, flame rectification circuit is completed between the sensor and burner ground. The flame sensing circuit in the module detects the flame current, shuts off the spark generator and energizes the second main valve operator which opens the second main valve. This allows gas to flow to the burners where it is ignited by the pilot burner flame. When the thermostat is satisfied, the valve operators are de-energized shutting off the pilot and main burners, and also the circulator.

23

Image 23
Contents For Your Safety Installation Operating InstructionsContents Receiving Equipment General SpecificationsSpecifications and Dimensions Clearancerequirements Installation ProceduresCode Requirements Mounting BaseFig. #8198.0 Venting ConnectionsFig.# Common VentsLocation Vent Damper InstallationMounting Installing the Vent Damper in Horizontal & Vertical VentD80D General Wiring Diagram Flair Damper Vent Damper Position IndicatorSystem Schematic Ladder Diagram Vent Damper OperationConnection Diagram Water Connections & System Piping GAS Supply ConnectionsGaspressure SINGLE-ZONEPIPING Piping DiagramsZone Heating with Indirect Domestic HOT Water Supply Multiple Zones with Zone Valves Fig.# Electrical WiringWiring Diagram KEY Page Page Wiring Diagram Single-Zone Taco Valve Wiring Diagram System with 3 Zone Pumps Fig. #2223.2e Wiring Diagram Standing Pilot With Low Water Cut-off Device Sequence of Operation Intermittent Ignition Device IID Servicing ProceduresGeneral Location of Controls Control BOX Component Locations Models 135What to do if YOU Smell GAS START-UPPROCEDURESFor Automatic Ignition Models Honeywell Pilot Robertshaw PilotTo Turn OFF GAS to Boiler SHUT-DOWNPROCEDUREFor Automatic Ignition Systems Flame Failure Inspection Procedures BurnersInspectionprocedures Safe SHUT-DOWN Tests Limit ActionRepairprocedures Raypak Tube Cleaning KITCombustion Chamber Removal Heat Exchanger RE-ASSEMBLYImportant Notice Troubleshooting GuidePiping ADJUSTMENT/REPLACEMENTOF Components RAYPAK, INC Replacement Parts ListPage Page Page Limited Parts Warranty