Raypak 0135B, 0030B, 0090B manual Mounting, Installing the Vent Damper in Horizontal & Vertical Vent

Page 8

MOUNTING

On vertical vents, the vent damper may be mounted with the actuator in any position. On horizontal vents, do not mount the actuator either directly above or directly below the vent pipe; mount the vent damper actuator to the side of the vent.

The vent damper is set up for a continuous pilot system. If the vent damper is installed on a system with an Intermittent Pilot or Hot Surface Ignition the energy savings of the vent damper can be improved by plugging the hole in the vent damper blade using the knockout plug, Part No. 105612R, provided in the parts envelope.

Hole in Vent Damper Blade

Closed Position

Fig. #8994

DO NOT plug the hole if installing the vent damper on a continuous pilot system as this will create a hazardous condition.

Fig. #8183.0

INSTALLING THE VENT DAMPER IN HORIZONTAL & VERTICAL VENT.

1K

 

 

 

 

 

 

1K1

 

D80

 

 

 

MOTOR

 

 

N.C.

 

 

 

END

 

 

1K2

SWITCH N.O.

C.

 

 

 

 

1K3

 

 

4

3

2

1

YELLOW

BLUE

BLACK

ORANGE

CABLE

Fig. #152323

D80D GENERAL WIRING DIAGRAM

INSTALL THE VENT DAMPER TO SERVICE ONLY THE SINGLE APPLIANCE FOR WHICH IT IS INTENDED. IF IMPROPERLY INSTALLED, A HAZARDOUS CONDITION, SUCH AS AN EXPLOSION OR CARBON MONOXIDE POISONING, COULD RESULT.

8

Image 8
Contents Installation Operating Instructions For Your SafetyContents Receiving Equipment General SpecificationsSpecifications and Dimensions Installation Procedures Code RequirementsMounting Base ClearancerequirementsVenting Connections Fig. #8198.0Common Vents Fig.#Vent Damper Installation LocationMounting Installing the Vent Damper in Horizontal & Vertical VentD80D General Wiring Diagram Vent Damper Position Indicator System Schematic Ladder DiagramVent Damper Operation Flair DamperConnection Diagram Water Connections & System Piping GAS Supply ConnectionsGaspressure Piping Diagrams SINGLE-ZONEPIPINGZone Heating with Indirect Domestic HOT Water Supply Multiple Zones with Zone Valves Electrical Wiring Fig.#Wiring Diagram KEY Page Page Wiring Diagram Single-Zone Taco Valve Wiring Diagram System with 3 Zone Pumps Fig. #2223.2e Wiring Diagram Standing Pilot With Low Water Cut-off Device Servicing Procedures General Location of ControlsControl BOX Component Locations Models 135 Sequence of Operation Intermittent Ignition Device IIDSTART-UPPROCEDURES What to do if YOU Smell GASHoneywell Pilot Robertshaw Pilot For Automatic Ignition ModelsSHUT-DOWNPROCEDURE To Turn OFF GAS to BoilerFor Automatic Ignition Systems Inspection Procedures Burners InspectionproceduresSafe SHUT-DOWN Tests Limit Action Flame FailureRaypak Tube Cleaning KIT RepairproceduresHeat Exchanger RE-ASSEMBLY Combustion Chamber RemovalTroubleshooting Guide Important NoticePiping ADJUSTMENT/REPLACEMENTOF Components Replacement Parts List RAYPAK, INCPage Page Page Limited Parts Warranty